Utah Admin. Code R315-261-1084 - Air Emission Standards for Tanks and Containers - Standards: Tanks
(a) Section
R315-261-1084 applies to the
control of air pollutant emissions from tanks that Subsection
R315-261-1082(b)
references the use of Section
R315-261-1084 for the air
emission control.
(b) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall control air pollutant emissions from each tank subject to
Section R315-261-1084 in accordance with
the requirements of Subsection
R315-261-1084(b)(1)
or R315-261-1084(b)(2)
as applicable:
(1) For a tank that manages
hazardous secondary material that meets the of the conditions specified in
Subsections R315-261-1084(b)(1)(i)
through R315-261-1084(b)(1)(iii),
the remanufacturer or other person that stores or treats the hazardous
secondary material shall control air pollutant emissions from the tank in
accordance with the Tank Level 1 controls specified in Subsection
R315-261-1084(c)
or the Tank Level 2 controls specified in Subsection
R315-261-1084(d).
(i) The hazardous secondary material in the
tank has a maximum organic vapor pressure that is less than the maximum organic
vapor pressure limit for the tank's design capacity category as follows:
(A) For a tank design capacity equal to or
greater than 151 m3, the maximum organic vapor
pressure limit for the tank is 5.2 kPa.
(B) For a tank design capacity equal to or
greater than 75 m3 but less than 151
m3, the maximum organic vapor pressure limit for the
tank is 27.6 kPa.
(C) For a tank
design capacity less than 75 m3, the maximum organic
vapor pressure limit for the tank is 76.6 kPa.
(ii) The hazardous secondary material in the
tank is not heated by the remanufacturer or other person that stores or treats
the hazardous secondary material to a temperature that is greater than the
temperature that the maximum organic vapor pressure of the hazardous secondary
material is determined for complying with Subsection
R315-261-1084(b)(1)(i).
(2) For a tank that manages
hazardous secondary material that does not meet the of the conditions specified
in Subsections R315-261-1084(b)(1)(i)
through R315-261-1084(b)(1)(iii),
the remanufacturer or other person that stores or treats the hazardous
secondary material shall control air pollutant emissions from the tank by using
Tank Level 2 controls in accordance with the requirements of Subsection
R315-261-1084(d).
An example of tanks required to use Tank Level 2 controls is a tank that the
hazardous secondary material in the tank has a maximum organic vapor pressure
that is equal to or greater than the maximum organic vapor pressure limit for
the tank's design capacity category as specified in Subsection
R315-261-1084(b)(1)(i).
(c) Remanufacturers or other
persons that store or treats the hazardous secondary material controlling air
pollutant emissions from a tank using Tank Level 1 controls shall meet the
requirements specified in Subsections
R315-261-1084(c)(1)
through R315-261-1084(c)(4):
(1) The remanufacturer or other person that
stores or treats that hazardous secondary material shall determine the maximum
organic vapor pressure for a hazardous secondary material to be managed in the
tank using Tank Level 1 controls before the first time the hazardous secondary
material is placed in the tank. The maximum organic vapor pressure shall be
determined using the procedures specified in Subsection
R315-261-1083(c).
Thereafter, the remanufacturer or other person that stores or treats the
hazardous secondary material shall perform a new determination if changes to
the hazardous secondary material managed in the tank could potentially cause
the maximum organic vapor pressure to increase to a level that is equal to or
greater than the maximum organic vapor pressure limit for the tank design
capacity category specified in Subsection
R315-261-1084(b)(1)(i),
as applicable to the tank.
(2) The
tank shall be equipped with a fixed roof designed to meet the specifications in
Subsections R315-261-1084(c)(2)(i)
through R315-261-1084(c)(2)(iii):
(i) The fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the hazardous secondary material in the tank. The fixed roof may be a separate
cover installed on the tank, for example, a removable cover mounted on an
open-top tank, or may be an integral part of the tank structural design, for
example, a horizontal cylindrical tank equipped with a hatch.
(ii) The fixed roof shall be installed in a
manner so that there are no visible cracks, holes, gaps, or other open spaces
between roof section joints or between the interface of the roof edge and the
tank wall.
(iii) Each opening in
the fixed roof, and any manifold system associated with the fixed roof, shall
be either:
(A) equipped with a closure device
designed to operate so that if the closure device is secured in the closed
position there are no visible cracks, holes, gaps, or other open spaces in the
closure device or between the perimeter of the opening and the closure device;
or
(B) connected by a closed-vent
system that is vented to a control device. The control device shall remove or
destroy organics in the vent stream, and shall be operating if hazardous
secondary material is managed in the tank, except as provided for in
Subsections R315-261-1084(c)(2)(iii)(B)(I)
and R315-261-1084(c)(2)(iii)(B)(II).
