Ga. Comp. R. & Regs. R. 391-3-5-.14 - Operation
(1)
Compliance with Safe Drinking Water Rules. A supplier of water
shall treat the water supplied so the water complies with the Safe Drinking
Water rules of this Chapter. Public water systems shall not use bottled water
to achieve compliance with a maximum contaminant level (MCL). Bottled water may
be used on a temporary basis to avoid unreasonable risk to health. Community
and non-transient non-community water systems shall not use point-of-use or
point-of-entry treatment units to achieve compliance with an MCL or a treatment
technique requirement.
(2)
Continuous Chlorination. The supplier of water must continuously
chlorinate the water to maintain a detectable residual of free chlorine in all
parts of the distribution system in the recommended amount of at least 0.2
parts per million, and such additional amounts as may be determined necessary
by the Division, unless other means of disinfection have been approved by the
Director. If the residual disinfectant concentration is measured by approved
analytical methods and not detected, the supplier may, upon approval by the
Division, determine and report detectability by the use of heterotrophic plate
count measurements as required by
40 CFR §
141.72 (1989) and other applicable paragraphs
of 40 CFR Part 141.
(3)
Disinfection Waiver. After consideration of the microbiological
quality of the source of water supply, the local geology, the population served
and the extent of the water distribution system, the disinfection treatment may
be waived by the Director.
(4)
Fluoridation Requirements. The supplier of water of a fluoridated
public water system shall daily sample and analyze the fluoride concentration
of the drinking water. Daily records of the analytical results shall be kept on
forms provided by the Division or on forms acceptable to the Division and a
copy of the result submitted to the Division in accordance with Rule
391-3-5-.30.
(5)
Surface Water Source Certified
Operator. A supplier having a surface water source must have a certified
operator on duty and onsite at all times when the water plant is in operation.
A supplier having a groundwater source under the direct influence of surface
water must have a certified operator on duty and onsite at all times when the
water plant is in operation, unless otherwise approved by the Division,
depending upon the complexity of the water treatment processes, quality of the
water sources, and the size of the system.
(6)
Groundwater Source Certified
Operator. A supplier having only ground water sources must have a
certified operator to comply with the classification prescribed in Section
391-3-5-.39 of this Chapter. The
Director may find that the availability of a certified operator to a system
with only groundwater sources is sufficient to comply with Section
391-3-5-.39 of this Chapter and may
so allow, but only if the Director determines that the complexity of the water
treatment processes, quality of the water sources, and the size of the system
so warrant.
(7)
Record
Maintenance. The supplier of water shall maintain daily records of the
operation of the water treatment facility and water distribution system as may
be required by the Division including the amount of water treated daily,
results of the performance of daily tests pertinent to the control of the water
treatment processes, disinfectant residuals, and tests performed in the water
distribution system. Daily records shall be kept by the supplier on forms
furnished by the Division and a copy of the record submitted to the Division in
accordance with Rule
391-3-5-.30. Based on the complexity
of the water treatment process, the quality of the water sources, and the size
of the system, the Director may establish less frequent maintenance of record
requirements for small groundwater systems.
(8)
Microbiological Laboratory.
All community water systems which have a surface water source with water
treatment facilities and those public water systems having only a ground water
source or only a water distribution system and serving a population of more
than 12,900 must have, or have available, the services of a microbiological
laboratory certified by the Division to perform the microbiological tests
necessary for compliance with the maximum microbiological contaminant levels.
The laboratory and equipment must be kept in good working order at all
times.
(9)
Summary
Microbiological Analytical Results. A supplier of water required to
have, or have available, a microbiological laboratory under paragraph (8) of
Section 391-3-5-.14
shall collect and analyze drinking water samples in accordance with the minimum
number specified in paragraph (1) of Section
391-3-5-.23 and such additional
samples as may be required by the Director. The supplier shall furnish the
Division, on forms provided by the Division, a monthly microbiological summary
of the number of samples analyzed and the results in accordance with Section
391-3-5-.30.
(10)
Routine Microbiological
Samples. The supplier of water shall collect routine drinking water
samples for microbiological analysis as follows:
(a) the minimum number of routine samples per
month shall be in accordance with paragraph (1) of Section
391-3-5-.23;
(b) at the treatment plant and at various
points in the distribution system which are representative of the drinking
water when three or more samples per month are required; or
(c) at various points in the distribution
system which are representative of the drinking water when only one or two
samples per month are required.
(11)
Certified Laboratories. For
the purposes of determining compliance with Rules
391-3-5-.18,
.19,
.20,
.21,
.22,
.23,
.24,
.25,
.26,
.27 samples may be considered only
if they have been analyzed by a laboratory certified by the Division, except
that measurements used solely for operational control, including but not
limited to turbidity, free chlorine residual, fluoride residual, temperature,
pH, conductivity, calcium, alkalinity, orthophosphate, chloramines, chlorine
dioxide, chlorite and silica may be performed by any person acceptable to the
Division.
(12)
Operations and
Maintenance Plan. All public surface water and ground water under the
direct influence of surface water systems shall develop an Operations and
Maintenance Plan (O & M Plan). The plan shall be prepared in accordance
with the Division's "Operation and Maintenance Plan - Guidance Manual
for Preparing Public Water Supply System O & M Plans", latest
edition. The plan shall be updated at intervals determined by the Director. For
public groundwater systems and systems that are using alternate treatment
technologies, development of such a plan may be required by the Director when
the complexity of the water treatment processes, quality of the water sources,
and the size of the system so warrant.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.