A. Owners and operators of a new UST system
shall meet the requirements described in this Section in order to prevent
releases due to structural failure, corrosion, or spills and overfills for as
long as the UST system is used to store regulated substances. In addition,
except for suction piping that meets the requirements of
R18-12-241(C)(2)(a) through
(e), tanks and piping installed or replaced
after January 1, 2009 shall be secondarily contained and use interstitial
monitoring in accordance with
R18-12-243(G) .
Secondary contain, be able to contain regulated substances leaked from the
primary containment until they are detected and removed and pre-vent the
release of regulated substances to the environment at any time during the
operational life of the UST system. For cases where the piping to be replaced
exceeds the percentage in A.R.S. §
49-1009(C), the
entire piping run shall be secondarily contained.
B. A tank shall be properly designed and
constructed, and any portion underground that routinely contains a regulated
substance shall be protected from corrosion in accordance with a code of
practice developed by a nationally recognized association or independent
testing laboratory as specified below:
1. The
tank is constructed of fiberglass-reinforced plastic. Compliance with this
subsection may be determined in accordance with the performance standards set
forth in
R18-12-281(B);
2. The tank is constructed of steel and is
cathodically protected, in accordance with one of the performance standards of
R18-12-281(C), by
all of the following:
a. The tank is coated
with a suitable dielectric material;
b. The field-installed cathodic protection
systems are designed by a corrosion expert;
c. The impressed current systems, if used,
are designed to allow determination of current operating status as required in
R18-12-231(C);
d. The cathodic protection systems are
operated and maintained in accordance with
R18-12-231.
3. The tank is constructed of steel and clad
or jacketed with a non-corrodible material. Compliance with this subsection
shall be determined in accordance with one of the performance standards set
forth in
R18-12-281(D).
4. The tank is constructed of metal without
additional corrosion protection measures, and both of the following conditions
are met:
a. The tank is installed at a site
that is determined by a corrosion expert not to be corrosive enough to cause it
to have a release due to corrosion during its operating life;
b. Owners and operators maintain records that
demonstrate compliance with the requirements of subsection (B)(4)(a) for the
remaining operational life of the tank.
5. The tank construction and corrosion
protection are determined by the Department to be designed to prevent the
release or threatened release of any stored regulated substance in a manner
that is no less protective of human health and the environment than the
requirements of subsections (B)(1) through (4).
C. The piping that routinely contains
regulated substances and is in contact with the ground shall be properly
designed, constructed, and protected from corrosion in accordance with a code
of practice developed by a nationally recognized association or independent
testing laboratory as specified below:
1. The
piping is constructed of non-corrodible material. Compliance with this
subsection may be determined in accordance with the performance standard set
forth in
R18-12-281(E).
2. The piping is constructed of steel and in
meeting the performance standards of
R18-12-281(F) is
cathodically protected according to all of the following:
a. The pipmg is coated with a suitable
dielectric material;
b.
Field-installed cathodic protection systems are designed by a corrosion
expert;
c. Impressed current
systems, if used, are designed to allow determination of current operating
status as required in
R18-12-231(C);
d. Cathodic protection systems are operated
and maintained in accordance with
R18-12-231.
3. The piping is constructed of metal without
additional corrosion protection measures, and all of the following requirements
are satisfied:
a. The piping is installed at a
site that is determined by a corrosion expert to not be corrosive enough to
cause it to have a release due to corrosion during its operating life;
b.
The piping meets the performance standards of R18
12281(G);
c
b. Owners and operators
maintain records that demonstrate compliance with the requirements of
subsection (a) for the remaining life of the piping.
4. The piping construction and corrosion
protection are determined by the Department to be designed to prevent the
release or threatened release of any stored regulated substance in a manner
that is no less protective of human health and the environment than the
requirements in subsections (C)(1) through (3).
D. Except as provided in subsections D)(3)
and (D)(4), owners and operators shall use both of the following spill and
overfill prevention equipment systems to prevent spilling and overfilling
associated with transfer of a regulated substance to the UST system:
1. Spill prevention equipment that will
prevent release of a regulated substance to the environment when the transfer
hose is detached from the fill pipe;
2. Overfill prevention equipment that will do
one or more of the following:
a. Automatically
shut off flow into the tank when the tank is no more than 95% full;
b. Alert the transfer operator when the tank
is no more than 90% full by restricting the flow into the tank or triggering a
high-level alarm that can be heard at the point of transfer;
c. Restrict flow 30 minutes prior to
overfilling, alert the operator with a high level alarm that can be heard at
the point of transfer one minute before overfilling, or automatically shut off
flow into the tank so that none of the fittings located on top of the tank are
exposed to a regulated substance due to overfilling.
3. Owners and operators are not required to
use the spill and overfill prevention equipment specified in subsections (D)(1)
and (2) if either of the following conditions is met:
a. Alternative equipment is used that is
determined by the Department to be no less protective of human health and the
environment than the equipment specified in subsections (D)(1) or
(2);
b. The tank is filled by
transfers of no more than 25 gallons at one time.
4. Flow restrictors used in vent lines may
not be used to comply with subsection (D)(2) of this Section when overfill
prevention is installed or replaced.
5. Spill and overfill prevention equipment
shall be periodically tested or inspected in accordance with
R18-12-235.
E. The UST system shall
1. be properly installed
in accordance with the manufacturer's instructions
2. and in accordance with
a code of practice developed by a nationally recognized association or
independent testing laboratory, such as those listed in
R18-12-281(G).
F. Owners and operators shall
ensure, in addition to the installation being inspected and approved by the
Department under
R18-12-219, that one or more of
the following methods of certification, testing, or inspection is used to
demonstrate compliance with subsection (E):
1. The installer has been certified by the
tank and piping manufacturers,
2.
The installation has been inspected and certified by a registered professional
engineer with education and experience in UST system installation, or
3.
The installation has been inspected and approved by
the Department,
4
3. All work listed in
the manufacturer's installation checklists has been completed, or
4. Owners and operators have complied with
another method for ensuring compliance with subsection (E) that is determined
by the Department to be no less protective of human health and the
environment.
G.
Under-dispenser containment. Each UST system shall be equipped with
under-dispenser containment for any new dispenser installed or replaced after
January 1, 2009. Under-dispenser containment shall be liquid-tight on its
sides, bottom, and at any penetrations. Under-dispenser containment shall allow
for visual inspection and access to the components in the containment system or
be periodically monitored for leaks from the dispenser system.
H. Notwithstanding subsection (G), under
dispenser containment is only required when a new dispenser system is installed
if the requirement for under dispenser containment in A.R.S. §
49-1009(D) is
changed to apply only to new dispenser system installation. A dispenser system
is considered new when both the dispenser and the equipment needed to connect
the dispenser to the underground storage tank system are installed at an UST
facility. The equipment necessary to connect the dispenser to the underground
storage tank system includes check valves, shear valves, unburied risers or
flexible connectors, or other transitional components that are underneath the
dispenser and connect the dispenser to the underground piping.
G
I.
Owners shall provide a certification of compliance on the UST Notification Form
in accordance with
R18-12-222(D)
and shall ensure that a certification statement in accordance with the
applicable requirements of
R18-12-222(E) is
signed by the installer on the Notification Form prior to submission to the
Department.
H.
If an UST system is installed or modified to meet
the requirements of this Section, owners shall notify the Department in
accordance with R18-12222(F)(2) within 30 days of the date that the UST system
is brought into operation or modified.