(I) During periods when it is necessary to
provide access to the tank for performing the activities of Subsection
R315-261-1084(c)(2)(iii)(B)(II),
venting of the vapor headspace underneath the fixed roof to the control device
is not required, opening of closure devices is allowed, and removal of the
fixed roof is allowed. Following completion of the activity, the remanufacturer
or other person that stores or treats the hazardous secondary material shall
promptly secure the closure device in the closed position or reinstall the
cover, as applicable, and resume operation of the control device.
(II) During periods of routine inspection,
maintenance, or other activities needed for normal operations, and for removal
of accumulated sludge or other residues from the bottom of the tank.
(iv) The fixed roof and
its closure devices shall be made of suitable materials that will minimize
exposure of the hazardous secondary material to the atmosphere, to the extent
practical, and will maintain the integrity of the fixed roof and closure
devices throughout their intended service life. Factors to be considered when
selecting the materials for and designing the fixed roof and closure devices
shall include: organic vapor permeability, the effects of any contact with the
hazardous secondary material or its vapors managed in the tank; the effects of
outdoor exposure to wind, moisture, and sunlight; and the operating practices
used for the tank that has a fixed roof installed.
(3) If a hazardous secondary material is in
the tank, the fixed roof shall be installed with each closure device secured in
the closed position except as follows:
(i)
Opening of closure devices or removal of the fixed roof is allowed in
accordance with Subsections
R315-261-1084(c)(3)(i)(A)
and R315-261-1084(c)(3)(i)(B):
(A) To provide access to the tank for
performing routine inspection, maintenance, or other activities needed for
normal operations. Examples of these activities include those times when a
worker needs to open a port to sample the liquid in the tank, or when a worker
needs to open a hatch to maintain or repair equipment. Following completion of
the activity, the remanufacturer or other person that stores or treats the
hazardous secondary material shall promptly secure the closure device in the
closed position or reinstall the cover, as applicable, to the tank.
(B) To remove accumulated sludge or other
residues from the bottom of tank.
(ii) Opening of a spring-loaded
pressure-vacuum relief valve, conservation vent, or similar type of pressure
relief device that vents to the atmosphere is allowed during normal operations
for maintaining the tank internal pressure in accordance with the tank design
specifications. The device shall be designed to operate with no detectable
organic emissions if the device is secured in the closed position. The settings
that cause the device to open shall be established so that the device remains
in the closed position if the tank internal pressure is within the internal
pressure operating range determined by the remanufacturer or other person that
stores or treats the hazardous secondary material based on the tank
manufacturer recommendations, applicable rules, fire protection and prevention
codes, standard engineering codes and practices, or other requirements for the
safe handling of flammable, ignitable, explosive, reactive, or hazardous
materials. Examples of normal operating conditions that may require these
devices to open are during those times when the tank internal pressure exceeds
the internal pressure operating range for the tank as a result of loading
operations or diurnal ambient temperature fluctuations.
(iii) Opening of a safety device, as defined
in Section R315-261-1081, is allowed at any
time conditions require doing so to avoid an unsafe condition.
(4) The remanufacturer or other
person that stores or treats the hazardous secondary material shall inspect the
air emission control equipment in accordance with the requirements in
Subsections R315-261-1084(c)(4)(i)
through R315-261-1084
(c)(4)(iv).
(i) The fixed roof and its closure devices
shall be visually inspected by the remanufacturer or other person that stores
or treats the hazardous secondary material to check for defects that could
result in air pollutant emissions. Defects include visible cracks, holes, or
gaps in the roof sections or between the roof and the tank wall; broken,
cracked, or otherwise damaged seals or gaskets on closure devices; and broken
or missing hatches, access covers, caps, or other closure devices.
(ii) The remanufacturer or other person that
stores or treats the hazardous secondary material shall perform an initial
inspection of the fixed roof and its closure devices on or before the date that
the tank becomes subject to Section
R315-261-1084. Thereafter, the
remanufacturer or other person that stores or treats the hazardous secondary
material shall perform the inspections at least once each year except under the
special conditions provided for in Subsection
R315-261-1084(l).
(iii) In the event that a defect is detected,
the remanufacturer or other person that stores or treats the hazardous
secondary material shall repair the defect in accordance with the requirements
of Subsection R315-261-1084(k).
