Fla. Admin. Code Ann. R. 62-555.350 - Operation and Maintenance of Public Water Systems
(1) Suppliers of water shall operate and
maintain their public water systems so as to comply with applicable standards
in Chapter 62-550, F.A.C., and requirements in this chapter.
(2) Suppliers of water shall keep all
necessary public water system components in operation and shall maintain such
components in good operating condition so the components function as intended.
Preventive maintenance on electrical or mechanical equipment - including
exercising of auxiliary power sources, checking the calibration of
finished-drinking-water meters at treatment plants, testing of air or pressure
relief valves for hydropneumatic tanks, and exercising of isolation valves -
shall be performed in accordance with the equipment manufacturer's
recommendations or in accordance with a written preventive maintenance program
established by the supplier of water; however, in no case shall auxiliary power
sources be run under load less frequently than monthly. Accumulated sludge and
biogrowths shall be cleaned routinely (i.e., at least annually) from all
treatment facilities that are in contact with raw, partially treated, or
finished drinking water and that are not specifically designed to collect
sludge or support a biogrowth; and blistering, chipped, or cracked coatings and
linings on treatment or storage facilities in contact with raw, partially
treated, or finished drinking water shall be rehabilitated or repaired.
Finished-drinking-water storage tanks, including conventional hydropneumatic
tanks with an access manhole but excluding bladder- or diaphragm-type
hydropneumatic tanks without an access manhole, shall be checked at least
annually to ensure that hatches are closed and screens are in place; shall be
cleaned at least once every five years to remove biogrowths, calcium or
iron/manganese deposits, and sludge from inside the tanks; and shall be
inspected for structural and coating integrity at least once every five years
by personnel under the responsible charge of a professional engineer licensed
in Florida. Dead-end water mains conveying finished drinking water shall be
flushed quarterly or in accordance with a written flushing program established
by the supplier of water; additionally, dead-end or other water mains conveying
finished water shall be flushed as necessary whenever legitimate water quality
complaints are received.
(3)
Suppliers of water shall ensure that drinking water treatment chemicals conform
to the standards referenced in paragraph
62-555.320(3)(a),
F.A.C., and shall have their lead/chief water treatment plant operators certify
in writing on the monthly operation reports required under subsection (12),
below, that drinking water treatment chemicals conform to the standards
referenced in paragraph
62-555.320(3)(a),
F.A.C. Lead/chief water treatment plant operators may base their certifications
upon evaluations conducted by the supplier of water or upon third-party or
manufacturer certifications.
(4) No
supplier of water shall operate any drinking water treatment plant at a
capacity greater than the plant's permitted operating capacity except with the
Department's prior approval, which shall be given when such operation will not
cause a violation of a maximum contaminant level, a treatment technique
requirement, or other operating requirements and is for no more than three
months, or under circumstances that the supplier of water documents as highly
unusual and nonrecurring. The permitted operating capacity of each plant shall
be as specified in the latest Department of Environmental Protection (DEP)
construction permit concerning source water or treatment facilities for the
plant. In cases where no permitted operating capacity has been specified in the
latest DEP construction permit concerning source water or treatment facilities
for a plant, the Department shall establish the permitted maximum-day operating
capacity of the plant and, if the plant is designed to meet peak water demand
or to supplement finished-water storage facilities in meeting peak water
demand, the permitted peak operating capacity of the plant based upon
information that is included in or with pertinent permit applications or that
is provided by the supplier of water and based upon design requirements in part
III of this chapter, including design requirements in the engineering
references listed in Rule
62-555.330, F.A.C. Each day that
a supplier of water is required under Chapter 62-699, F.A.C., to have a
licensed operator staff or visit a plant, the supplier of water shall measure
and record in the logs and reports required under subsection (12), below, the
net quantity of finished drinking water, excluding any filter backwash water,
produced by the plant.
(5)
Suppliers of water who are using ground water not under the direct influence of
surface water and who are required to provide treatment to reliably achieve at
least four-log inactivation or removal of viruses in accordance with paragraph
62-555.320(12)(b),
F.A.C., shall monitor, record, and maintain the effectiveness and reliability
of disinfection treatment as described in paragraphs (a) through (c), below.
