20 CSR 4240-40.030 - Safety Standards-Transportation of Gas by Pipeline
PUBLISHER'S NOTE: The secretary of state has determined that publication of the entire text of the material that is incorporated by reference as a portion of this rule would be unduly cumbersome or expensive. This material as incorporated by reference in this rule shall be maintained by the agency at its headquarters and shall be made available to the public for inspection and copying at no more than the actual cost of reproduction. This note applies only to the reference material. The entire text of the rule is printed here.
AGENCY NOTE: This rule is similar to the Minimum Federal Safety Standards contained in 49 CFR part 192, Code of Federal Regulations. Parallel citations to Part 192 are provided for gas operator convenience and to promote public safety. Appendix E, contained in this rule, is a Table of Contents for 20 CSR 424040.030.
Table 1 to Part (1)(E)1.C.(II)
|
Type |
Feature |
Area |
Safety Buffer |
|
A |
* Metallic and the MAOP produces a hoop stress of twenty percent (20%) or more of SMYS. * If the stress level is unknown, an operator must determine the stress level according to the applicable provisions in section (3). * Non-metallic and the MAOP is more than one hundred twenty-five (125) psig (862 kPa). |
Class 2, 3, or 4 location (see subsection (1)(C)). |
None. |
|
B |
* Metallic and the MAOP produces a hoop stress of less than twenty percent (20%) of SMYS. If the stress level is unknown, an operator must determine the stress level according to the applicable provisions in section (3). * Non-metallic and the MAOP is one hundred twenty-five (125) psig (862 kPa) or less. |
Area 1. Class 3 or 4 location. Area 2. An area within a Class 2 location the operator determines by using any of the following three methods: (a) A Class 2 location; (b) An area extending one hundred fifty feet (150') (45.7 m) on each side of the centerline of any continuous one (1) mile (1.6 km) of pipeline and including more than ten (10) but fewer than forty-six (46) dwellings; or (c) An area extending one hundred fifty feet (150') (45.7 m) on each side of the centerline of any continuous one thousand feet (1000') (305 m) of pipeline and including five (5) or more dwellings. |
If the gathering pipeline is in Area 2(b) or 2(c), the additional lengths of line extend upstream and downstream from the area to a point where the line is at least one hundred fifty feet (150') (45.7 m) from the nearest dwelling in the area. However, if a cluster of dwellings in Area 2(b) or 2(c) qualifies a pipeline as Type B, the Type B classification ends one hundred fifty feet (150') (45.7 m) from the nearest dwelling in the cluster. |
|
C |
* Outside diameter greater than or equal to 8.625 inches and any of the following: -Metallic and the MAOP produces a hoop stress of twenty percent (20%) or more of SMYS; -If the stress level is unknown, segment is metallic and the MAOP is more than one hundred twenty-five (125) psig (862 kPa); or -Non-metallic and the MAOP is more than one hundred twenty-five (125) psig (862 kPa). |
Class 1 location. |
None. |
|
R |
All other gathering lines. |
Class 1 and Class 2 locations. |
None. |
|
Requirement |
Compliance Deadline |
|
(i) Control corrosion according to requirements for transmission lines in section (9). |
April 15, 2009. |
|
(ii) Carry out a damage prevention program under subsection (12)(I). |
October 15, 2007. |
|
(iii) Establish MAOP under subsection (12)(M). |
October 15, 2007. |
|
(iv) Install and maintain line markers under subsection (13)(E). |
April 15, 2008. |
|
(v) Establish a public education program under subsection (12)(K). |
April 15, 2008. |
|
(vi) Other provisions of this rule as required by subparagraph (1)(E)2.B. for Type A lines. |
April 15, 2009. |
|
Pipeline |
Date |
|
Regulated onshore gathering pipeline to which this rule did not apply until April 14, 2006 (see (1)(E)) |
March 15, 2007 |
|
Regulated onshore gathering pipeline to which this rule did not apply until May 16, 2022 (see (1)(E)) |
May 16, 2023 |
|
All other pipelines |
March 12, 1971 |
|
Pipeline |
Date |
|
Regulated onshore gathering pipeline to which this rule did no apply until April 14, 2006 (see (1)(E)) |
March 15, 2007 |
|
Regulated onshore gathering pipeline to which this rule did no apply until May 16, 2022 (see (1)(E)) |
May 16, 2023 |
|
All other pipelines |
November 12, 1970 |
P = (2 St/D) × F × E × T
where-
P = Design pressure in pounds per square inch (kPa) gauge;
S = Yield strength in pounds per square inch (kPa) determined in accordance with subsection (3)(D); (192.107)
D = Nominal outside diameter of the pipe in inches (millimeters);
t = Nominal wall thickness of the pipe in inches (millimeters). If this is unknown, it is determined in accordance with subsection (3)(E) (192.109). Additional wall thickness required for concurrent external loads in accordance with subsection (3) (B) (192.103) may not be included in computing design pressure;
F = Design factor determined in accordance with subsection (3)(F) (192.111);
E = Longitudinal joint factor determined in accordance with subsection (3)(G) (192.113); and
T = Temperature derating factor determined in accordance with subsection (3)(H) (192.115).