(iv) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(d) Remanufacturers or
other persons that store or treat the hazardous secondary material controlling
air pollutant emissions from a tank using Tank Level 2 controls shall use one
of the tanks specified in Subsections
R315-261-1084(d)(1)
through R315-261-1084(d)(5):
(1) A fixed roof tank equipped with an
internal floating roof in accordance with the requirements specified in
Subsection R315-261-1084(e);
(2) A tank equipped with an external floating
roof in accordance with the requirements specified in Subsection
R315-261-1084(f);
(3) A tank vented through a closed-vent
system to a control device in accordance with the requirements specified in
Subsection R315-261-1084(g);
(4) A pressure tank designed and operated in
accordance with the requirements specified in Subsection
R315-261-1084(h);
or
(5) A tank located inside an
enclosure that is vented through a closed-vent system to an enclosed combustion
control device in accordance with the requirements specified in Subsection
R315-261-1084(i).
(e) The remanufacturer or other
person that stores or treats the hazardous secondary material who controls air
pollutant emissions from a tank using a fixed roof with an internal floating
roof shall meet the requirements specified in Subsections
R315-261-1084(e)(1)
through R315-261-1084(e)(3).
(1) The tank shall be equipped with a fixed
roof and an internal floating roof in accordance with the requirements in
Subsections R315-261-1084(e)(1)(i)
through R315-261-1084(e)(1)(iii):
(i) The internal floating roof shall be
designed to float on the liquid surface except when the floating roof shall be
supported by the leg supports.
(ii)
The internal floating roof shall be equipped with a continuous seal between the
wall of the tank and the floating roof edge that meets either of the
requirements in Subsection
R315-261-1084(e)(1)(ii)(A)
or R315-261-1084(e)(1)(ii)(B):
(A) A single continuous seal that is either a
liquid-mounted seal or a metallic shoe seal, as defined in Section
R315-261-1081; or
(B) Two continuous seals mounted one above
the other. The lower seal may be a vapor-mounted seal.
(iii) The internal floating roof shall meet
the specifications of Subsections
R315-261-1084(e)(1)(iii)(A)
through R315-261-1084(e)(1)(iii)(F):
(A) Each opening in a noncontact internal
floating roof except for automatic bleeder vents, vacuum breaker vents, and the
rim space vents is to provide a projection below the liquid surface.
(B) Each opening in the internal floating
roof shall be equipped with a gasketed cover or a gasketed lid except for leg
sleeves, automatic bleeder vents, rim space vents, column wells, ladder wells,
sample wells, and stub drains.
(C)
Each penetration of the internal floating roof for sampling shall have a slit
fabric cover that covers at least 90% of the opening.
(D) Each automatic bleeder vent and rim space
vent shall be gasketed.
(E) Each
penetration of the internal floating roof that allows for passage of a ladder
shall have a gasketed sliding cover.
(F) Each penetration of the internal floating
roof that allows for passage of a column supporting the fixed roof shall have a
flexible fabric sleeve seal or a gasketed sliding cover.
(2) The remanufacturer or other
person that stores or treats the hazardous secondary material shall operate the
tank in accordance with the requirements of Subsections
R315-261-1084(e)(2)(i)
through R315-261-1084(e)(2)(iii):
(i) If the floating roof is resting on the
leg supports, the process of filling, emptying, or refilling shall be
continuous and shall be finished as soon as practical.
(ii) Automatic bleeder vents are to be always
set closed if the roof is floating, except when the roof is being floated off
or is being landed on the leg supports.
(iii) Before filling the tank, each cover,
access hatch, gauge float well or lid on any opening in the internal floating
roof shall be bolted or fastened closed, that is, no visible gaps. Rim space
vents are to be set to open only if the internal floating roof is not floating
or if the pressure beneath the rim exceeds the manufacturer's recommended
setting.
(3) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall inspect the internal floating roof in accordance with the
procedures specified as follows:
(i) The
floating roof and its closure devices shall be visually inspected by the
remanufacture or other person that stores or treats the hazardous secondary
material to check for defects that could result in air pollutant emissions.
Defects include: The internal floating roof is not floating on the surface of
the liquid inside the tank; liquid has accumulated on top of the internal
floating roof; any portion of the roof seals have detached from the roof rim;
holes, tears, or other openings are visible in the seal fabric; the gaskets no
longer close off the hazardous secondary material surface from the atmosphere;
or the slotted membrane has more than 10% open area.
(ii) The remanufacturer or other person that
stores or treats the hazardous secondary material shall inspect the internal
floating roof components as follows except as provided in Subsection
R315-261-1084(e)(3)(iii):
(A) Visually inspect the internal floating
roof components through openings on the fixed roof, for example, manholes and
roof hatches, at least once each 12 month period after initial fill;
and
(B) Visually inspect the
internal floating roof, primary seal, secondary seal, if one is in service,
gaskets, slotted membranes, and sleeve seals, if any, each time the tank is
emptied and degassed and at least each 10 year period.
