(1)
Definitions.
(a)
Spray-finishing
operations. Employment of methods wherein organic or inorganic materials
are utilized in dispersed form from deposit on surfaces to be coated, treated
or cleaned. Such methods of deposit may involve either automatic, manual, or
electrostatic deposition but do not include metal spraying or metallizing,
dipping, flow coating, roller coating, tumbling, centrifuging, or spray washing
and degreasing as conducted in self-contained washing and degreasing machines
or systems.
(b)
Spray
booth. Spray booths are defined and described in WAC
296-24-370
through
296-24-37007. (See
sections 103, 104, and 105 of the Standard for Spray Finishing Using Flammable
and Combustible Materials, NFPA No. 33-1969.)
(c)
Spray room. A room in which
spray-finishing operations not conducted in a spray booth are performed
separately from other areas.
(d)
Minimum maintained velocity. The velocity of air movement which
must be maintained in order to meet minimum specified requirements for health
and safety.
(2)
Location and application. Spray booths or spray rooms are to be used to enclose
or confine all operations. Spray-finishing operations must be located as
provided in sections 201 through 206 of the Standard for Spray Finishing Using
Flammable and Combustible Materials, NFPA No. 33-1969.
(3) Design and construction of spray booths.
(a) Spray booths must be designed and
constructed in accordance with WAC
296-24-370
through
296-24-37007 (see
sections 301-304 and 306-310 of the Standard for Spray Finishing Using
Flammable and Combustible Materials, NFPA No. 33-1969), for general
construction specifications.
| Note: |
For a more detailed discussion of fundamentals relating
to this subject, see ANSI Z9.2-1960. |
(i) Lights,
motors, electrical equipment and other sources of ignition must conform to the
requirements of WAC
296-24-370.
(See section 310 and chapter 4 of the Standard for Spray Finishing Using
Flammable and Combustible Materials, NFPA No. 33-1969.)
(ii) In no case must combustible material be
used in the construction of a spray booth and supply or exhaust duct connected
to it.
(b) Unobstructed
walkways must not be less than 6 1/2 feet high and must be maintained clear of
obstruction from any work location in the booth to a booth exit or open booth
front. In booths where the open front is the only exit, such exits must be not
less than 3 feet wide. In booths having multiple exits, such exits must not be
less than 2 feet wide, provided that the maximum distance from the work
location to the exit is 25 feet or less. Where booth exits are provided with
doors, such doors shall open outward from the booth.
(c) Baffles, distribution plates, and
dry-type overspray collectors must conform to the requirements of WAC
296-24-370.
(See sections 304 and 305 of the Standard for Spray Finishing Using Flammable
and Combustible Materials, NFPA No. 33-1969.)
(i)
Overspray filters must be installed and maintained in accordance
with the requirements of WAC
296-24-370,
(See section 305 of the Standard for Spray Finishing Using Flammable and
Combustible Materials, NFPA No. 33-1969), and must only be in a location easily
accessible for inspection, cleaning, or replacement.
(ii) Where effective means, independent of
the overspray filters are installed which will result in design air
distribution across the booth cross section, it is permissible to operate the
booth without the filters in place.
(d)
(i)
For wet or water-wash spray booths, the water-chamber enclosure, within which
intimate contact of contaminated air and cleaning water or other cleaning
medium is maintained, if made of steel, must be 18 gauge or heavier and
adequately protected against corrosion.
(ii)
Chambers may include scrubber spray nozzles, headers, troughs, or
other devices. Chambers must be provided with adequate means for creating and
maintaining scrubbing action for removal of particulate matter from the exhaust
air stream.
(e)
Collecting tanks must be of welded steel construction or other suitable
noncombustible material. If pits are used as collecting tanks, they must be
concrete, masonry, or other material having similar properties.
(i) Tanks must be provided with weirs,
skimmer plates, or screens to prevent sludge and floating paint from entering
the pump suction box. Means for automatically maintaining the proper water
level must also be provided. Fresh water inlets must not be submerged. They
must terminate at least one pipe diameter above the safety overflow level of
the tank.
(ii) Tanks must be so
constructed as to discourage accumulation of hazardous deposits.
(f) Pump manifolds, risers, and
headers must be adequately sized to insure sufficient water flow to provide
efficient operation of the water chamber.
(4) Design and construction of spray rooms.
(a) Spray rooms, including floors, must be
constructed of masonry, concrete, or other noncombustible material.
(b) Spray rooms must have noncombustible
fire doors and shutters.
