Utah Admin. Code R315-261-1084 - Air Emission Standards for Tanks and Containers - Standards: Tanks
(a) The provisions of Section R315-261-1084
apply to the control of air pollutant emissions from tanks for which Subsection
R315-261-1082(b)
references the use of Section R315-261-1084 for such air emission
control.
(b) The remanufacturer or
other person that stores or treats the hazardous secondary material shall
control air pollutant emissions from each tank subject to Section R315-261-1084
in accordance with the following requirements as applicable:
(1) For a tank that manages hazardous
secondary material that meets all of the conditions specified in Subsections
R315-261-1084(b)(1)(i) through (iii), the remanufacturer or other person that
stores or treats the hazardous secondary material shall control air pollutant
emissions from the tank in accordance with the Tank Level 1 controls specified
in Subsection R315-261-1084(c) or the Tank Level 2 controls specified in
Subsection R315-261-1084(d).
(i) The
hazardous secondary material in the tank has a maximum organic vapor pressure
which is less than the maximum organic vapor pressure limit for the tank's
design capacity category as follows:
(A) For
a tank design capacity equal to or greater than 151 m
3, the maximum organic vapor pressure limit for the
tank is 5.2 kPa.
(B) For a tank
design capacity equal to or greater than 75 m 3 but
less than 151 m 3, the maximum organic vapor
pressure limit for the tank is 27.6 kPa.
(C) For a tank design capacity less than 75 m
3, the maximum organic vapor pressure limit for the
tank is 76.6 kPa.
(ii)
The hazardous secondary material in the tank is not heated by the
remanufacturer or other person that stores or treats the hazardous secondary
material to a temperature that is greater than the temperature at which the
maximum organic vapor pressure of the hazardous secondary material is
determined for the purpose of complying with Subsection R315-261-1084(b)(1)(i).
(2) For a tank that
manages hazardous secondary material that does not meet all of the conditions
specified in Subsections R315-261-1084(b)(1)(i) through (iii), the
remanufacturer or other person that stores or treats the hazardous secondary
material shall control air pollutant emissions from the tank by using Tank
Level 2 controls in accordance with the requirements of Subsection
R315-261-1084(d). An example of tanks required to use Tank Level 2 controls is
a tank for which the hazardous secondary material in the tank has a maximum
organic vapor pressure that is equal to or greater than the maximum organic
vapor pressure limit for the tank's design capacity category as specified in
Subsection R315-261-1084(b)(1)(i).
(c) Remanufacturers or other persons that
store or treats the hazardous secondary material controlling air pollutant
emissions from a tank using Tank Level 1 controls shall meet the requirements
specified in Subsection R315-261-1084(c)(1) through (4):
(1) The remanufacturer or other person that
stores or treats that hazardous secondary material shall determine the maximum
organic vapor pressure for a hazardous secondary material to be managed in the
tank using Tank Level 1 controls before the first time the hazardous secondary
material is placed in the tank. The maximum organic vapor pressure shall be
determined using the procedures specified in Subsection
R315-261-1083(c).
Thereafter, the remanufacturer or other person that stores or treats the
hazardous secondary material shall perform a new determination whenever changes
to the hazardous secondary material managed in the tank could potentially cause
the maximum organic vapor pressure to increase to a level that is equal to or
greater than the maximum organic vapor pressure limit for the tank design
capacity category specified in Subsection R315-261-1084(b)(1)(i), as applicable
to the tank.
(2) The tank shall be
equipped with a fixed roof designed to meet the following specifications:
(i) The fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the hazardous secondary material in the tank. The fixed roof may be a separate
cover installed on the tank, e.g., a removable cover mounted on an open-top
tank, or may be an integral part of the tank structural design, e.g., a
horizontal cylindrical tank equipped with a hatch.
(ii) The fixed roof shall be installed in a
manner such that there are no visible cracks, holes, gaps, or other open spaces
between roof section joints or between the interface of the roof edge and the
tank wall.
(iii) Each opening in
the fixed roof, and any manifold system associated with the fixed roof, shall
be either:
(A) Equipped with a closure device
designed to operate such that when the closure device is secured in the closed
position there are no visible cracks, holes, gaps, or other open spaces in the
closure device or between the perimeter of the opening and the closure device;
or
(B) Connected by a closed-vent
system that is vented to a control device. The control device shall remove or
destroy organics in the vent stream, and shall be operating whenever hazardous
secondary material is managed in the tank, except as provided for in Subsection
R315-261-1084(c)(2)(iii)(B)(I) and (II).
(I)
During periods when it is necessary to provide access to the tank for
performing the activities of Subsection R315-261-1084(c)(2)(iii)(B)(2), venting
of the vapor headspace underneath the fixed roof to the control device is not
required, opening of closure devices is allowed, and removal of the fixed roof
is allowed. Following completion of the activity , the remanufacturer or other
person that stores or treats the hazardous secondary material shall promptly
secure the closure device in the closed position or reinstall the cover, as
applicable, and resume operation of the control device.
(II) During periods of routine inspection ,
maintenance, or other activities needed for normal operations, and for removal
of accumulated sludge or other residues from the bottom of the tank.
(iv) The fixed roof and
its closure devices shall be made of suitable materials that will minimize
exposure of the hazardous secondary material to the atmosphere, to the extent
practical, and will maintain the integrity of the fixed roof and closure
devices throughout their intended service life. Factors to be considered when
selecting the materials for and designing the fixed roof and closure devices
shall include: organic vapor permeability, the effects of any contact with the
hazardous secondary material or its vapors managed in the tank; the effects of
outdoor exposure to wind, moisture, and sunlight; and the operating practices
used for the tank on which the fixed roof is installed.