(iii) As an alternative to performing the
inspections specified in Subsection
R315-261-1084(e)(3)(ii)
for an internal floating roof equipped with two continuous seals mounted one
above the other, the remanufacturer or other person that stores or treats the
hazardous secondary material may visually inspect the internal floating roof,
primary and secondary seals, gaskets, slotted membranes, and sleeve seals, if
any, each time the tank is emptied and degassed and at least each five year
period.
(iv) Before each inspection
required by Subsection
R315-261-1084(e)(3)(ii)
or R315-261-1084(e)(3)(iii),
the remanufacturer or other person that stores or treats the hazardous
secondary material shall notify the director in advance of each inspection to
provide the director with the opportunity to have an observer present during
the inspection. The remanufacturer or other person that stores or treats the
hazardous secondary material shall notify the director of the date and location
of the inspection as follows:
(A) Before each
visual inspection of an internal floating roof in a tank that has been emptied
and degassed, written notification shall be prepared and sent by the
remanufacturer or other person that stores or treats the hazardous secondary
material so that it is received by the director at least 30 calendar days
before refilling the tank except when an inspection is not planned as provided
for in Subsection R315-261-1084(e)(3)(iv)(B).
(B) If a visual inspection is not planned and
the remanufacturer or other person that stores or treats the hazardous
secondary material could not have known about the inspection 30 calendar days
before refilling the tank, the remanufacturer or other person that stores or
treats the hazardous secondary material shall notify the director as soon as
possible, but no later than seven calendar days before refilling of the tank.
This notification may be made by telephone and immediately followed by a
written explanation for why the inspection is unplanned. Alternatively, written
notification, including the explanation for the unplanned inspection, may be
sent so that it is received by the director at least seven calendar days before
refilling the tank.
(v)
In the event that a defect is detected, the remanufacturer or other person that
stores or treats the hazardous secondary material shall repair the defect in
accordance with the requirements of Subsection
R315-261-1084(k).
(vi) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(4) Safety devices, as defined in
Section R315-261-1081, may be installed
and operated as necessary on any tank complying with the requirements of
Subsection R315-261-1084(e).
(f) The remanufacturer or other
person that stores or treats the hazardous secondary material who controls air
pollutant emissions from a tank using an external floating roof shall meet the
requirements specified in Subsections
R315-261-1084(f)(1)
through R315-261-1084(f)(3).
(1) The remanufacturer or other person that
stores or treats the hazardous secondary material shall design the external
floating roof in accordance with the requirements of Subsections
R315-261-1084(f)(1)(i)
and R315-261-1084(f)(1)(ii):
(i) The external floating roof shall be
designed to float on the liquid surface except when the floating roof shall be
supported by the leg supports.
(ii)
The floating roof shall be equipped with two continuous seals, one above the
other, between the wall of the tank and the roof edge. The lower seal is
referred to as the primary seal, and the upper seal is referred to as the
secondary seal.
(A) The primary seal shall be
a liquid-mounted seal or a metallic shoe seal, as defined in Section
R315-261-1081. The total area of
the gaps between the tank wall and the primary seal may not exceed 212 square
centimeters per meter of tank diameter, and the width of any portion of these
gaps may not exceed 3.8 centimeters. If a metallic shoe seal is used for the
primary seal, the metallic shoe seal shall be designed so that one end extends
into the liquid in the tank and the other end extends a vertical distance of at
least 61 centimeters above the liquid surface.
(B) The secondary seal shall be mounted above
the primary seal and cover the annular space between the floating roof and the
wall of the tank. The total area of the gaps between the tank wall and the
secondary seal may not exceed 21.2 square centimeters per meter of tank
diameter, and the width of any portion of these gaps may not exceed 1.3
centimeters.
(iii) The
external floating roof shall meet the specifications in Subsections
R315-261-1084(f)(1)(iii)(A)
through R315-261-1084(f)(1)(iii)(I):
(A) Except for automatic bleeder vents,
vacuum breaker vents, and rim space vents, each opening in a noncontact
external floating roof shall provide a projection below the liquid
surface.
(B) Except for automatic
bleeder vents, rim space vents, roof drains, and leg sleeves, each opening in
the roof shall be equipped with a gasketed cover, seal, or lid.
(C) Each access hatch and each gauge float
well shall be equipped with a cover designed to be bolted or fastened if the
cover is secured in the closed position.
(D) Each automatic bleeder vent and each rim
space vent shall be equipped with a gasket.
