Utah Admin. Code R309-210-8 - Disinfection Byproducts - Stage 1 Requirements
(1) General requirements. The requirements in
this subsection establish criteria under which community and non-transient
non-community water systems that add a chemical disinfectant to the water in
any part of the drinking water treatment process, shall modify their practices
to meet MCLs and MRDLs in
R309-200-5(3)(c)
and meet treatment technique requirements in
R309-215-12
and 13. The requirements of this sub-section also establish criteria under
which transient non-community water systems that use chlorine dioxide shall
modify their practices to meet MRDLs for chlorine dioxide in
R309-200-5(3)(c).
(a) Compliance dates.
(i) Community and Non-transient non-community
water systems. Surface water systems serving 10,000 or more persons must comply
with this section beginning January 1, 2002. Surface water systems serving
fewer than 10,000 persons and systems using only ground water not under the
direct influence of surface water must comply with this section beginning
January 1, 2004.
(ii) Transient
non-community water systems. Surface water systems serving 10,000 or more
persons and using chlorine dioxide as a disinfectant or oxidant must comply
with any requirements for chlorine dioxide in this section beginning January 1,
2002. Surface water systems serving fewer than 10,000 persons and using
chlorine dioxide as a disinfectant or oxidant and systems using only ground
water not under the direct influence of surface water and using chlorine
dioxide as a disinfectant or oxidant must comply with any requirements for
chlorine dioxide in this section beginning January 1, 2004.
(b) Systems must take all samples
during normal operating conditions.
(c) Systems may consider multiple wells
drawing water from a single aquifer as one treatment plant for determining the
minimum number of TTHM and HAA5 samples required, with approval from the
Director.
(d) Failure to monitor in
accordance with the monitoring plan required under paragraph (5) of this
section is a monitoring violation.
(e) Failure to monitor will be treated as a
violation for the entire period covered by the annual average where compliance
is based on a running annual average of monthly or quarterly samples or
averages and the system's failure to monitor makes it impossible to determine
compliance with MCLs or MRDLs.
(f)
Systems may use only data collected under the provisions of this section or the
federal Information Collection Rule, (40 CFR, Part 141, Subpart M) to qualify
for reduced monitoring.
(2) Monitoring requirements for disinfection
byproducts.
(a) TTHMs and HAA5s
(i) Routine monitoring. Systems must monitor
at the frequency indicated in the following:
(A) If a system elects to sample more
frequently than the minimum required, at least 25 percent of all samples
collected each quarter (including those taken in excess of the required
frequency) must be taken at locations that represent the maximum residence time
of the water in the distribution system. The remaining samples must be taken at
locations representative of at least average residence time in the distribution
system.
(B) Surface water systems
serving at least 10,000 persons shall take four water samples per quarter per
treatment plant. At least 25 percent of all samples collected each quarter
shall be at locations representing maximum residence time. The remaining
samples taken at locations representative of at least average residence time in
the distribution system and representing the entire distribution system, taking
into account number of persons served, different sources of water, and
different treatment methods.
(C)
Surface water systems serving from 500 to 9,999 persons shall take one water
sample per quarter per treatment plant at a locations representing maximum
residence time.
(D) Surface water
systems serving fewer than 500 persons shall take one sample per year per
treatment plant during month of warmest water temperature at a location
representing maximum residence time. If the sample (or average of annual
samples, if more than one sample is taken) exceeds the MCL, the system must
increase monitoring to one sample per treatment plant per quarter, taken at a
point reflecting the maximum residence time in the distribution system, until
the system meets reduced monitoring criteria in paragraph (2)(a)(v) of this
section.
(E) Systems using only
ground water not under direct influence of surface water using chemical
disinfectant and serving at least 10,000 persons shall take one water sample
per quarter per treatment plant at a locations representing maximum residence
time.
(F) Systems using only ground
water not under direct influence of surface water using chemical disinfectant
and serving fewer than 10,000 persons shall take one sample per year per
treatment plant during month of warmest water temperature at a location
representing maximum residence time. If the sample (or average of annual
samples, if more than one sample is taken) exceeds the MCL, the system must
increase monitoring to one sample per treatment plant per quarter, taken at a
point reflecting the maximum residence time in the distribution system, until
the system meets criteria in paragraph (2) (a)(v) of this section for reduced
monitoring.
