Or. Admin. Code § 340-150-0440 - Manual Tank Gauging Release Detection Method
(1) An owner and permittee may use manual
tank gauging as a release detection method for USTs that are less than 2,001
gallons in size.
(a) For USTs of 550 gallons
or less nominal capacity and USTs with a nominal capacity of 551 to 1,000
gallons that meet the tank diameter criteria in the table may use this as the
sole method of release detection.
(b) For USTs of 551 to 2,000 gallons in size,
this method may be used instead of manual inventory control (OAR
340-150-0430). This method is
allowed for a period of:
(A) Ten years after
the installation of the UST system; or
(B) Ten years after the UST system achieved
compliance with corrosion protection requirements; except
(C) In no case may manual tank gauging be
used as a primary release detection method after December 22, 2008.
(c) After the period of use has
expired as listed in paragraph (1)(b)(C) of this section, an owner and
permittee of an UST between 551 and 2,000 gallons in size must use one of the
release detection methods in OAR
340-150-0435 through
340-150-0470.
(2) An owner and permittee must
use the following procedures for the manual tank gauging release detection
method:
(a) Tank liquid level measurements
must be taken at the beginning and ending of a minimum 36-hour test period,
during which time no liquid (i.e., regulated substance) may be added to or
removed from the UST;
(b) Level
measurements must be based on an average of two consecutive measuring stick or
automatic tank gauge readings at both the beginning and ending of the period in
which the UST is tested; and
(c)
The equipment used to measure the level of regulated substance in the UST
(e.g., stick or automatic tank gauge) must be capable of measuring the level of
the regulated substance over the full range of the UST's height to the nearest
one-eighth of an inch.
(3) An owner and permittee must monitor the
UST system for releases at least weekly and record and reconcile the results of
each week's readings for each month.
(4) In addition to any other requirements of
this rule, an owner and permittee must conduct tightness testing (OAR
340-150-0445) of USTs of 1,001
to 2,000 gallons in size at least once every five years.
(5) An owner and permittee must report to DEQ
any variation between beginning and ending measurements that exceeds either the
weekly or monthly standards in the table in
340-150-0440(1)(a)
within 24 hours as a suspected release (OAR
340-150-0500) and immediately
begin investigation as
340-150-0510
specifies.
(6) An owner and
permittee must immediately investigate all larger-than-normal or reoccurring
variations in results and report such variations to DEQ as a suspected release
if the variation cannot be accounted for, without waiting to obtain a second
week of data.
(7) An owner and
permittee must retain at a minimum the most current 12 consecutive months of
release detection records and the last two tightness test results.
Notes
To view tables referenced in rule text, click here to view rule.
Statutory/Other Authority: ORS 466.706 - 466.835, 466.994 & 466.995
Statutes/Other Implemented: ORS 466.746 & 466.765