(E) Each roof drain that empties into the
liquid managed in the tank shall be equipped with a slotted membrane fabric
cover that covers at least 90% of the area of the opening.
(F) Each unslotted and slotted guide pole
well shall be equipped with a gasketed sliding cover or a flexible fabric
sleeve seal.
(G) Each unslotted
guide pole shall be equipped with a gasketed cap on the end of the
pole.
(H) Each slotted guide pole
shall be equipped with a gasketed float or other device that closes off the
liquid surface from the atmosphere.
(I) Each gauge hatch and each sample well
shall be equipped with a gasketed cover.
(2) The remanufacturer or other person that
stores or treats the hazardous secondary material shall operate the tank in
accordance with the requirements of Subsections
R315-261-1084(f)(2)(i)
through R315-261-1084(f)(2)(viii):
(i) If the floating roof is resting on the
leg supports, the process of filling, emptying, or refilling shall be
continuous and shall be finished as soon as practical.
(ii) Except for automatic bleeder vents, rim
space vents, roof drains, and leg sleeves, each opening in the roof shall
always be secured and maintained in a closed position except when the closure
device shall be open for access.
(iii) Covers on each access hatch and each
gauge float well shall be bolted or fastened if secured in the closed
position.
(iv) Automatic bleeder
vents shall always be set closed if the roof is floating, except when the roof
is being floated off or is being landed on the leg supports.
(v) Rim space vents shall be set to open only
at those times that the roof is being floated off the roof leg supports or if
the pressure beneath the rim seal exceeds the manufacturer's recommended
setting.
(vi) The cap on the end of
each unslotted guide pole shall always be secured in the closed position except
when measuring the level or collecting samples of the liquid in the
tank.
(vii) The cover on each gauge
hatch or sample well shall always be secured in the closed position except when
the hatch or well shall be opened for access.
(viii) Both the primary seal and the
secondary seal shall completely cover the annular space between the external
floating roof and the wall of the tank in a continuous fashion except during
inspections.
(3) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall inspect the external floating roof in accordance with the
procedures specified as follows:
(i) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall measure the external floating roof seal gaps in accordance with
the requirements in Subsections
R315-261-1084(f)(3)(i)(A)
through R315-261-1084(f)(3)(i)(F):
(A) The remanufacturer or other person that
stores or treats the hazardous secondary material shall perform measurements of
gaps between the tank wall and the primary seal within 60 calendar days after
initial operation of the tank following installation of the floating roof and,
thereafter, at least once each 5 year period.
(B) The remanufacturer or other person that
stores or treats the hazardous secondary material shall perform measurements of
gaps between the tank wall and the secondary seal within 60 calendar days after
initial operation of the tank following installation of the floating roof and,
thereafter, at least once each yea r.
(C) If a tank stops holding hazardous
secondary material for a period of 1 year or more, subsequent introduction of
hazardous secondary material into the tank shall be considered an initial
operation for the purposes of Subsections
R315-261-1084(f)(3)(i)(A)
and R315-261-1084(f)(3)(i)(B).
(D) The remanufacturer or other person that
stores or treats the hazardous secondary material shall determine the total
surface area of gaps in the primary seal and in the secondary seal individually
using the procedure contained in Subsections
R315-261-1084(f)(3)(i)(D)(I)
through R315-261-1084(f)(3)(i)(D)(IV):
(I) The seal gap measurements shall be
performed at one or more floating roof levels if the roof is floating off the
roof supports.
(II) Seal gaps, if
any, shall be measured around the entire perimeter of the floating roof in each
place where a 0.32-centimeter diameter uniform probe passes freely, without
forcing or binding against the seal, between the seal and the wall of the tank
and measure the circumferential distance of each location.
(III) For a seal gap measured under
Subsection R315-261-1084(f)(3),
the gap surface area shall be determined by using probes of various widths to
measure accurately the actual distance from the tank wall to the seal and
multiplying each width by its respective circumferential distance.
(IV) The total gap area shall be calculated
by adding the gap surface areas determined for each identified gap location for
the primary seal and the secondary seal individually, and then dividing the sum
for each seal type by the nominal diameter of the tank. These total gap areas
for the primary seal and secondary seal are then compared to the respective
standards for the seal type as specified in Subsection
R315-261-1084(f)(1)(ii).
(E) In the event that the seal gap
measurements do not conform to the specifications in Subsection
R315-261-1084(f)(1)(ii),
the remanufacturer or other person that stores or treats the hazardous
secondary material shall repair the defect in accordance with the requirements
of Subsection R315-261-1084(k).