(ii) Systems
may reduce monitoring, except as otherwise provided, if the system has
monitored for at least one year and is in accordance with the following
paragraphs. Any Surface water system serving fewer than 500 persons may not
reduce its monitoring to less than one sample per treatment plant per year.
(A) A surface water system serving at least
10,000 persons which has a source water annual average TOC level, before any
treatment, of less than or equal to 4.0 mg/L and has a TTHM annual average of
less than or equal to 0.040 mg/L and has a HAA5 annual average of less than or
equal to 0.030 mg/L may reduce monitoring to one sample per treatment plant per
quarter at a distribution system location reflecting maximum residence
time.
(B) A surface water system
serving from 500 to 9,999 persons which has a source water annual average TOC
level, before any treatment, of less than or equal to 4.0 mg/L and has a TTHM
annual average of less than or equal to 0.040 mg/L and has a HAA5 annual
average of less than or equal to 0.030 mg/L may reduce monitoring to one sample
per treatment plant per year at a distribution system location reflecting
maximum residence time during the month of warmest water temperature.
(C) A system using only ground water not
under direct influence of surface water using chemical disinfectant and serving
at least 10,000 persons that has a TTHM annual average of less than or equal to
0.040 mg/L and has a HAA5 annual average of less than or equal to 0.030 mg/L
may reduce monitoring to one sample per treatment plant per year at a
distribution system location reflecting maximum residence time during the month
of warmest water temperature.
(D) A
system using only ground water not under direct influence of surface water
using chemical disinfectant and serving fewer than 10,000 persons that has a
TTHM annual average of less than or equal to 0.040 mg/L and has a HAA5 annual
average of less than or equal to 0.030 mg/L for two consecutive years or has a
TTHM annual average of less than or equal to 0.020 mg/L and has a HAA5 annual
average of less than or equal to 0.015mg/L for one year may reduce monitoring
to one sample per treatment plant per three year monitoring cycle at a
distribution system location reflecting maximum residence time during the month
of warmest water temperature, with the three-year cycle beginning on January 1
following the quarter in which the system qualifies for reduced
monitoring.
(iii)
Monitoring requirements for source water TOC in order to qualify for reduced
monitoring for TTHM and HAA5 under paragraph (2)(a)(ii) of this section,
surface water systems not monitoring under the provisions of paragraph (d) of
this section must take monthly TOC samples every 30 days at a location prior to
any treatment, beginning April 1, 2008 or earlier, if specified by the
Director. In addition to meeting other criteria for reduced monitoring in
paragraph (2)(a)(ii) of this section, the source water TOC running annual
average must be equal to or less than 4.0 mg/L (based on the most recent four
quarters of monitoring) on a continuing basis at each treatment plant to reduce
or remain on reduced monitoring for TTHM and HAA5. Once qualified for reduced
monitoring for TTHM and HAA5 under paragraph (2)(a)(ii) of this section, a
system may reduce source water TOC monitoring to quarterly TOC samples taken
every 90 days at a location prior to any treatment.
(iv) Systems on a reduced monitoring schedule
may remain on that reduced schedule as long as the average of all samples taken
in the year (for systems which must monitor quarterly) or the result of the
sample (for systems which must monitor no more frequently than annually) is no
more than 0.060 mg/L and 0.045 mg/L for TTHMs and HAA5, respectively. Systems
that do not meet these levels must resume monitoring at the frequency
identified in paragraph (2)(a)(i) of this section in the quarter immediately
following the monitoring period in which the system exceeds 0.060 mg/L or 0.045
mg/L for TTHM or HAA5, respectively. For systems using only ground water not
under the direct influence of surface water and serving fewer than 10,000
persons, if either the TTHM annual average is greater than 0.080 mg/L or the
HAA5 annual average is greater than 0.060 mg/L, the system must go to the
increased monitoring identified in paragraph (2)(a)(i) of this section in the
quarter immediately following the monitoring period in which the system exceeds
0.080 mg/L or 0.060 mg/L for TTHMs or HAA5 respectively.
(v) Systems on increased monitoring may
return to routine monitoring if, after at least one year of monitoring their
TTHM annual average is less than or equal to 0.060 mg/L and their HAA5 annual
average is less than or equal to 0.045 mg/L.
(vi) The Director may return a system to
routine monitoring when appropriate to protect public health.
(b) Chlorite. Community and
non-transient non-community water systems using chlorine dioxide, for
disinfection or oxidation, must conduct monitoring for chlorite.