|
Class Location |
Design Factor (F) |
|
1 |
0.72 |
|
2 |
0.60 |
|
3 |
0.50 |
|
4 |
0.40 |
|
Specification |
Pipe Class |
Longitudinal Joint Factor (E) |
|
ASTM A 53/A53M |
Seamless |
1.00 |
|
Electric resistance welded |
1.00 |
|
|
Furnace butt welded |
0.60 |
|
|
ASTM A 106 |
Seamless |
1.00 |
|
ASTM A 333/A 333M |
Seamless |
1.00 |
|
Electric resistance welded |
1.00 |
|
|
ASTM A 381 |
Double submerged arc welded |
1.00 |
|
ASTM A 671 |
Electric fusion welded |
1.00 |
|
ASTM A 672 |
Electric fusion welded |
1.00 |
|
ASTM A 691 |
Electric fusion welded |
1.00 |
|
API 5L |
Seamless |
1.00 |
|
Electric resistance welded |
1.00 |
|
|
Electric flash welded |
1.00 |
|
|
Submerged arc welded |
1.00 |
|
|
Furnace butt welded |
0.60 |
|
|
Other |
Pipe over 4 inches (102 millimeters) |
0.80 |
|
Other |
Pipe 4 inches (102 millimeters) or less |
0.60 |
If the type of longitudinal joint cannot be determined, the joint factor to be used must not exceed that designated for Other.
|
Gas Temperature in Degrees Fahrenheit (Celsius) |
Temperature Derating Factor (T) |
|
250 °F (121 °C) or less |
1.000 |
|
300 °F (149 °C) |
0.967 |
|
350 °F (177 °C) |
0.933 |
|
400 °F (204 °C) |
0.900 |
|
450 °F (232 °C) |
0.867 |
For intermediate gas temperatures, the derating factor is determined by interpolation.
Click to view image
where
P = Design pressure, psi (kPa) gauge;
S = For thermoplastic pipe, the hydrostatic design base (HDB) is determined in accordance with the listed specification at a temperature equal to 73 °F (23 °C), 100 °F (38 °C), 120 °F (49 °C), or 140 °F (60 °C). In the absence of an HDB established at the specified temperature, the HDB of a higher temperature may be used in determining a design pressure rating at the specified temperature by arithmetic interpolation using the procedure in Part D.2. of PPI TR-3/2008, HDB/PDB/SDB/MRS Policies (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D));
t = Specified wall thickness, inches (millimeters);
D = Specified outside diameter, inches (millimeters); and
SDR = Standard dimension ratio, the ratio of the average specified outside diameter to the minimum specified wall thickness, corresponding to a value from a common numbering system that was derived from the American National Standards Institute preferred number series 10.