(F) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(ii) The remanufacturer or other
person that stores or treats the hazardous secondary material shall visually
inspect the external floating roof in accordance with the requirements in
Subsections R315-261-1084(f)(3)(ii)(A)
through R315-261-1084(f)(3)(ii)(D):
(A) The floating roof and its closure devices
shall be visually inspected by the remanufacturer or other person that stores
or treats the hazardous secondary material to check for defects that could
result in air pollutant emissions. Defects include: Holes, tears, or other
openings in the rim seal or seal fabric of the floating roof; a rim seal
detached from the floating roof; the floating roof deck or a portion of the
floating roof deck being submerged below the surface of the liquid in the tank;
broken, cracked, or otherwise damaged seals or gaskets on closure devices; and
broken or missing hatches, access covers, caps, or other closure
devices.
(B) The remanufacturer or
other person that stores or treats the hazardous secondary material shall
perform an initial inspection of the external floating roof and its closure
devices on or before the date that the tank becomes subject to Section
R315-261-1084. Thereafter, the
remanufacturer or other person that stores or treats the hazardous secondary
material shall perform the inspections at least once each year except for the
special conditions provided for in Subsection
R315-261-1084(l).
(C) In the event that a defect is detected,
the remanufacturer or other person that stores or treats the hazardous
secondary material shall repair the defect in accordance with the requirements
of Subsection R315-261-1084(k).
(D) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(iii) Before each inspection
required by Subsection
R315-261-1084(f)(3)(i)
or R315-261-1084(f)(3)(ii),
the remanufacturer or other person that stores or treats the hazardous
secondary material shall notify the director in advance of each inspection to
provide the director with the opportunity to have an observer present during
the inspection. The remanufacturer or other person that stores or treats the
hazardous secondary material shall notify the director of the date and location
of the inspection as follows:
(A) Before each
inspection to measure external floating roof seal gaps as required under
Subsection R315-261-1084(f)(3)(i),
written notification shall be prepared and sent by the remanufacturer or other
person that stores or treats the hazardous secondary material so that it is
received by the director at least 30 calendar days before the date the
measurements are scheduled to be performed.
(B) Before each visual inspection of an
external floating roof in a tank that has been emptied and degassed, written
notification shall be prepared and sent by the remanufacturer or other person
that stores or treats the hazardous secondary material so that it is received
by the director at least 30 calendar days before refilling the tank except when
an inspection is not planned as provided for in Subsection
R315-261-1084(f)(3)(iii)(C).
(C) If a visual inspection is not planned and
the remanufacturer or other person that stores or treats the hazardous
secondary material could not have known about the inspection 30 calendar days
before refilling the tank, the owner or operator shall notify the director as
soon as possible, but no later than seven calendar days before refilling of the
tank. This notification may be made by telephone and immediately followed by a
written explanation for why the inspection is unplanned. Alternatively, written
notification, including the explanation for the unplanned inspection, may be
sent so that it is received by the director at least seven calendar days before
refilling the tank.
(4) Safety devices, as defined in Section
R315-261-1081, may be installed
and operated as necessary on any tank complying with the requirements of
Subsection R315-261-1084(f).
(g) The remanufacturer or other person that
stores or treats the hazardous secondary material who controls air pollutant
emissions from a tank by venting the tank to a control device shall meet the
requirements specified in Subsections
R315-261-1084(g)(1)
through R315-261-1084(g)(3).
(1) The tank shall be covered by a fixed roof
and vented directly through a closed-vent system to a control device in
accordance with the requirements specified in Subsections
R315-261-1084(g)(1)(i)
through R315-261-1084(g)(1)(iv):
(i) The fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the liquid in the tank.
(ii) Each
opening in the fixed roof not vented to the control device shall be equipped
with a closure device. If the pressure in the vapor headspace underneath the
fixed roof is less than atmospheric pressure when the control device is
operating, the closure devices shall be designed to operate so that if the
closure device is secured in the closed position there are no visible cracks,
holes, gaps, or other open spaces in the closure device or between the
perimeter of the cover opening and the closure device. If the pressure in the
vapor headspace underneath the fixed roof is equal to or greater than
atmospheric pressure when the control device is operating, the closure device
shall be designed to operate with no detectable organic emissions.
(iii) The fixed roof and its closure devices
shall be made of suitable materials that will minimize exposure of the
hazardous secondary material to the atmosphere, to the extent practical, and
will maintain the integrity of the fixed roof and closure devices throughout
their intended service life. Factors to be considered when selecting the
materials for and designing the fixed roof and closure devices shall include:
Organic vapor permeability, the effects of any contact with the liquid and its
vapor managed in the tank; the effects of outdoor exposure to wind, moisture,
and sunlight; and the operating practices used for the tank that has a fixed
roof installed.
