Utah Admin. Code R432-6-18 - Special Design Features
(1) Building
entrances in large facilities shall be at grade level, clearly marked, and
located to minimize the need for residents to traverse other program areas. A
main facility entrance shall be designated and accessible to persons with
disabilities.
(2) Lobbies of
multi-occupancy buildings may be shared if the design precludes unrelated
traffic within or through units or suites of the licensed health care
facility.
(3) At least one building
entrance shall be accessible to persons with physical disabilities. Entrances
requiring ramps with a slope in excess of 1:20 shall have steps as well as
ramps.
(4) In Large facilities
where all resident units do not have kitchens or toilet facilities, at least
one drinking fountain or water cooler, toilet, and handwashing fixture on each
floor shall be wheelchair accessible.
(5) Each resident bedroom or sleeping room
shall have a wardrobe, closet, or locker for each resident occupying the unit.
The closet, wardrobe or locker shall have a shelf and a hanging rod, with
minimum inside dimensions of 22 inches deep by 36 inches wide by 72 inches
tall, suitable for hanging full-length garments.