A. Exception to piping secondary containment
requirements. Owners and operators may use single walled piping when installing
or replacing piping associated with UST systems with field-constructed tanks
greater than 50,000 gallons and piping associated with airport hydrant
systems.
B. Piping associated with
UST systems with field-constructed tanks less than or equal to 50,000 gallons
not part of an airport hydrant system shall meet the secondary containment
requirement when installed or replaced. Where the piping to be replaced exceeds
the percentage in A.R.S. §
49-1009(C), the
entire piping run shall be secondarily contained.
C. Upgrade requirements. Airport hydrant
systems and UST systems with field-constructed tanks shall meet the following
requirements or be permanently closed pursuant to
R18-12-270 through
R18-12-274 .
1. Corrosion protection. UST system
components in contact with the ground that routinely contain regulated
substances shall meet one of the following:
a.
Except as provided in subsection (A) of this Section, the new UST system
performance standards for tanks at
R18-12-220(A) and
for piping at
R18-12-220(B);
or
b. Be constructed of metal and
cathodically protected according to a code of practice developed by a
nationally recognized association or independent testing laboratory and meets
the following:
i. Cathodic protection shall
meet the requirements of
R18-12-220(A)(2)(ii),
(iii) and (iv) for tanks, and
R18-12-220(B)(2)(ii),
(iii), and (iv) for piping.
ii.
Tanks greater than 10 years old without cathodic protection shall be assessed
to ensure the tank is structurally sound and free of corrosion holes prior to
adding cathodic protection. The assessment shall be by internal inspection or
another method determined by the Department to adequately assess the tank for
structural soundness and corrosion holes.
Note to subsection (C)(1): The following codes of practice
may be used to comply with this subsection:
(A) NACE International Standard Practice
SP0285-2011, "Corrosion Control of Underground Storage Tank Systems by Cathodic
Protection";
(B) NACE International
Standard Practice SP0169-2013, "Control of External Corrosion on Underground or
Submerged Metallic Piping Systems";
(C) National Leak Prevention Association
Standard 631, Chapter C, "Internal Inspection of Steel Tanks for Retrofit of
Cathodic Protection", 2009 revision; or
(D) American Society for Testing and
Materials Standard G158-98, "Standard Guide for Three Methods of Assessing
Buried Steel Tanks".
2. Spill and overfill prevention equipment.
To prevent spilling and overfilling associated with product transfer to the UST
system, all UST systems with field-constructed tanks and airport hydrant
systems shall comply with new UST system spill and overfill prevention
equipment requirements specified in
R18-12-220(C).
D. Walkthrough inspections. In addition to
the walkthrough inspection requirements in
R18-12-236, owners and operators
shall inspect the following additional areas for airport hydrant systems at
least once every 30 days if confined space entry according to the Occupational
Safety and Health Administration (see 29 CFR part
1910) is not required or at
least annually if confined space entry is required and keep documentation of
the inspection according to
R18-12-236(B) .
1. Hydrant pits - visually check for any
damage; remove any liquid or debris; and check for any leaks, and
2. Hydrant piping vaults - check for any
hydrant piping leaks.
E.
Release detection. Owners and operators of UST systems with field-constructed
tanks and airport hydrant systems shall meet the release detection requirements
described in this Article as follows:
1.
Methods of release detection for field-constructed tanks. Owners and operators
of field-constructed tanks with a capacity less than or equal to 50,000 gallons
shall meet the release detection requirements in
R18-12-240 through
R18-12-245 . Owners and operators
of field-constructed tanks with a capacity greater than 50,000 gallons shall
meet either the requirements in
R18-12-240 through
R18-12-245 (except
R18-12-243(E) and
(F) shall be combined with inventory control
as stated below) or use one or a combination of the following alternative
methods of release detection:
a. Conduct an
annual tank tightness test that can detect a 0.5 gallon per hour leak
rate;
b. Use an automatic tank
gauging system to perform release detection at least every 30 days that can
detect a leak rate less than or equal to one gallon per hour. This method shall
be combined with a tank tightness test that can detect a 0.2 gallon per hour
leak rate performed at least every three years;
c. Use an automatic tank gauging system to
perform release detection at least every 30 days that can detect a leak rate
less than or equal to two gallons per hour. This method shall be combined with
a tank tightness test that can detect a 0.2 gallon per hour leak rate performed
at least every two years;
d.