DF = Design Factor, a maximum of 0.32 unless otherwise specified for a particular material in this subsection.
|
PE Pipe: Minimum Wall Thickness and SDR Values |
||
|
Pipe Size (inches) |
Minimum wall thickness (inches) |
Corresponding SDR (values) |
|
1/2" CTS |
0.090 |
7 |
|
3/4" CTS |
0.090 |
9.7 |
|
1/2" IPS |
0.090 |
9.3 |
|
3/4" IPS |
0.095 |
11 |
|
1" CTS |
0.099 |
11 |
|
1" IPS |
0.119 |
11 |
|
1 1/4" IPS |
0.151 |
11 |
|
1 1/2" IPS |
0.173 |
11 |
|
2" |
0.216 |
11 |
|
3" |
0.259 |
13.5 |
|
4" |
0.265 |
17 |
|
6" |
0.315 |
21 |
|
8" |
0.411 |
21 |
|
10" |
0.512 |
21 |
|
12" |
0.607 |
21 |
|
16" |
0.762 |
21 |
|
18" |
0.857 |
21 |
|
20" |
0.952 |
21 |
|
22" |
1.048 |
21 |
|
24" |
1.143 |
21 |
|
Standard Size (inch) (millimeter) |
Nominal O.D. (inch) (millimeters) |
Wall Thickness Nominal |
Tolerance (inch) (millimeter) |
|
1/2 (13) |
.625 (16) |
.040 (1.06) |
.0035 (.0889) |
|
5/8 (16) |
.750 (19) |
.042 (1.07) |
.0035 (.0889) |
|
3/4 (19) |
.875 (22) |
.045 (1.14) |
.004 (.102) |
|
1 (25) |
1.125 (29) |
.050 (1.27) |
.004 (.102) |
|
1 1/4 (32) |
1.375 (35) |
.055 (1.40) |
.0045 (.1143) |
|
1 1/2 (38) |
1.625 (41) |
.060 (1.52) |
.0045 (.1143) |
Click to view image
where
C = Minimum clearance between pipe containers or bottles in inches (millimeters);
D = Outside diameter of pipe containers or bottles in inches (millimeters);
P = Maximum allowable operating pressure, psi (kPa) gauge; and
F = Design factor as set forth in subsection (3)(F) (192.111).
|
Maximum Allowable Operating Pressure |
Minimum Clearance feet (meters) |
|
Less than 1000 psi (7 MPa) gauge |
25 (7.6) |
|
1000 psi (7 MPa) gauge or more |
100 (31) |
For the purpose of this subsection, a "dent" is a depression that produces a gross disturbance in the curvature of the pipe wall without reducing the pipe-wall thickness. The depth of a dent is measured as the gap between the lowest point of the dent and a prolongation of the original contour of the pipe.
superimposed loads;
|
Location |
Normal Soil inches |
Consolidated Rock (millimeters) |
|
Class 1 locations |
30 (762) |
18 (457) |
|
Class 2, 3, and 4 locations |
36 (914) |
24 (610) |
|
Drainage ditches of public roads and railroad crossings |
36 (914) |
24 (610) |
|
Threat |
Standard1 (see section (16)) |
|
External corrosion |
49 CFR 192.925 2 |
|
Internal corrosion in pipelines that transport dry gas |
49 CFR 192.927 |
|
Stress corrosion cracking |
49 CFR 192.929 |
1For lines not subject to 49 CFR part 192, subpart O, the terms "covered segment" and "covered pipeline segment" in 49 CFR 192.925, 192.927, and 192.929 refer to the pipeline segment on which direct assessment is performed.
2In 49 CFR 192.925 [b], the provision regarding detection of coating damage applies only to pipelines subject to 49 CFR part 192, subpart O.