The residual disinfectant, temperature, or pH measurements required under
paragraph (a) or (b), may be performed by any authorized representative of the
supplier of water; but field measurements of residual chlorine, temperature,
and pH shall be performed following the appropriate procedures in the
Department of Environmental Protection Standard Operating Procedures for Field
Activities, DEP-SOP-001/01, as incorporated into Rule
62-160.800, F.A.C., and all
other measurements shall be performed using an appropriate method referenced in
subsection 62-550.550(1),
F.A.C., or in Standard Methods for the Examination of Water and
Wastewater as adopted in Rule
62-555.335, F.A.C.
(a) For each day a supplier of water serving
3,300 or more persons serves water to the public from a drinking water
treatment plant that includes chemical disinfection for virus inactivation, the
supplier of water shall continuously monitor the residual disinfectant
concentration (C) before or at the first customer and shall record in the logs
and reports required under subsection (12), below, the lowest C measured before
or at the first customer during peak flow, the corresponding disinfectant
contact time (T) at the C monitoring point during peak flow, and the resulting
lowest CT provided before or at the first customer during peak flow. In
addition, at least once for each day the supplier of water serves water to the
public from the plant, the supplier of water shall measure and record the
temperature of the water at the point where C is monitored; shall measure and
record the pH of the water at the point where C is monitored if free chlorine
is being used for virus inactivation; and with this temperature and pH
information, shall determine and record the minimum CT required to comply with
paragraph 62-555.320(12)(b),
F.A.C. If there is a failure of equipment used to continuously monitor C, the
supplier of water may temporarily monitor C by taking grab samples every four
hours but may do so for no more than one week following the equipment failure.
If at any time the "CT provided" falls below the minimum CT required, the
supplier of water shall increase the disinfectant dose until the "CT provided"
is at least equal to the minimum CT required and shall notify the Department in
accordance with subsection (10), below.
(b) For each day a supplier of water serving
less than 3,300 persons serves water to the public from a drinking water
treatment plant that includes chemical disinfection for virus inactivation, the
supplier of water shall monitor the residual disinfectant concentration (C)
before or at the first customer by taking at least one grab sample during peak
flow and shall record in the logs and reports required under subsection (12),
below, the lowest C measured before or at the first customer during peak flow,
the corresponding disinfectant contact time (T) at the C monitoring point
during peak flow, and the resulting CT provided before or at the first customer
during peak flow. In addition, at least once for each day the supplier of water
serves water to the public from the plant, the supplier of water shall measure
and record the temperature of the water at the point where C is monitored;
shall measure and record the pH of the water at the point where C is monitored
if free chlorine is being used for virus inactivation; and with this
temperature and pH information, shall determine and record the minimum CT
required to comply with paragraph
62-555.320(12)(b),
F.A.C. If any measurement of the "CT provided" falls below the minimum CT
required, the supplier of water shall increase the disinfectant dose and take
follow-up grab samples at least every four hours until the "CT provided" is at
least equal to the minimum CT required and shall notify the Department in
accordance with subsection (10), below.
(c) For each day a supplier of water serves
water to the public from a drinking water treatment plant that includes
ultraviolet (UV) disinfection for virus inactivation, the supplier of water
shall continuously monitor the operating UV dose and shall record in the logs
and reports required under subsection (12), below, the lowest operating UV dose
measured. If at any time the operating UV dose falls below the minimum UV dose
required to comply with paragraph
62-555.320(12)(b),
F.A.C., the supplier of water shall clean the UV lamp sleeves or replace the UV
lamps to restore the operating UV dose to a level at least equal to the
required minimum UV dose and shall notify the Department in accordance with
subsection (10), below.