(iv) The
closed-vent system and control device shall be designed and operated in
accordance with the requirements of Section
R315-261-1087.
(2) If a hazardous secondary
material is in the tank, the fixed roof shall be installed with each closure
device secured in the closed position and the vapor headspace underneath the
fixed roof vented to the control device except as follows:
(i) Venting to the control device is not
required, and opening of closure devices or removal of the fixed roof is
allowed in accordance with Subsections
R315-261-1084(g)(2)(i)(A)
and R315-261-1084(g)(2)(i)(B):
(A) To provide access to the tank for
performing routine inspection, maintenance, or other activities needed for
normal operations. Examples of these activities include those times when a
worker needs to open a port to sample liquid in the tank, or when a worker
needs to open a hatch to maintain or repair equipment. Following completion of
the activity, the remanufacturer or other person that stores or treats the
hazardous secondary material shall promptly secure the closure device in the
closed position or reinstall the cover, as applicable, to the tank.
(B) To remove accumulated sludge or other
residues from the bottom of a tank.
(ii) Opening of a safety device, as defined
in Section R315-261-1081, is allowed at any
time conditions require doing so to avoid an unsafe condition.
(3) The remanufacturer or other
person that stores or treats the hazardous secondary material shall inspect and
monitor the air emission control equipment in accordance with the procedures
specified in Subsections
R315-261-1084(g)(3)(i)
through R315-261-1084(g)(3)(v):
(i) The fixed roof and its closure devices
shall be visually inspected by the remanufacturer or other person that stores
or treats the hazardous secondary material to check for defects that could
result in air pollutant emissions. Defects include visible cracks, holes, or
gaps in the roof sections or between the roof and the tank wall; broken,
cracked, or otherwise damaged seals or gaskets on closure devices; and broken
or missing hatches, access covers, caps, or other closure devices.
(ii) The closed-vent system and control
device shall be inspected and monitored by the remanufacturer or other person
that stores or treats the hazardous secondary material in accordance with the
procedures specified in Section
R315-261-1087.
(iii) The remanufacturer or other person that
stores or treats the hazardous secondary material shall perform an initial
inspection of the air emission control equipment on or before the date that the
tank becomes subject to Section
R315-261-1084. Thereafter, the
remanufacturer or other person that stores or treats the hazardous secondary
material shall perform the inspections at least once each year except for the
special conditions provided for in Subsection
R315-261-1084(l).
(iv) In the event that a defect is detected,
the remanufacture or other person that stores or treats the hazardous secondary
material shall repair the defect in accordance with the requirements of
Subsection R315-261-1084(k).
(v) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(h) The remanufacturer
or other person that stores or treats the hazardous secondary material who
controls air pollutant emissions by using a pressure tank shall meet the
requirements of Subsections
R315-261-1084(h)(1)
through R315-261-1084(h)(3).
(1) The tank shall be designed not to vent to
the atmosphere as a result of compression of the vapor headspace in the tank
during filling of the tank to its design capacity.
(2) Each tank opening shall be equipped with
closure devices designed to operate with no detectable organic emissions as
determined using the procedure specified in Subsection
R315-261-1083(d).
(3) If a hazardous secondary material is in
the tank, the tank shall be operated as a closed system that does not vent to
the atmosphere except under either of the conditions specified in Subsection
R315-261-1084(h)(3)(i)
or R315-261-1084(h)(3)(ii).
(i) At those times when opening of a safety
device, as defined in Section
R315-261-1081, is required to
avoid an unsafe condition.
(ii) At
those times when purging of inerts from the tank is required and the purge
stream is routed to a closed-vent system and control device designed and
operated in accordance with the requirements of Section
R315-261-1087.
(i) The
remanufacturer or other person that stores or treats the hazardous secondary
material who controls air pollutant emissions by using an enclosure vented
through a closed-vent system to an enclosed combustion control device shall
meet the requirements specified in Subsections
R315-261-1084(i)(1)
through R315-261-1084(i)(4).
(1) The tank shall be located inside an
enclosure. The enclosure shall be designed and operated in accordance with the
criteria for a permanent total enclosure as specified in "Procedure T -
Criteria for and Verification of a Permanent or Temporary Total Enclosure"
under 40 CFR
52.741, appendix B. The enclosure may have
permanent or temporary openings to allow worker access; passage of material
into or out of the enclosure by conveyor, vehicles, or other mechanical means;
entry of permanent mechanical or electrical equipment; or direct airflow into
the enclosure. The remanufacturer or other person that stores or treats the
hazardous secondary material shall perform the verification procedure for the
enclosure as specified in Section 5.0 to "Procedure T - Criteria for and
Verification of a Permanent or Temporary Total Enclosure" initially when the
enclosure is first installed and, thereafter, annually.