|
Class Location |
Maximum Hoop Stress Allowed as Percentage of SMYS |
|
|
Natural Gas |
Air or Inert Gas |
|
|
1 |
80 |
80 |
|
2 |
30 |
75 |
|
3 |
30 |
50 |
|
4 |
30 |
40 |
Allowance inches (millimeters) Cast Iron Pipe
|
Pipe Size inches (millimeters) |
Pit Cast Pipe |
Centrifugally Cast Pipe |
Ductile Iron Pipe |
|
3 to 8 (76 to 203) |
0.075 (1.91) |
0.065 (1.65) |
0.065 (1.65) |
|
10 to 12 (254 to 305) |
0.08 (2.03) |
0.07 (1.78) |
0.07 (1.78) |
|
14 to 24 (356 to 610) |
0.08 (2.03) |
0.08 (2.03) |
0.075 (1.91) |
|
30 to 42 (762 to 1067) |
0.09 (2.29) |
0.09 (2.29) |
0.075 (1.91) |
|
48 (1219) |
0.09 (2.29) |
0.09 (2.29) |
0.08 (2.03) |
|
54 to 60 (1372 to 1524) |
0.09 (2.29) |
- - |
- - |
|
Class Location |
Factors1,2, Segment- |
|||
|
Installed before Nov. 12, 1970 |
Installed after Nov. 11, 1970, and before July 1, 2020 |
Installed on or after July 1, 2020 |
Converted under subsection (1)(H) (192.14) |
|
|
1 |
1.1 |
1.1 |
1.25 |
1.25 |
|
2 |
1.25 |
1.25 |
1.25 |
1.25 |
|
3 |
1.4 |
1.5 |
1.5 |
1.5 |
|
4 |
1.4 |
1.5 |
1.5 |
1.5 |
1 For segments installed, uprated, or converted after July 31, 1977, that are located on a platform in inland navigable waters, including a pipe riser, the factor is 1.5.
2 For a component with a design pressure established in accordance with paragraphs (4)(H)1. or (4)(H)2. of this rule (192.153(a) or (b)) installed after July 14, 2004, the factor is 1.3;
|
Pipeline Segment |
Pressure Date |
Test Date |
|
Onshore regulated gathering pipeline (Type A or Type B under paragraph (1) (E)2.) that first became subject to this rule after April 13, 2006. |
March 15, 2006, or date line becomes subject to this rule, whichever is later. |
Five (5) years preceding applicable date in second column. |
|
Onshore regulated gathering pipeline (Type C under paragraph (1)(E)2.) that first became subject to this rule on or after May 16, 2022. |
May 16, 2023, or date pipeline becomes subject to this rule, whichever is later. |
Five (5) years preceding applicable date in second column. |
|
Onshore transmission pipeline that was a gathering line not subject to this rule before March 15, 2006 (see subsection (1)(E)). |
March 15, 2006, or date line becomes subject to this rule, whichever is later. |
Five (5) years preceding applicable date in second column. |
|
All other pipelines. |
July 1, 1970. |
July 1, 1965. |
Table 1
|
Class locations |
Patrols |
Leakage surveys |
|
(A) Class 1 and Class 2 |
31/2 months, but at least four times each calendar year |
31/2 months, but at least four times each calendar year |
|
(B) Class 3 and Class 4 |
3 months, but at least six times each calendar year |
3 months, but at least six times each calendar year |
Maximum Interval Between Patrols
|
Class Location of Line |
At Highway and Railroad Crossing Locations |
At All Other Locations |
|
1, 2 |
7 1/2 months; but at least twice each calendar year |
15 months; but at least once each calendar year |
|
3 |
4 1/2 months; but at least four times each calendar year |
7 1/2 months; but at least twice each calendar year |
|
4 |
4 1/2 months; but at least four times each calendar year |
4 1/2 months; but at least four times each calendar year |
Appendix A-20 CSR 4240-40.030
(Reserved)
Appendix B to 20 CSR 4240-40.030
Appendix B-Qualification of Pipe and Components
ANSI/API Specification 5L-Steel pipe, "API Specification for Line Pipe" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM A53/A53M-Steel pipe, "Standard Specification for Pipe, Steel Black and Hot-Dipped, Zinc-Coated, Welded and Seamless" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM A106/A106M-Steel pipe, "Standard Specification for Seamless Carbon Steel Pipe for High Temperature Service" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM A333/A333M-Steel pipe, "Standard Specification for Seamless and Welded Steel Pipe for Low Temperature Service" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM A381-Steel pipe, "Standard Specification for Metal-Arc-Welded Steel Pipe for Use with High-Pressure Transmission