(6) Suppliers of water shall maintain a
minimum free chlorine residual of 0.2 milligram per liter, or a minimum
combined chlorine residual of 0.6 milligram per liter or an equivalent chlorine
dioxide residual, throughout their drinking water distribution system at all
times. If at any time the residual disinfectant concentration in any portion of
a distribution system falls below the required minimum level, the supplier of
water shall increase the disinfectant dose as necessary and flush said portion
of the distribution system until the residual disinfectant concentration is
restored to the required minimum level. Suppliers of water shall monitor and
record the residual disinfectant concentration in their distribution system as
described in paragraphs (a) and (b), below. The residual disinfectant
measurements required under paragraph (a) or (b), may be performed by any
authorized representative of the supplier of water; but field measurements of
chlorine residual shall be performed following the appropriate procedures in
the Department of Environmental Protection Standard Operating Procedures for
Field Activities, DEP-SOP-001/01, as incorporated into Rule
62-160.800, F.A.C., and all
other measurements shall be performed using an appropriate method referenced in
subsection 62-550.550(1),
F.A.C.
(a) Each supplier of water serving
3,300 or more persons shall take at least one grab sample each day the supplier
serves water to the public or at least five days per week, whichever is less,
at a point in the water supplier's distribution system reflecting maximum
residence time after disinfectant addition, shall measure the residual
disinfectant concentration, and shall record the residual disinfectant
concentration in the logs and reports required under subsection (12),
below.
(b) Each supplier of water
serving less than 3,300 persons shall take at least one grab sample each day
the supplier serves water to the public or at least two days per week,
whichever is less, at a point in the water supplier's distribution system
reflecting maximum residence time after disinfectant addition, shall measure
the residual disinfectant concentration, and shall record the residual
disinfectant concentration in the logs and reports required under subsection
(12), below.
(7) Except
when a water main breaks or treatment or pumping equipment fails and except
under circumstances that the supplier of water documents to be highly unusual
and nonrecurring, suppliers of water shall maintain a minimum gauge pressure of
20 pounds per square inch throughout their drinking water distribution system
up to each customer's point of connection to the water supplier's distribution
system.
(8) Suppliers of water
shall employ licensed operation personnel in accordance with Chapters 62-602
and 62-699, F.A.C., for all public water systems except transient non-community
water systems using only ground water and serving only businesses other than
public food service establishments as defined in, and regulated under, Chapter
381, 500, or 509, F.S.
(9) No
supplier of water shall alter or replace underground portions of, or abandon,
any public water system well without first obtaining a permit from the
appropriate water management district or delegated permitting authority if such
a permit is required under Chapter 62-532, F.A.C. In addition, no supplier of
water shall introduce a new source of water into any public water system;
alter, or discontinue use of, any public water system components other than
wells (but including well pumping equipment and appurtenances); or alter the
type of chemicals being used to treat drinking water without first obtaining a
construction permit or written approval from the Department if such a permit or
such approval is required under subsection
62-555.520(1),
F.A.C., or first submitting written notification to the Department if such
notification is required under subsection
62-555.520(1),
F.A.C.
(10) Suppliers of water
shall notify the State Warning Point (SWP), the appropriate Department of
Environmental Protection (DEP) District Office or Approved County Health
Department (ACHD), and water customers in accordance with the following
procedures in the event of the following circumstances.
(a) Suppliers of water shall telephone the
SWP at 1(800)320-0519 immediately (i.e., within two hours) after discovery of
any actual or suspected sabotage or security breach, or any suspicious
incident, involving a public water system.
(b) Suppliers of water shall telephone, and
speak directly to a person at, the appropriate DEP District Office or ACHD as
soon as possible, but never later than noon of the next business day, in the
event of any of the following emergency or abnormal operating conditions:
1. The occurrence of any abnormal color,
odor, or taste in a public water system's raw or finished water,
2. The failure of a public water system to
comply with applicable disinfection requirements, or
3. The breakdown of any water treatment or
pumping facilities, or the break of any water main, in a public water system if
the breakdown or break is expected to adversely affect finished-water quality,
interrupt water service to 150 or more service connections or 350 or more
people, interrupt water service to any one service connection for more than
eight hours, or necessitate the issuance of a precautionary "boil water" notice
in accordance with the Department of Health's "Guidelines for the Issuance of
Precautionary Boil Water Notices" as adopted in Rule
62-555.335, F.A.C.