(c) Spray
rooms must be adequately ventilated so that the atmosphere in the breathing
zone of the operator must be maintained in accordance with the requirements of
(6)(b) of this section.
(d) Spray
rooms used for production spray-finishing operations must conform to the
requirements of spray booths.
(5)
Ventilation.
(a) Ventilation
must be provided in accordance with provisions of WAC
296-24-370,
(See chapter 5 of the Standard for Spray Finishing Using Flammable or
Combustible Materials, NFPA No. 33-1969), and in accordance with the following:
(i) Where a fan plenum is used to equalize
or control the distribution of exhaust air movement through the booth, it must
be of sufficient strength or rigidity to withstand the differential air
pressure or other superficially imposed loads for which the equipment is
designed and also to facilitate cleaning. Construction specifications must be
at least equivalent to those of (5)(c) of this section.
(ii) All fan ratings must be in accordance
with Air Moving and Conditioning Association Standard Test Code for Testing Air
Moving Devices, Bulletin 210, April 1962.
(b) Inlet or supply ductwork used to
transport makeup air to spray booths or surrounding areas must be constructed
of noncombustible materials.
(i) If negative
pressure exists within inlet ductwork, all seams and joints must be sealed if
there is a possibility of infiltration of harmful quantities of noxious gases,
fumes, or mists from areas through which ductwork passes.
(ii) Inlet ductwork must be sized in
accordance with volume flow requirements and provide design air requirements at
the spray booth.
(iii) Inlet
ductwork must be so supported throughout its length to sustain at least its own
weight plus any negative pressure which is exerted upon it under normal
operating conditions.
(c)
Ducts must be so constructed as to provide structural strength
and stability at least equivalent to sheet steel of not less than the following
thickness:
DIAMETER OR GREATER DIMENSION
| (U.S. gauge) |
| Up to 8 inches inclusive ................. |
No. 24 |
| Over 8 inches to 18 inches inclusive ........ |
No. 22 |
| Over 18 inches to 30 inches inclusive ....... |
No. 20 |
| Over 30 inches ......................... |
No. 18 |
(i) Exhaust
ductwork must be adequately supported throughout its length to sustain its
weight plus any normal accumulation in interior during normal operating
conditions and any negative pressure exerted upon it.
(ii) Exhaust ductwork must be sized in
accordance with good design practice which shall include consideration of fan
capacity, length of duct, number of turns and elbows, variation in size,
volume, and character of materials being exhausted. See American National
Standard Z9.2-1960 for further details and explanation concerning elements of
design.
(iii) Longitudinal joints
in sheet steel ductwork must be either lock-seamed, riveted, or welded. For
other than steel construction, equivalent securing of joints must be
provided.
(iv) Circumferential
joints in ductwork must be substantially fastened together and lapped in the
direction of airflow. At least every fourth joint must be provided with
connecting flanges, bolted together or of equivalent fastening
security.
(v) Inspection or
clean-out doors must be provided for every nine to twelve feet of running
length for ducts up to twelve inches in diameter, but the distance between
clean-out doors may be greater for larger pipes. (See 8.3.21 of American
National Standard Z9.1-1960.) A clean-out door or doors must be provided for
servicing the fan, and where necessary, a drain shall be provided.
(vi) Where ductwork passes through a
combustible roof or wall, the roof or wall must be protected at the point of
penetration by open space or fire-resistive material between the duct and the
roof or wall. When ducts pass through fire-walls, they must be provided with
automatic fire dampers on both sides of the wall, except that three-eighth-inch
steel plates may be used in lieu of automatic fire dampers for ducts not
exceeding 18 inches in diameter.
(vii)
Ductwork used for ventilating any process covered in this
standard must not be connected to ducts ventilating any other process or any
chimney or flue used for conveying any products of combustion.
(6) Velocity and air
flow requirements.
(a) Except where a spray
booth has an adequate air replacement system, the velocity of air into all
openings of a spray booth must be not less than that specified in Table 14 for
the operating conditions specified. An adequate air replacement system is one
which introduces replacement air upstream or above the object being sprayed and
is so designed that the velocity of air in the booth cross section is not less
than that specified in Table 14 when measured upstream or above the object
being sprayed.