(2) The enclosure shall be vented through a
closed-vent system to an enclosed combustion control device that is designed
and operated in accordance with the standards for either a vapor incinerator,
boiler, or process heater specified in Section
R315-261-1087.
(3) Safety devices, as defined in Section
R315-261-1081, may be installed
and operated as necessary on any enclosure, closed-vent system, or control
device used to comply with the requirements of Subsections
R315-261-1084(i)(1)
and R315-261-1084(i)(2).
(4) The remanufacturer or other person that
stores or treats the hazardous secondary material shall inspect and monitor the
closed-vent system and control device as specified in Section
R315-261-1087.
(j) The remanufacturer or other
person that stores or treats the hazardous secondary material shall transfer
hazardous secondary material to a tank subject to Section
R315-261-1084 in accordance with
the requirements of Subsection
R315-261-1084(j)(1)
or R315-261-1084(j)(2):
(1) Transfer of hazardous secondary material,
except as provided in Subsection
R315-261-1084(j)(2),
to the tank from another tank subject to Section
R315-261-1084 shall be conducted
using continuous hard piping or another closed system that does not allow
exposure of the hazardous secondary material to the atmosphere. For complying
with this provision, an individual drain system is considered to be a closed
system if it meets the requirements of 40 CFR part 63, subpart RR - National
Emission Standards for Individual Drain Systems.
(2) The requirements of Subsection
R315-261-1084(j)(1)
do not apply when transferring a hazardous secondary material to the tank under
any of the conditions specified in Subsections
R315-261-1084(j)(2)(i)
through R315-261-1084(j)(2)(iii):
(i) The hazardous secondary material meets
the average VO concentration conditions specified in Subsection
R315-261-1082(c)
at the point of material origination.
(ii) The hazardous secondary material has
been treated by an organic destruction or removal process to meet the
requirements in Subsection
R315-261-1082(c)(2).
(iii) The hazardous secondary material meets
the requirements of Subsection
R315-261-1082(c)(4).
(k) The remanufacturer
or other person that stores or treats the hazardous secondary material shall
repair each defect detected during an inspection performed in accordance with
the requirements of Subsection
R315-261-1084(c)(4),
R315-261-1084(e)(3),
R315-261-1084(f)(3),
or R315-261-1084(g)(3)
as follows:
(1) The remanufacturer or other
person that stores or treats the hazardous secondary material shall make first
efforts at repair of the defect no later than five calendar days after
detection, and repair shall be finished as soon as possible but no later than
45 calendar days after detection except as provided in Subsection
R315-261-1084(k)(2).
(2) Repair of a defect may be delayed beyond
45 calendar days if the remanufacturer or other person that stores or treats
the hazardous secondary material determines that repair of the defect requires
emptying or temporary removal from service of the tank and no alternative tank
capacity is available at the site to accept the hazardous secondary material
normally managed in the tank. In this case, the remanufacturer or other person
that stores or treats the hazardous secondary material shall repair the defect
the next time the process or unit that is generating the hazardous secondary
material managed in the tank stops operation. Repair of the defect shall be
finished before the process or unit resumes operation.
(l) Following the initial inspection and
monitoring of the cover as required by Sections
R315-261-1080 through
R315-261-1089, subsequent
inspection and monitoring may be performed at intervals longer than 1 year
under the special conditions specified in Subsections
R315-261-1084(l)(1)
and R315-261-1084(l)(2):
(1) If inspecting or monitoring the cover
would expose a worker to dangerous, hazardous, or other unsafe conditions, then
the remanufacturer or other person that stores or treats the hazardous
secondary material may designate a cover as an unsafe to inspect and monitor
cover and comply with the requirements in Subsections
R315-261-1084(l)(1)(i)
and R315-261-1084(l)(1)(ii):
(i) Prepare a written explanation for the
cover stating the reasons why the cover is unsafe to visually inspect or to
monitor, if required.
(ii) Develop
and implement a written plan and schedule to inspect and monitor the cover,
using the procedures specified in the applicable section of Sections
R315-261-1080 through
R315-261-1089, as often as
practicable during those times when a worker can safely access the
cover.
(2) If a tank is
buried partially or entirely underground, a remanufacturer or other person that
stores or treats the hazardous secondary material shall inspect and monitor, as
required by Section R315-261-1084, only those
portions of the tank cover and those connections to the tank, for example, fill
ports, access hatches, and gauge wells, that are located on or above the ground
surface.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.