(c) Suppliers of water shall
notify the appropriate DEP District Office or ACHD and affected water customers
by no later than the previous business day before initiating any planned
permanent or temporary conversion from free chlorine to chloramines or vice
versa for disinfection. Notices to the appropriate DEP District Office or ACHD
shall be delivered by telephoning, and speaking directly to a person at, the
DEP District Office or ACHD, and notices to affected water customers shall be
delivered in writing or via telephone, newspaper, radio, or television. A
single notice may be provided to cover both a planned temporary conversion from
chloramines to free chlorine and the planned subsequent conversion back to
chloramines. Notification is not required before unplanned temporary
conversions from chloramines to free chlorine to protect public health during
emergency operating conditions caused by circumstances such as source water
contamination, water main breaks, or backflow incidents.
(d) Suppliers of water shall notify affected
water customers in writing or via telephone, newspaper, radio, or television by
no later than the previous business day before taking public water system (PWS)
components out of operation for planned maintenance or repair work if the work
is expected to adversely affect finished-water quality or interrupt water
service to any service connection. Additionally, suppliers of water shall
telephone, and speak directly to a person at, the appropriate DEP District
Office or ACHD by no later than the previous business day before taking PWS
components out of operation for planned maintenance or repair work if the work
is expected to adversely affect finished-water quality, interrupt water service
to 150 or more service connections or 350 or more people, interrupt water
service to any one service connection for more than eight hours, or necessitate
the issuance of a precautionary "boil water" notice in accordance with the
Department of Health's "Guidelines for the Issuance of Precautionary Boil Water
Notices" as adopted in Rule
62-555.335, F.A.C.
(e) Suppliers of water shall describe in the
monthly operation reports required under subsection (12), below, all emergency
or abnormal operating conditions and all maintenance or repair work that
involves taking out of operation public water system components other than
water service lines.
(11) Suppliers of water shall issue
precautionary "boil water" notices as required or recommended in the Department
of Health's "Guidelines for the Issuance of Precautionary Boil Water Notices"
as adopted in Rule 62-555.335, F.A.C.
(12) Suppliers of water shall keep and submit
operation and maintenance logs, reports, and records as described below.
(a) All suppliers of water shall keep
operation and maintenance logs at their drinking water treatment plants. For
plants that are part of a transient non-community water system using only
ground water and serving only businesses other than public food service
establishments, the operation and maintenance logs shall contain a minimum of
three months of data at all times and shall contain the date and type of all
maintenance performed and the date and results of all sampling and analyses
performed unless the sampling or analyses are documented on a laboratory sheet.
For all other plants, the operation and maintenance logs shall contain the
information listed in, and shall be maintained as described in, subsection
62-602.650(4),
F.A.C.
(b) For all public water
systems except transient non-community water systems using only ground water
and serving only businesses other than public food service establishments,
suppliers of water shall submit monthly operation reports to the appropriate
Department of Environmental Protection District Office or Approved County
Health Department within ten days after each month of operation per paragraph
62-550.730(1)(d),
F.A.C., and shall do so using the following forms as applicable: Form
62-555.900(2),
Monthly Operation Report for Subpart H Systems as incorporated into paragraph
62-550.817(11)(a),
F.A.C.; Form 62-555.900(3),
Monthly Operation Report for PWSs Treating Raw Ground Water or Purchased
Finished Water, hereby adopted and incorporated by reference, effective August
28, 2003; Form 62-555.900(4),
Monthly Operation Report for Consecutive Systems that Do Not Treat Water,
hereby adopted and incorporated by reference, effective August 28, 2003; Form
62-555.900(6),
Monthly Operation Report for Consecutive Systems that Receive Purchased
Finished Water from a Subpart H System as incorporated into paragraph
62-550.817(11)(b),
F.A.C.; Form 62-555.900(11),
Monthly Operation Report for Summation of Finished-Water Production by CWSs
that Have Multiple Treatment Plants, hereby adopted and incorporated by
reference, effective August 28, 2003; Form
62-555.350(12)(b),
Supplemental Monthly Operation Report for PWS Receiving Advanced Treated Water,
hereby adopted and incorporated by reference, effective February 26, 2025
(http://www.flrules.org/Gateway/reference.asp?No=Ref-17752).