(i) Routine monitoring.
(A) Daily monitoring. Systems must take daily
samples at the entrance to the distribution system. For any daily sample that
exceeds the chlorite MCL, the system must take additional samples in the
distribution system the following day at the locations required by paragraph
(2)(b)(ii) of this section, in addition to the sample required at the entrance
to the distribution system.
(B)
Monthly monitoring. Systems must take a three-sample set each month in the
distribution system. The system must take one sample at each of the following
locations: near the first customer, at a location representative of average
residence time, and at a location reflecting maximum residence time in the
distribution system. Any additional routine sampling must be conducted in the
same manner (as three-sample sets, at the specified locations). The system may
use the results of additional monitoring conducted under paragraph (2)(b)(ii)
of this section to meet the requirement for monitoring in this
paragraph.
(ii)
Additional monitoring. On each day following a routine sample monitoring result
that exceeds the chlorite MCL at the entrance to the distribution system, the
system is required to take three chlorite distribution system samples at the
following locations: as close to the first customer as possible, in a location
representative of average residence time, and as close to the end of the
distribution system as possible (reflecting maximum residence time in the
distribution system).
(iii) Reduced
monitoring.
(A) Chlorite monitoring at the
entrance to the distribution system required by paragraph (2)(b)(i)(A) of this
section may not be reduced.
(B)
Chlorite monitoring in the distribution system required by paragraph
(2)(b)(i)(B) of this section may be reduced to one three-sample set per quarter
after one year of monitoring where no individual chlorite sample taken in the
distribution system under paragraph (2)(b)(i)(B) of this section has exceeded
the chlorite MCL and the system has not been required to conduct monitoring
under paragraph (2)(b)(ii) of this section. The system may remain on the
reduced monitoring schedule until either any of the three individual chlorite
samples taken monthly in the distribution system under paragraph (2)(b)(i)(B)
of this section exceeds the chlorite MCL or the system is required to conduct
monitoring under paragraph (2)(b)(ii) of this section, at which time the system
must revert to routine monitoring.
(c) Bromate.
(i) Routine monitoring. Community and
nontransient noncommunity systems using ozone, for disinfection or oxidation,
must take one sample per month for each treatment plant in the system using
ozone. Systems must take samples monthly at the entrance to the distribution
system while the ozonation system is operating under normal
conditions.
(ii) Reduced
monitoring.
(A) Until March 31, 2009, systems
required to analyze for bromate may reduce monitoring from monthly to once per
quarter, if the system demonstrates that the average source water bromide
concentration is less than 0.05 mg/L based upon representative monthly bromide
measurements for one year. The system may remain on reduced bromate monitoring
until the running annual average source water bromide concentration, computed
quarterly, is equal to or greater than 0.05 mg/L based upon representative
monthly measurements. If the running annual average source water bromide
concentration is greater than or equal to 0.05 mg/L, the system must resume
routine monitoring required by paragraph (2)(c)(i) of this section in the
following month.
(B) Beginning
April 1, 2009, systems may no longer use the provisions of paragraph
(2)(c)(ii)(A) of this section to qualify for reduced monitoring. A system
required to analyze for bromate may reduce monitoring from monthly to
quarterly, if the system's running annual average bromate concentration is
equal to or less than 0.0025 mg/L based on monthly bromate measurements under
paragraph (2)(c) (i) of this section for the most recent four quarters, with
samples analyzed using Method 317.0 Revision 2.0, 326.0 or 321.8. If a system
has qualified for reduced bromate monitoring under paragraph (2)(c)(ii)(A) of
this section, that system may remain on reduced monitoring as long as the
running annual average of quarterly bromate samples is less than or equal to
0.0025 mg/L based on samples analyzed using Method 317.0 Revision 2.0, 326.0 or
321.8. If the running annual average bromate concentration is greater than
0.0025 mg/L, the system must resume routine monitoring required by (2)(c)(i) of
this section.
(3) Monitoring requirements for disinfectant
residuals.
(a) Chlorine and chloramines.
(i) Routine monitoring. Community and
non-transient non-community water systems that use chlorine or chloramines must
measure the residual disinfectant level in the distribution system at the same
point in the distribution system and at the same time as total coliforms are
sampled, as specified in R309-211. Systems that use surface water may use the
results of residual disinfectant concentration sampling conducted in
R309-215-10(4),
in lieu of taking separate samples.