TABLE 14
MINIMUM MAINTAINED VELOCITIES INTO SPRAY BOOTHS
| Operating Airflow conditions for object
completely inside booth |
Crossdraft f.p.m. |
Velocities, f.p.m. |
| Design |
Range |
| Electrostatic and automatic airless operation contained
in booth without operator. |
Negligible . . . |
50 large booth 100 small booth |
50-75 75-125 |
| Air-operated guns, manual or automatic |
Up to 50 . . . . |
100 large booth 150 small booth |
75-125 125-175 |
| Air-operated guns, manual or automatic |
Up to 100 . . . |
150 large booth 200 small booth |
125-175 150-250 |
| Notes: |
(1) Attention is invited to the fact that the
effectiveness of the spray booth is dependent upon the relationship of the
depth of the booth to its height and width.
(2) Crossdrafts can be eliminated through proper
design and such design should be sought. Crossdrafts in excess of 100 fpm (feet
per minute) should not be permitted.
(3) Excessive air pressures result in loss of both
efficiency and material waste in addition to creating a backlash that may carry
overspray and fumes into adjacent work areas.
(4) Booths should be designed with velocity shown in
the column headed "Design." However, booths operating with velocities shown in
the column headed "Range" are in compliance with this standard.
|
(b)
In addition to the requirements in (6)(a) of this section the total air volume
exhausted through a spray booth must be such as to dilute solvent vapor to at
least 25 percent of the lower explosive limit of the solvent being sprayed. An
example of the method of calculating this volume is given below.
Example: To determine the lower explosive limits of the most
common solvents used in spray finishing, see Table 15. Column 1 gives the
number of cubic feet of vapor per gallon of solvent and column 2 gives the
lower explosive limit (LEL) in percentage by volume of air. Note that the
quantity of solvent will be diminished by the quantity of solids and
nonflammable contained in the finish.
To determine the volume of air in cubic feet necessary to
dilute the vapor from 1 gallon of solvent to 25 percent of the lower explosive
limit, apply the following formula:
|
Dilution volume required per gallon of
solvent
|
=
|
4 (100-LEL) (cubic feet of vapor per gallon)
____________________
|
|
LEL
|
|
Using toluene as the solvent.
(1) LEL of toluene from Table 15, column 2, is 1.4
percent.
(2) Cubic feet of vapor per gallon from Table 15,
column 1, is 30.4 cubic feet per gallon.
|
|
(3) Dilution volume required =
|
4 (100-1.4) 30.4
_________
|
=
|
8,564 cubic feet.
|
|
1.4
|
|
(4) To convert to cubic feet per minute of required
ventilation, multiply the dilution volume required per gallon of solvent by the
number of gallons of solvent evaporated per minute.
|
TABLE 15
LOWER EXPLOSIVE LIMIT OF SOME COMMONLY USED SOLVENTS
| Solvent |
Cubic feet of vapor per gallon of liquid at 70°F.
|
Lower explosive limit in percent by volume of air at
70°F. |
| Column 1 |
Column 2 |
| Acetone ........................ |
44.0 |
2.6 |
| Amyl Acetate (iso) ............... |
21.6 |
1.01
|
| Amyl Alcohol (n) ................ |
29.6 |
1.2 |
| Amyl Alcohol (iso) ............... |
29.6 |
1.2 |
| Benzene ....................... |
36.8 |
1.41
|
| Butyl Acetate (n) ................ |
24.8 |
1.7 |
| Butyl Alcohol (n) ................ |
35.2 |
1.4 |
| Butyl Cellosolve ................. |
24.8 |
1.1 |
| Cellosolve ...................... |
33.6 |
1.8 |
| Cellosolve Acetate ............... |
23.2 |
1.7 |
| Cyclohexanone .................. |
31.2 |
1.11
|
| 1,1 Dichloroethylene ............. |
42.4 |
5.6 |
| 1,2 Dichloroethylene ............. |
42.4 |
9.7 |
| Ethyl Acetate ................... |
32.8 |
2.5 |
| Ethyl Alcohol ................... |
55.2 |
4.3 |
| Ethyl Lactate .................... |
28.0 |
1.51
|
| Methyl Acetate .................. |
40.0 |
3.1 |
| Methyl Alcohol .................. |
80.8 |
7.3 |
| Methyl Cellosolve ............... |
40.8 |
2.5 |
| Methyl Ethyl Ketone ............. |
36.0 |
1.8 |
| Methyl n-Propyl Ketone ........... |
30.4 |
1.5 |
| Naphtha (VM&P) (76° Naphtha) ..................