Copies of these forms are available from the Department of Environmental
Protection Drinking Water Section, M.S. #3520, 2600 Blair Stone Road,
Tallahassee, Florida 32399-2400. Suppliers of water shall keep copies of
monthly operation reports, together with any additional operation records
required by the monthly operation reports, for at least ten years in accordance
with subsection 62-550.720(5),
F.A.C.
(c) All suppliers of water
shall keep records documenting that their finished-drinking-water storage
tanks, including conventional hydropneumatic tanks with an access manhole but
excluding bladder- or diaphragm-type hydropneumatic tanks without an access
manhole, have been cleaned and inspected during the past five years in
accordance with subsection
62-555.350(2),
F.A.C. In addition, all suppliers of water shall keep records documenting that
their isolation valves are being exercised, and their water mains conveying
finished drinking water are being flushed, in accordance with subsection
62-555.350(2),
F.A.C.
(13) Suppliers of
water shall provide an operation and maintenance manual for each of their
drinking water treatment plants by no later than December 31, 2005, and shall
update the manual thereafter as necessary to reflect plant alterations and
additions. The manual shall contain operation and control procedures, and
preventive maintenance and repair procedures, for all plant equipment and shall
be made available for reference at the plant or at a convenient location near
the plant. Bound and indexed equipment manufacturer manuals shall be considered
sufficient to meet the requirements of this subsection.
(14) By December 31, 2005, suppliers of water
who own or operate a community water system serving, or designed to serve, 350
or more persons or 150 or more service connections shall have, and thereafter
maintain, an up-to-date map of their drinking water distribution system. Such a
map shall show the location and size of water mains if known; the location of
valves and fire hydrants; and the location of any pressure zone boundaries,
pumping facilities, storage tanks, and interconnections with other public water
systems.
(15) Suppliers of water
who own or operate a community water system serving, or designed to serve, 350
or more persons or 150 or more service connections shall develop a written
emergency preparedness/response plan in accordance with Emergency
Planning for Water Utilities, AWWA Manual M19, as adopted in Rule
62-555.335, F.A.C., by no later
than December 31, 2004, and shall update and implement the plan as necessary
thereafter. Said suppliers of water shall coordinate with their Local Emergency
Planning Committee and their Florida Department of Law Enforcement Regional
Security Task Force when developing their emergency plan and shall include in
their plan all of the information in paragraphs (a) through (e), below.
(a) A communication chart as described in
Chapter 5 of AWWA Manual M19.
(b)
Written agreements with other agencies, utilities, or response
organizations.
(c) A
disaster-specific preparedness/response plan as described in Chapter 5 of AWWA
Manual M19 for each of the following disasters: vandalism or sabotage; a
drought; a hurricane; a structure fire; and if applicable, a flood, a forest or
brush fire, and a hazardous material release. Each disaster-specific
preparedness/response plan shall incorporate the results of a vulnerability
assessment; shall include actions and procedures, and identify equipment, that
can obviate or lessen the impact of such a disaster; and shall include plans
and procedures that can be implemented, and identify equipment that can be
utilized, in the event of such a disaster.
(d) Details about how the water system meets
the standby power requirements under subsection
62-555.320(14),
F.A.C., and, if applicable, recommendations regarding the amount of fuel to
maintain on site, and the amount of fuel to hold in reserve under contracts
with fuel suppliers, for operation of auxiliary power sources.
(e) If applicable, recommendations regarding
the amount of drinking water treatment chemicals, including chemicals used for
regeneration of ion-exchange resins or for onsite generation of disinfectants,
to maintain in inventory at treatment plants.
Notes
Rulemaking Authority 403.861(9) FS. Law Implemented 403.852(12), 403.853(6), 403.861(17) FS.
New 11-19-87, Formerly 17-22.650, Amended 1-18-89, 1-1-93, Formerly 17-555.350, Amended 8-28-03.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.