Perform vapor monitoring (conducted in accordance with
R18-12-243(E)
for a tracer compound placed in the tank system) capable of detecting a 0.1
gallon per hour leak rate at least every two years;
e. Perform inventory control (conducted in
accordance with Department of Defense Directive 4140.25-M, volume 9; ATA
Airport Fuel Facility Operations and Maintenance Guidance Manual, revision
2004.1; or equivalent procedures) at least every 30 days that can detect a leak
equal to or less than 0.5 percent of flow-through; and
i. Perform a tank tightness test that can
detect a 0.5 gallon per hour leak rate at least every two years; or
ii. Perform vapor monitoring or groundwater
monitoring (conducted in accordance with
R18-12-243(E) or
(F), respectively, for the stored regulated
substance) at least every 30 days; or
f. Another method approved by the Department
if the owner and operator can demonstrate that the method can detect a release
as effectively as any of the methods allowed in subsections (E)(1)(a) through
(e) of this Section. In comparing methods, the Department shall consider the
size of release that the method can detect and the frequency and reliability of
detection.
2. Methods of
release detection for piping. Owners and operators of underground piping
associated with field-constructed tanks less than or equal to 50,000 gallons
shall meet the release detection requirements in
R18-12-240 through
R18-12-245 . Owners and operators
of underground piping associated with airport hydrant systems and
field-constructed tanks greater than 50,000 gallons shall follow either the
requirements in
R18-12-240 through
R18-12-245 (except
R18-12-243(E) and
(F) shall be combined with inventory control
as stated below) or use one or a combination of the following alternative
methods of release detection:
i. Perform a
semiannual or annual line tightness test at or above the piping operating
pressure in accordance with the table below.
|
Maximum Leak Detection Rate Per Test Section
Volume
|
|
Test Section Volume (Gallons)
|
Semiannual Test -Leak Detection Rate Not To Exceed
(Gallons Per Hour)
|
Annual Test - Leak Detection Rate Not To Exceed
(Gallons Per Hour)
|
|
< 50,000
|
1.0
|
0.5
|
|
>= 50,000 to < 75,000
|
1.5
|
0.75
|
|
>= 75,000 to < 100,000
|
2.0
|
1.0
|
|
>= 100,000
|
3.0
|
1.5
|
ii.
Piping segment volumes >=100,000 gallons not capable of meeting the maximum
3.0 gallon per hour leak rate for the semiannual test may be tested at a leak
rate up to 6.0 gallons per hour according to the following schedule:
|
Phase In For Piping Segments >= 100,000
Gallons In Volume
|
|
First test
|
Not later than March 1, 2020 (may use up to 6.0 gph
leak rate)
|
|
Second test
|
Between March 1, 2020 and March 1, 2023 (may use up
to 6.0 gph leak rate)
|
|
Third test
|
Between March 1, 2023 and March 1, 2024 (may use up
to 3.0 gph leak rate)
|
|
Subsequent tests
|
After March 1, 2024, begin using semiannual or annual
line testing according to the Maximum Leak Detection Rate Per Test Section
Volume table above
|
b. Perform
vapor monitoring (conducted in accordance with
R18-12-243(E)
for a tracer compound placed in the tank system) capable of detecting a 0.1
gallon per hour leak rate at least every two years;
c. Perform inventory control (conducted in
accordance with Department of Defense Directive 4140.25m, volume 9; ATA Airport
Fuel Facility Operations and Maintenance Guidance Manual, revision 2004.1; or
equivalent procedures) at least every 30 days that can detect a leak equal to
or less than 0.5 percent of flow-through; and
i. Perform a line tightness test (conducted
in accordance with subsection (D)(2)(a) of this Section using the leak rates
for the semiannual test) at least every two years; or
ii. Perform vapor monitoring or groundwater
monitoring (conducted in accordance with
R18-12-243(E) or
(F), respectively, for the stored regulated
substance) at least every 30 days; or
d. Another method approved by the Department
if the owner and operator can demonstrate that the method can detect a release
as effectively as any of the methods allowed in subsections (E)(2)(a) through
(c) of this Section. In comparing methods, the Department shall consider the
size of release that the method can detect and the frequency and reliability of
detection.
3.
Recordkeeping for release detection. Owners and operators shall maintain
release detection records according to the recordkeeping requirements in
R18-12-245.
F. Applicability of closure requirements to
previously closed UST systems. When directed by the Department, the owner and
operator of an UST system with field-constructed tanks or airport hydrant
system permanently closed before January 1, 2020 shall assess the excavation
zone and close the UST system in accordance with
R18-12-270 through
R18-12-274 if releases from the
UST may, in the judgment of the Department, pose a current or potential threat
to human health and the environment.