|
22.4 |
0.9 |
| Naphtha (100° Flash) Safety Solvent-Stoddard Solvent
.................... |
23.2 |
1.1 |
| Propyl Acetate (n) ............... |
27.2 |
2.0 |
| Propyl Acetate (iso) .............. |
28.0 |
1.8 |
| Propyl Alcohol (n) ............... |
44.8 |
2.1 |
| Propyl Alcohol (iso) .............. |
44.0 |
2.0 |
| Toluene ........................ |
30.4 |
1.4 |
| Turpentine ...................... |
20.8 |
0.8 |
| Xylene (o) ...................... |
26.4 |
1.0 |
1 At 212°F.
(c)
(i)
When an operator is in a booth downstream of the object being sprayed, an
air-supplied respirator or other type of respirator certified by NIOSH under 42
C.F.R. part
84 for the material being sprayed should be used by the
operator.
(ii) Where downdraft
booths are provided with doors, such doors must be closed when spray
painting.
(7)
Make-up air.
(a) Clean fresh air, free of
contamination from adjacent industrial exhaust systems, chimneys, stacks, or
vents, must be supplied to a spray booth or room in quantities equal to the
volume of air exhausted through the spray booth.
(b) Where a spray booth or room receives
make-up air through self-closing doors, dampers, or louvers, they must be fully
open at all times when the booth or room is in use for spraying. The velocity
of air through such doors, dampers, or louvers must not exceed 200 feet per
minute. If the fan characteristics are such that the required air flow through
the booth will be provided, higher velocities through the doors, dampers, or
louvers may be used.
(c)
(i) Where the air supply to a spray booth or
room is filtered, the fan static pressure must be calculated on the assumption
that the filters are dirty to the extent that they require cleaning or
replacement.
(ii) The rating of
filters must be governed by test data supplied by the manufacturer of the
filter. A pressure gauge must be installed to show the pressure drop across the
filters. This gauge must be marked to show the pressure drop at which the
filters require cleaning or replacement. Filters must be replaced or cleaned
whenever the pressure drop across them becomes excessive or whenever the air
flow through the face of the booth falls below that specified in Table
14.
(d)
(i) Means of heating make-up air to any
spray booth or room, before or at the time spraying is normally performed, must
be provided in all places where the outdoor temperature may be expected to
remain below 55°F. for appreciable periods of time during the operation of
the booth except where adequate and safe means of radiant heating for all
operating personnel affected is provided. The replacement air during the
heating seasons must be maintained at not less than 65°F. at the point of
entry into the spray booth or spray room. When otherwise unheated makeup air
would be at a temperature of more than 10°F. below room temperature, its
temperature must be regulated as provided in section 3.6 of ANSI
Z9.2-1960.
(ii) As an alternative
to an air replacement system complying with the preceding section, general
heating of the building in which the spray room or booth is located may be
employed provided that all occupied parts of the building are maintained at not
less than 65°F. when the exhaust system is in operation or the general
heating system supplemented by other sources of heat may be employed to meet
this requirement.
(iii) No means
of heating make-up air must be located in a spray booth.
(iv) Where make-up air is heated by coal or
oil, the products of combustion must not be allowed to mix with the make-up
air, and the products of combustion must be conducted outside the building
through a flue terminating at a point remote from all points where make-up air
enters the building.
(v) Where
make-up air is heated by gas, and the products of combustion are not mixed with
the make-up air but are conducted through an independent flue to a point
outside the building remote from all points where make-up air enters the
building, it is not necessary to comply with (7)(d)(vi) of this
section.
(vi) Where make-up air to
any manually operated spray booth or room is heated by gas and the products of
combustion are allowed to mix with the supply air, the following precautions
must be taken:
(A) The gas must have a
distinctive and strong enough odor to warn workmen in a spray booth or room of
its presence if in an unburned state in the make-up air.
(B) The maximum rate of gas supply to the
make-up air heater burners must not exceed that which would yield in excess of
200 p.p.m. (parts per million) of carbon monoxide or 2,000 p.p.m. of total
combustible gases in the mixture if the unburned gas upon the occurrence of
flame failure were mixed with all of the make-up air supplied.
(C) A fan must be provided to deliver the
mixture of heated air and products of combustion from the plenum chamber
housing the gas burners to the spray booth or room.
(8) Scope. Spray booths
or spray rooms are to be used to enclose or confine all spray finishing
operations covered by this paragraph. This paragraph does not apply to the
spraying of the exteriors of buildings, fixed tanks, or similar structures, nor
to small portable spraying apparatus not used repeatedly in the same
location.