Cal. Code Regs. Tit. 19, § 568 - Fire Extinguisher Size and Placement for Class a Hazards
Table 2
|
Light (Low) Hazard Occupancy |
Ordinary (Moderate) Hazard Occupancy |
Extra (High) Hazard Occupancy |
|
|
Minimum rated single extinguisher |
2-A |
2-A |
4-A* |
|
Maximum floor area per unit of A |
3,000 sq ft |
1,500 sq ft |
1,000 sq ft |
|
Maximum floor area for extinguisher |
11,250 sq ft |
11,250 sq ft |
11,250 sq ft |
|
Maximum travel distance to extinguisher |
75 ft |
75 ft |
75 ft |
* Two 2 1/2 gal (9.46 L) water type extinguishers can be used to fulfill the requirement of one 4-A rated extinguisher.
NOTE: 1 ft = 0.305 m
1 sq ft = 0.0929 m2
Notes
2. Amendment of subsections (a) and (b) filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
3. Change without regulatory effect amending subsection (c) filed 7-25-2006 pursuant to section 100, title 1, California Code of Regulations (Register 2006, No. 30).
4. Amendment of subsections (a) and (b) filed 2-28-2007; operative 3-30-2007 (Register 2007, No. 9).
Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
2. Amendment of subsections (a) and (b) filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
3. Change without regulatory effect amending subsection (c) filed 7-25-2006 pursuant to section 100, title 1, California Code of Regulations (Register 2006, No. 30).
4. Amendment of subsections (a) and (b) filed 2-28-2007; operative 3-30-2007 (Register 2007, No. 9).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.