(ii) In addition, ground water systems shall
take the following readings at each facility a minimum of three times a week:
the total volume of water treated; the type and amount of disinfectant used in
treating the water (clearly indicating the weight if gas feeders are used, or
the percent solution and volume fed if liquid feeders are used); and the
setting of the rotometer valve or injector pump. Surface water systems may use
the results of residual disinfectant concentration sampling conducted under
R309-215-10(3)
for systems which filter, in lieu of taking separate samples.
(iii) Reduced monitoring. Monitoring may not
be reduced.
(b) Chlorine
Dioxide.
(i) Routine monitoring. Community,
nontransient noncommunity, and transient noncommunity water systems that use
chlorine dioxide for disinfection or oxidation must take daily samples at the
entrance to the distribution system. For any daily sample that exceeds the
MRDL, the system must take samples in the distribution system the following day
at the locations required by paragraph (3)(b) (ii) of this section, in addition
to the sample required at the entrance to the distribution system.
(ii) Additional monitoring. On each day
following a routine sample monitoring result that exceeds the MRDL, the system
is required to take three chlorine dioxide distribution system samples. If
chlorine dioxide or chloramines are used to maintain a disinfectant residual in
the distribution system, or if chlorine is used to maintain a disinfectant
residual in the distribution system and there are no disinfection addition
points after the entrance to the distribution system (i.e., no booster
chlorination), the system must take three samples as close to the first
customer as possible, at intervals of at least six hours. If chlorine is used
to maintain a disinfectant residual in the distribution system and there are
one or more disinfection addition points after the entrance to the distribution
system (i.e., booster chlorination), the system must take one sample at each of
the following locations: as close to the first customer as possible, in a
location representative of average residence time, and as close to the end of
the distribution system as possible (reflecting maximum residence time in the
distribution system).
(iii) Reduced
monitoring. Chlorine dioxide monitoring may not be reduced.
(4) Bromide. Systems
required to analyze for bromate may reduce bromate monitoring from monthly to
once per quarter, if the system demonstrates that the average source water
bromide concentration is less than 0.05 mg/L based upon representative monthly
measurements for one year. The system must continue bromide monitoring to
remain on reduced bromate monitoring.
(5) Monitoring plans. Each system required to
monitor under this section must develop and implement a monitoring plan. The
system must maintain the plan and make it available for inspection by the
Director and the general public no later than 30 days following the applicable
compliance dates in R309-210-8(1)(a). All Surface water systems serving more
than 3300 people must submit a copy of the monitoring plan to the Director no
later than the date of the first report required under
R309-105-16(2).
The Director may also require the plan to be submitted by any other system.
After review, the Director may require changes in any plan elements. The plan
must include at least the following elements.
(a) Specific locations and schedules for
collecting samples for any parameters included in this subpart.
(b) How the system will calculate compliance
with MCLs, MRDLs, and treatment techniques.
(c) If approved for monitoring as a
consecutive system, or if providing water to a consecutive system, the Director
may modify the monitoring requirements treating the systems as a single
distribution system, however, the sampling plan shall reflect the entire
distribution system of all interconnected systems.
(6) Compliance requirements.
(a) General requirements.
(i) Where compliance is based on a running
annual average of monthly or quarterly samples or averages and the system fails
to monitor for TTHM, HAA5, or bromate, this failure to monitor will be treated
as a monitoring violation for the entire period covered by the annual average.
Where compliance is based on a running annual average of monthly or quarterly
samples or averages and the system's failure to monitor makes it impossible to
determine compliance with MRDLs for chlorine and chloramines, this failure to
monitor will be treated as a monitoring violation for the entire period covered
by the annual average.
(ii) All
samples taken and analyzed under the provisions of this section shall be
included in determining compliance, even if that number is greater than the
minimum required.
(iii) If, during
the first year of monitoring under R309-210-8, any individual quarter's average
will cause the running annual average of that system to exceed the MCL, the
system is out of compliance at the end of that quarter.
(b) Disinfection byproducts.
(i) TTHMs and HAA5.
(A) For systems monitoring quarterly,
compliance with MCLs in
R309-200-5(3)(c)
shall be based on a running annual arithmetic average, computed quarterly, of
quarterly arithmetic averages of all samples collected by the system as
prescribed by R309-210-8(2)(a).
(B)
For systems monitoring less frequently than quarterly, systems demonstrate MCL
compliance if the average of samples taken that year under the provisions of
R309-210-8(2)(a) does not exceed the MCLs in
R309-200-5(3)(c).
