105 CMR, § 150.700 - Heating and Air Conditioning Systems
(A)
Every facility shall be equipped with a heating system which is sufficient to
maintain a minimum temperature of 75/F throughout the facility at all times at
winter design temperatures.
(B)
Heating fixtures and all exposed pipes shall be shielded for the safety of
residents.
(C) Each heating fixture
shall be equipped with hand controls unless an individual automatic room
control is provided.
(D) Every
facility whose architectural plans are approved after the promulgation of 105
CMR 150.700(D) for new construction or major renovations such as the
installation of a heating air conditioning and ventilation system or complete
interior reconstruction shall be equipped with a cooling system which is
capable of maintaining a maximum temperature of 75/F throughout the resident
areas affected by the new construction or renovation at all times at summer
design temperatures. Temperatures must be maintained at a level which ensures
the comfort and health of residents of the facility.