310 CMR, § 80.27 - Requirements for Turbine, Intermediate and Dispenser Sumps
(1) Owners and Operators shall operate and
maintain turbine, intermediate and dispenser sumps in accordance with 310 CMR
80.27.
(2) Turbine, intermediate
and dispenser sumps shall be clean and free of solid and liquid material at all
times.
(a) If a sensor or visual observation
indicates that there is liquid in the sump, the liquid shall be removed
immediately.
(b) If the liquid is a
regulated substance, the Owner or Operator shall investigate the source of the
regulated substance, shall investigate the path of entry to the sump, and shall
make any necessary repairs in accordance with
310 CMR
80.33.
(c) The solid and liquid material that
collects in a sump shall be removed, managed and disposed of in accordance with
applicable local, state and federal laws and regulations.
(3) All sump sensors shall be placed in
accordance with the manufacturer's specifications, or, if no such
specifications exist, the sensors shall be placed at the lowest possible
location in the sump, where it can feasibly be installed.
(4) All manhole covers shall prevent water
infiltration to the sump. All sump covers shall be free of cracks and
holes.
(5) All tanks using a
submersible pump that do not have a turbine sump shall be inspected every 30
days.
(a) The Owner or Operator shall visually
inspect the area around the submersible pump as follows:
1. Visually inspect the submersible pump for
release of regulated substance(s); and
2. Visually inspect the submersible pump and
other components for signs of corrosion, breakage and wear.
(b) The Owner or Operator shall
repair or replace components as necessary in accordance with
310 CMR
80.33; and
(6) The Owner or Operator shall inspect
turbine, intermediate and dispenser sumps, except sumps that only contain a
single-walled siphon line with no connections within the sump or sumps that
only contain a European suction system or sumps that do not contain any
regulated substance piping connections, in accordance with the following and in
accordance with
310 CMR
80.35(3) or (4), as
applicable:
(a) Single-walled and
double-walled sumps without continuous monitoring sensors in the sump shall be
inspected every 90 days.
(b)
Single-walled and double-walled sumps with correctly installed and operating
continuous monitoring sensors in the sump shall be inspected
annually.
(7) The Owner
or Operator shall conduct an integrity test of turbine, intermediate and
dispenser sumps, except sumps listed in 310 CMR 80.27(8), on or before January
2, 2017, on or before October 13, 2021, and once every three years thereafter
as follows:
(a) Sumps with properly operating
and installed sensors that are not used for interstitial monitoring of piping
may be tested hydrostatically to the level that will activate the sensors. The
sump passes the integrity test if the sensors are activated when they come in
contact with the liquid.
(b)
Dispenser sumps with properly operating and installed sensors used for
interstitial monitoring of piping and that shuts off the dispenser when
activated may be tested hydrostatically to the level that will activate the
sensor, if the UST facility is always staffed when the pumps are operational.
The sump passes the integrity test if the sensors are activated when they come
in contact with the liquid and shut off the dispenser.
(c) Turbine sumps with properly operating and
installed sensors that are used for interstitial monitoring of piping and that
shuts off the submersible pump when activated may be tested hydrostatically to
the level that will activate the sensor. The sump passes the integrity test if
the sensors are activated when they come in contact with the liquid and shut
off the submersible pump.
(d) Sumps
that do not meet the requirements of 310 CMR 80.27(7)(a), (b) or (c) or do not
have a sensor shall be integrity tested by vacuum or hydrostatic testing in
accordance with PEI RP1200-19.
(8) The following sumps are not subject to
the testing requirements in 310 CMR 80.27(7), 80.27(9) or
80.20(54):
(a) Sumps that only contain a single-walled
siphon line with no connections within the sump or sumps that do not contain
any regulated substance piping connections;
(b) Sumps that only contain a European
suction system; and
(c)
Double-walled sumps, if the integrity of both walls is monitored every 90 days
or annually, as applicable under 310 CMR 80.27(6), by checking vacuum, pressure
or liquid interstitial integrity indicators.
1. A sensor in a dry interstice does not meet
the requirements of monitoring the integrity of both walls.
(9) If the sump fails a test, the Owner or
Operator shall investigate the failure and shall make any necessary repairs in
accordance with
310 CMR
80.33.
(a)
The Owner or Operator shall keep records of the test and any repairs to
demonstrate compliance with 310 CMR 80.27(7) and
310 CMR
80.33 including, but not limited to, the date
of the test and the results, in accordance with
310 CMR
80.36.
(b) Turbine, intermediate and dispenser sumps
that are repaired, except sumps listed in 310 CMR 80.27(8), shall pass an
integrity test in accordance with 310 CMR 80.27(7) prior to commencing
operation. The Owner or Operator shall keep records of such tests in accordance
with
310 CMR
80.36.
(c) Repairs which do not affect the integrity
of a sump to retain liquid including, but not limited to, a sump lid and
gasket, do not require an integrity test prior to commencing service.