Ariz. Admin. Code § R18-12-231 - Operation and Maintenance of Corrosion Protection
A. A corrosion protection system shall be
operated and maintained to continuously provide corrosion protection to the
metal components of an UST system which are subject to the corrosion protection
requirements of
R18-12-220 and
R18-12-221 and to piping which
routinely contains regulated substances and is in contact with the
ground.
B. An UST system equipped
with cathodic protection systems shall be inspected for proper operation by a
qualified cathodic protection tester. Owners and operators shall ensure
compliance with both of the following requirements:
1. A cathodic protection system shall be
tested within six months of installation and at least every three years
thereafter,
2. The criteria that
are used to determine that cathodic protection is adequate as required by this
Section shall be in accordance with the codes of practice set forth in
R18-12-281(J).
C. An UST system with an impressed current
cathodic protection system, in addition to meeting the requirements of
subsections (A) and (B) shall be inspected every 60 days to ensure the
equipment is operating in accordance with its design specifications.
D. For an UST system using cathodic
protection, records of the operation of the cathodic protection shall be
maintained in accordance with
R18-12-234 to demonstrate
compliance with the performance standards in this Section and
R18-12-281(J) .
These records shall provide the following:
1.
The results of testing from the last two inspections required by subsection
(B),
2. The results of the last
three inspections required by subsection (C).
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.