If the average of these samples exceeds the MCL, the system shall increase
monitoring to once per quarter per treatment plant and such a system is not in
violation of the MCL until it has completed one year of quarterly monitoring,
unless the result of fewer than four quarters of monitoring will cause the
running annual average to exceed the MCL, in which case the system is in
violation at the end of that quarter. Systems required to increase monitoring
frequency to quarterly monitoring shall calculate compliance by including the
sample which triggered the increased monitoring plus the following three
quarters of monitoring.
(C) If the
running annual arithmetic average of quarterly averages covering any
consecutive four-quarter period exceeds the MCL, the system is in violation of
the MCL and shall notify the public pursuant to R309-220, in addition to
reporting to the Director pursuant to
R309-105-16.
(D) If a PWS fails to complete four
consecutive quarters of monitoring, compliance with the MCL for the last
four-quarter compliance period shall be based on an average of the available
data.
(ii) Chlorite.
Compliance shall be based on an arithmetic average of each three sample set
taken in the distribution system as prescribed by R309-210-8(2)(b)(i)(B) and
(2)(b)(ii). If the arithmetic average of any three sample sets exceeds the MCL,
the system is in violation of the MCL and shall notify the public pursuant to
R309-220, in addition to reporting to the Director pursuant to
R309-105-16.
(iii) Bromate. Compliance shall be based on a
running annual arithmetic average, computed quarterly, of monthly samples (or,
for months in which the system takes more than one sample, the average of all
samples taken during the month) collected by the system as prescribed by
R309-210-8(2)(c). If the average of samples covering any consecutive
four-quarter period exceeds the MCL, the system is in violation of the MCL and
shall notify the public pursuant to R309-220, in addition to reporting to the
Director pursuant to
R309-105-16.
If a PWS fails to complete 12 consecutive months' monitoring, compliance with
the MCL for the last four-quarter compliance period shall be based on an
average of the available data.
(c) Disinfectant residuals.
(i) Chlorine and chloramines.
(A) Compliance shall be based on a running
annual arithmetic average, computed quarterly, of monthly averages of all
samples collected by the system under R309-210-8(3)(a). If the average covering
any consecutive four-quarter period exceeds the MRDL, the system is in
violation of the MRDL and shall notify the public pursuant to R309-220, in
addition to reporting to the Director pursuant to
R309-105-16.
(B) In cases where systems switch between the
use of chlorine and chloramines for residual disinfection during the year,
compliance shall be determined by including together all monitoring results of
both chlorine and chloramines in calculating compliance. Reports submitted
pursuant to
R309-105-16
shall clearly indicate which residual disinfectant was analyzed for each
sample.
(ii) Chlorine
dioxide.
(A) Acute violations. Compliance
shall be based on consecutive daily samples collected by the system under
R309-210-8(3)(b). If any daily sample taken at the entrance to the distribution
system exceeds the MRDL, and on the following day one (or more) of the three
samples taken in the distribution system exceed the MRDL, the system is in
violation of the MRDL and shall take immediate corrective action to lower the
level of chlorine dioxide below the MRDL and shall notify the public pursuant
to the procedures for acute health risks in
R309-220-5.
Failure to take samples in the distribution system the day following an
exceedance of the chlorine dioxide MRDL at the entrance to the distribution
system will also be considered an MRDL violation and the system shall notify
the public of the violation in accordance with the provisions for acute
violations under
R309-220-5
in addition to reporting the Director pursuant to
R309-105-16.
(B) Nonacute violations. Compliance shall be
based on consecutive daily samples collected by the system under
R309-210-8(3)(b). If any two consecutive daily samples taken at the entrance to
the distribution system exceed the MRDL and all distribution system samples
taken are below the MRDL, the system is in violation of the MRDL and shall take
corrective action to lower the level of chlorine dioxide below the MRDL at the
point of sampling and will notify the public pursuant to the procedures for
nonacute health risks in
R309-220-6
in addition to reporting to the Director pursuant to
R309-105-16.
Failure to monitor at the entrance to the distribution system the day following
an exceedance of the chlorine dioxide MRDL at the entrance to the distribution
system is also an MRDL violation and the system shall notify the public of the
violation in accordance with the provisions for nonacute violations under
R309-220-6
in addition to reporting to the Director pursuant to
R309-105-16.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.