Utah Admin. Code R432-500-27 - Provisions for Gas Usage
(1) Flammable
anesthetic agents or chemicals may not be used unless the building is properly
constructed for its use.
(2) For
gas usage in a facility, the licensee shall ensure:
(a) compressed gasses and flammable liquids
are stored safely and any compressed gas cylinders in storage are capped and
secured;
(b) oxidizing agents may
not be stored with flammables;
(c)
oxygen and flammable agents are stored away from combustibles;
(d) liquid flammable agents are stored in
metal cabinets with no more than ten gallons of any one flammable liquid or 60
gallons total of flammable liquids stored per cabinet;
(e) warning signs are posted when compressed
gasses or flammable liquids are used;
(f) equipment is available to extinguish
liquid oxygen and enriched gasses; and
(g) employees are trained in the proper use
of equipment and containment of combustions.
(3) When using oxygen, the licensee shall
ensure provision is made for the following:
(a) safe handling and storage; and
(b) facility personnel may not transfer gas
from one cylinder to another.
(4) The licensee shall test the piped oxygen
system and file a written report as follows:
(a) upon completion of initial
installation;
(b) when changes are
made to the system;
(c) when the
integrity of the system has been breached; and
(d) ensure there is a scavenging system for
evacuation of anesthetic waste gas.