Fla. Admin. Code Ann. R. 62-610.668 - Cooling Water Applications
(1)
Once-through cooling.
(a) Reclaimed water may
be used for once-through cooling.
(b) Setback distances shall be as established
in Rule 62-610.662, F.A.C.
(c) Reclaimed water, upon flowing out of the
once-through, non-contact, cooling system, that is returned to the domestic
wastewater facilities for additional treatment or disposal or reuse, shall be
defined to be a "domestic wastewater." This definition is made solely for the
purposes of classifying wastewater treatment, reuse, and effluent disposal
facilities associated with the domestic wastewater facilities. This definition
shall apply only if the sole change to the quality of the reclaimed water
during the once-through, non-contact, cooling process is a temperature
increase, and conditioning chemicals, other than chlorine and other chemicals
accepted by the Department, have not been added to the reclaimed
water.
(d) Reclaimed water which
has not been disinfected may be used for once-through cooling purposes at
industrial facilities if the following conditions are met:
1. The reclaimed water has received at least
secondary treatment as defined in subparagraph
62-600.420(1)(b)
2., F.A.C.
2. The reclaimed water
is conveyed and used in closed systems which are not open to the
atmosphere.
3. The reclaimed water
is returned to the domestic wastewater treatment facility.
(e) Water used for once-through cooling under
the provisions of paragraph
62-610.668(1)(d),
F.A.C., shall be considered "reclaimed water" and the use of this water shall
be considered "reuse."
(2) Open cooling towers.
(a) Reclaimed water may be used in open
cooling towers, if the requirements in paragraphs
62-610.668(2)(b), (c), or
(d), F.A.C., are met.
(b) All requirements of Part III of this
chapter, including minimum system size requirements, shall be met.
(c) As an alternative to the requirements in
paragraph 62-610.668(2)(b),
F.A.C., all of the following requirements shall apply:
1. Preapplication waste treatment shall
result in a reclaimed water that meets secondary treatment and basic
disinfection.
2. A 300-foot setback
distance shall be provided from the cooling tower that receives reclaimed water
to the site property line.
3. The
cooling tower shall be designed and operated to minimize aerosol drift to areas
beyond the site property line that are accessible to the public.
4. The cooling tower shall be designed,
operated, and maintained utilizing best engineering practices to control
biological growth.
(d) As
an alternative to the requirements in paragraph
62-610.668(2)(b),
F.A.C., all of the following requirements shall be met in the facility's
industrial wastewater permit:
1. The
high-level disinfection requirements of subsection
62-600.440(5),
F.A.C.
2. The filtration
requirements of subsection
62-610.460(3),
F.A.C.
3. The continuous monitoring
requirements of subsection
62-610.463(2),
F.A.C.
4. In lieu of the operation,
staffing, and reliability provisions in Rule
62-610.462, F.A.C., operation,
maintenance, staffing and reliability requirements shall be addressed in the
facility's industrial wastewater permit in accordance with applicable
industrial wastewater rules.
5. The
cooling tower shall be designed, operated, and maintained utilizing best
engineering practices to control biological
growth.