Wash. Admin. Code § 296-24-92007 - Low-pressure cylinders subject to hydrostatic testing
(1)
Application. Cylinders
covered in this section are low-pressure cylinders other than those covered in
WAC 296-24-92005 through
296-24-92005(3)(o)(ii).
They differ essentially from such cylinders in that they require a periodic
hydrostatic retest which includes an internal and external examination. Defect
limits for the external examination are prescribed in WAC
296-24-92005 through
296-24-92005(3)(o)(ii),
with exceptions for aluminum cylinders shown in WAC
296-24-92007(4).
(2)Preparation for inspection.
You must purge flammable gas cylinders before being examined with a light.
Lamps used for flammable gas cylinder inspection must be explosion
proof.
(3)Internal
inspection. You must inspect cylinders internally at least every time
the cylinder is periodically retested. You must perform the examination with a
light of sufficient intensity to clearly illuminate the interior
walls.
(4)
External
inspection of aluminum cylinders. The inspection requirements of WAC
296-24-92005 through
296-24-92005(3)(o)(ii)
must be met, except as follows:
(a) You must reject aluminum cylinders when
impairment to the surface (corrosion or mechanical defect) exceeds a depth
where the remaining wall is less than three-fourths of the minimum allowable
wall thickness required by the specification under which the cylinder was
manufactured.
(b) You must remove
aluminum cylinders subjected to the action of fire from service.
Notes
Order 73-5, § 296-24-92007, filed 5/9/73 and Order 73-4, § 296-24-92007, filed 5/7/73.