Ill. Admin. Code tit. 77, § 890.1150 - Water Service Pipe Installation
a)
Underground Water Service. Water service pipe shall be installed outside the
foundation wall in accordance with either subsection (a)(1) or (2) and shall
comply with both subsections (a)(3) and (4).
1) Water service and building drain or
building sewer may be installed in separate trenches with a minimum of 10 feet
horizontal separation. Material listed in Appendix A.Table A (Approved
Materials for Building Sewer and Approved Materials for Water Service Pipe)
shall be used, provided that the material is specific for this type of
installation. (See Appendix I.Illustration E.)
2) The water service and the building drain
or building sewer may be installed in the same trench provided that the water
service is placed on a solid shelf a minimum of 18 inches above the building
drain or building sewer. The building sewer shall be of material listed in
Appendix A.Table A (Approved Building Drainage/Vent Pipe) for a building drain.
(See Appendix I.Illustration F for the proper installation of water service,
building drain and building sewer.)
3) The minimum depth for any water service
pipe shall be at least 36 inches or the maximum frost penetration of the local
area, whichever is of greater depth.
4) No water service pipe shall be installed
or permitted outside of a building or in an exterior wall unless the pipe is
protected from freezing, in accordance with Section
890.1210(a).
b) Potable Water Piping and
Sanitary Sewer Crossing Installation Requirements
1) Potable water piping that passes above or
below a sanitary sewer shall be installed with a minimum vertical separation of
18 inches for a distance of 10 feet on either side from the center of the
sanitary sewer.
2) If potable water
piping passes beneath a sanitary sewer or drain, the sanitary sewer or drain
shall be constructed of materials as specified in Appendix A.Table A (Approved
Building Drainage/Vent Pipe) for building drains and shall extend on each side
of the crossing to a distance of at least 10 feet as measured at right angles
to the water line. The potable water piping shall comply with Appendix A.Table
A as specified for a water service pipe (Approved Materials for Water Service
Pipe). (See Appendix I.Illustration G.)
3) When compliance with subsection (b)(1) or
(2) is not possible, a pressure rated pipe, approved for building drain
material listed in Appendix A.Table A, shall encase the water service pipe. The
casing pipe shall be sealed with a casing seal and extend 10 feet on either
side of the center of the sanitary sewer pipe. The sleeve or case shall be at
least two times the size of the water service.
c) When compliance with subsection (a) or (b)
is not possible, the Department shall be contacted for consideration of
alternative methods.
d)
Stop-and-Waste Valve. Combination stop-and-waste valves and cocks shall not be
installed in an underground potable water pipe. Frost-free hydrants and fire
hydrants shall not be considered stop-and-waste valves. (See Section
890.1140(e).)