010-3 Wyo. Code R. §§ 3-23 - Air Blower and Air Induction Systems; Entry Devices
(a) This section pertains to all devices and
systems which induce or allow air to enter the spa either by means of a power
pump or passive design.
(i) Air intake
sources shall not:
(A) Induce water external
to the spa unit; and
(B) Induce
dirt or contaminants into the spa.
(ii) An air blower installed within an
enclosure or indoors shall:
(A) Be provided
with adequate ventilation;
(B) Be
installed in accordance with any federal, state or local codes;
(C) Be installed according to the
manufacturer's recommendations; and
(D) Be accessible for inspection and
service.
(b)
Integral air passages shall be pressure tested at the time of manufacture to
provide structural integrity to a value of one and one-half (11/2) times the
intended working pressure.
(c) An
air induction system shall totally prevent water back-up that could cause
electrical shock hazards.
(d) A
hydrotherapy pump and air blower in a spa pool shall be connected to a maximum
fifteen (15) minute time switch located no closer than ten (10) feet (3m) from
the spa water's edge.
(e) Air
blower and air induction systems must be separate from the recirculation
system.