Utah Admin. Code R432-12-5 - General Construction Requirements
|
TABLE 1 CONSTRUCTION REQUIREMENTS SUMMARY |
||||
|
LEVEL I |
LEVEL II |
LEVEL III |
LEVEL IV |
|
|
Number of. residents |
1 -16 |
4 -16 |
4 -16 |
4-16 |
|
Are residents Capable of Unassisted Self Preservation? |
No, they are non ambulatory non-mobile |
No, they are non ambulatory non-mobile |
Yes, they are ambulatory mobile |
Yes, they are ambulatory mobile |
|
What are resident's exit ability in an emergency |
Restricted, physical or mental disability and medical condition |
Restricted, physical or mental disability |
Restricted, chemical or physical restraints |
Not restricted |
|
Percentage of accessible rooms required |
100% |
10% or 100% if Physical Rehab. |
10% |
10% |
|
Construction Requirements code or regulation |
NFPA 101 |
NFPA 101 |
NFPA 101 |
Utah Fire Prevention Board Rule R710-3; IBC R-4 occupancy |
|
Fire rating of construction |
1 hour |
1 hour |
1 hour |
No requirement |
|
Sprinkler required? |
Yes |
Yes |
Yes |
Only if bldg.. larger than 4,500 SF |
|
Smoke detector required? |
Yes |
Yes |
Yes |
Yes |
|
Manual fire alarm required? |
Yes |
Yes |
Yes |
Yes |
|
Above 3 systems required to be interconnected |
Yes |
Yes |
Yes |
No |
|
Corridor width required |
8 feet |
6 feet` |
5 feet |
As required by IBC |
|
Resident room door width required |
44 inch |
44 inch |
36 inch |
36 inch |
|
Nurse call system required? |
Yes |
Yes |
Optional |
yes |
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.