Systems" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM A671/A671M-Steel pipe, "Standard Specification for Electric-Fusion-Welded Pipe for Atmospheric and Lower Temperatures" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM A672/A672M-Steel pipe, "Standard Specification for Electric-Fusion-Welded Steel Pipe for High-Pressure Service at Moderate Temperatures" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM A691/A691M-Steel pipe, "Standard Specification for Carbon and Alloy Steel Pipe, Electric-Fusion-Welded for High-Pressure Service at High Temperatures" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM D2513-"Standard Specification for Polyethylene (PE) Gas Pressure Pipe, Tubing, and Fittings" (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM F2817-10-''Standard Specification for Poly (Vinyl Chloride) (PVC) Gas Pressure Pipe and Fittings for Maintenance or Repair'' (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASME B16.40-2008-''Manually Operated Thermoplastic Gas Shutoffs and Valves in Gas Distribution Systems'' (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM D2513-''Standard Specification for Polyethylene (PE) Gas Pressure Pipe, Tubing, and Fittings'' (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM F1055-98 (2006)-''Standard Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene Pipe and Tubing'' (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM F1924-12-''Standard Specification for Plastic Mechanical Fittings for Use on Outside Diameter Controlled Polyethylene Gas Distribution Pipe and Tubing'' (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM F1948-12-''Standard Specification for Metallic Mechanical Fittings for Use on Outside Diameter Controlled Thermoplastic Gas Distribution Pipe and Tubing'' (incorporated by reference, in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM F1973-13-''Standard Specification for Factory Assembled Anodeless Risers and Transition Fittings in Polyethylene (PE) and Polyamide 11 (PA 11) and Polyamide 12 (PA 12) Fuel Gas Distribution Systems'' (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
ASTM F2817-10-''Standard Specification for Poly (Vinyl Chloride) (PVC) Gas Pressure Pipe and Fittings for Maintenance or Repair'' (incorporated by reference in 49 CFR 192.7 and adopted in subsection (1)(D)).
|
Number of Tensile Tests-All Sizes |
|
|
10 lengths or less |
1 set of tests for each length. |
|
11 to 100 lengths |
1 set of tests for each 5 lengths, but not less than 10 tests. |
|
Over 100 lengths |
1 set of tests for each 10 lengths, but not less than 20 tests. |
If the yield-tensile ratio, based on the properties determined by those tests, exceeds 0.85, the pipe may be used only as provided in paragraph (2)(C)3. of 20 CSR 4240-40.030. (192.55[c])
Appendix C to 20 CSR 4240-40.030
Appendix C-Qualification of Welders for Low Stress Level Pipe
Appendix D to 20 CSR 4240-40.030
Appendix D-Criteria for Cathodic Protection and Determination of Measurements
Appendix E to 20 CSR 4240-40.030
Appendix E-Table of Contents-Safety Standards-Transportation of Gas by Pipeline
20 CSR 4240-40.030(1) General
20 CSR 4240-40.030(2) Materials
20 CSR 4240-40.030(3) Pipe Design
20 CSR 4240-40.030(4) Design of Pipeline Components
20 CSR 4240-40.030(5) Welding of Steel in Pipelines
20 CSR 4240-40.030(6) Joining of Materials Other Than by Welding
20 CSR 4240-40.030(7) General Construction Requirements for Transmission Lines and Mains
20 CSR 4240-40.030(8) Customer Meters, Service Regulators, and Service Lines
20 CSR 4240-40.030(9) Requirements for Corrosion Control
20 CSR 4240-40.030(10) Test Requirements
20 CSR 4240-40.030(11) Uprating
20 CSR 4240-40.030(12) Operations
20 CSR 4240-40.030(13) Maintenance
20 CSR 4240-40.030(14) Gas Leaks
20 CSR 4240-40.030(15) Replacement Programs
20 CSR 4240-40.030(16) Pipeline Integrity Management for Transmission Lines
20 CSR 4240-40.030(17) Gas Distribution Pipeline Integrity Management (IM)
20 CSR 4240-40.030(18) Waivers of Compliance
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.