(3) Whenever a hazardous secondary material
is in the tank, the fixed roof shall be installed with each closure device
secured in the closed position except as follows:
(i) Opening of closure devices or removal of
the fixed roof is allowed at the following times:
(A) To provide access to the tank for
performing routine inspection , maintenance, or other activities needed for
normal operations. Examples of such activities include those times when a
worker needs to open a port to sample the liquid in the tank, or when a worker
needs to open a hatch to maintain or repair equipment. Following completion of
the activity , the remanufacturer or other person that stores or treats the
hazardous secondary material shall promptly secure the closure device in the
closed position or reinstall the cover, as applicable, to the tank.
(B) To remove accumulated sludge or other
residues from the bottom of tank.
(ii) Opening of a spring-loaded
pressure-vacuum relief valve, conservation vent, or similar type of pressure
relief device which vents to the atmosphere is allowed during normal operations
for the purpose of maintaining the tank internal pressure in accordance with
the tank design specifications. The device shall be designed to operate with no
detectable organic emissions when the device is secured in the closed position.
The settings at which the device opens shall be established such that the
device remains in the closed position whenever the tank internal pressure is
within the internal pressure operating range determined by the remanufacturer
or other person that stores or treats the hazardous secondary material based on
the tank manufacturer recommendations, applicable regulations, fire protection
and prevention codes, standard engineering codes and practices, or other
requirements for the safe handling of flammable, ignitable, explosive,
reactive, or hazardous materials . Examples of normal operating conditions that
may require these devices to open are during those times when the tank internal
pressure exceeds the internal pressure operating range for the tank as a result
of loading operations or diurnal ambient temperature fluctuations.
(iii) Opening of a safety device, as defined
in Section
R315-261-1081,
is allowed at any time conditions require doing so to avoid an unsafe
condition.
(4) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall inspect the air emission control equipment in accordance with
the following requirements.
(i) The fixed
roof and its closure devices shall be visually inspected by the remanufacturer
or other person that stores or treats the hazardous secondary material to check
for defects that could result in air pollutant emissions. Defects include, but
are not limited to, visible cracks, holes, or gaps in the roof sections or
between the roof and the tank wall; broken, cracked, or otherwise damaged seals
or gaskets on closure devices; and broken or missing hatches, access covers,
caps, or other closure devices.
(ii) The remanufacturer or other person that
stores or treats the hazardous secondary material shall perform an initial
inspection of the fixed roof and its closure devices on or before the date that
the tank becomes subject to Section R315-261-1084. Thereafter, the
remanufacturer or other person that stores or treats the hazardous secondary
material shall perform the inspections at least once every year except under
the special conditions provided for in Subsection R315-261-1084(l).
(iii) In the event that a defect is detected,
the remanufacturer or other person that stores or treats the hazardous
secondary material shall repair the defect in accordance with the requirements
of Subsection R315-261-1084(k).
(iv) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(d) Remanufacturers or other persons that
store or treat the hazardous secondary material controlling air pollutant
emissions from a tank using Tank Level 2 controls shall use one of the
following tanks:
(1) A fixed-roof tank
equipped with an internal floating roof in accordance with the requirements
specified in Subsection R315-261-1084(e);
(2) A tank equipped with an external floating
roof in accordance with the requirements specified in Subsection
R315-261-1084(f);
(3) A tank vented
through a closed-vent system to a control device in accordance with the
requirements specified in Subsection R315-261-1084(g);
(4) A pressure tank designed and operated in
accordance with the requirements specified in Subsection R315-261-1084(h); or
(5) A tank located inside an
enclosure that is vented through a closed-vent system to an enclosed combustion
control device in accordance with the requirements specified in Subsection
R315-261-1084(i).
(e) The
remanufacturer or other person that stores or treats the hazardous secondary
material who controls air pollutant emissions from a tank using a fixed roof
with an internal floating roof shall meet the requirements specified in
Subsections R315-261-1084(e)(1) through (3).
(1) The tank shall be equipped with a fixed
roof and an internal floating roof in accordance with the following
requirements:
(i) The internal floating roof
shall be designed to float on the liquid surface except when the floating roof
shall be supported by the leg supports.
(ii) The internal floating roof shall be
equipped with a continuous seal between the wall of the tank and the floating
roof edge that meets either of the following requirements:
(A) A single continuous seal that is either a
liquid-mounted seal or a metallic shoe seal, as defined in Section
R315-261-1081;
or
(B) Two continuous seals mounted
one above the other. The lower seal may be a vapor-mounted
seal.
(iii) The internal
floating roof shall meet the following specifications:
(A) Each opening in a noncontact internal
floating roof except for automatic bleeder vents, vacuum breaker vents, and the
rim space vents is to provide a projection below the liquid surface.
(B) Each opening in the internal floating
roof shall be equipped with a gasketed cover or a gasketed lid except for leg
sleeves, automatic bleeder vents, rim space vents, column wells, ladder wells,
sample wells, and stub drains.
(C)
Each penetration of the internal floating roof for the purpose of sampling
shall have a slit fabric cover that covers at least 90 percent of the
opening.
(D) Each automatic bleeder
vent and rim space vent shall be gasketed.
(E) Each penetration of the internal floating
roof that allows for passage of a ladder shall have a gasketed sliding
cover.
(F) Each penetration of the
internal floating roof that allows for passage of a column supporting the fixed
roof shall have a flexible fabric sleeve seal or a gasketed sliding
cover.
(2) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall operate the tank in accordance with the following requirements:
(i) When the floating roof is resting on the
leg supports, the process of filling, emptying, or refilling shall be
continuous and shall be completed as soon as practical.
(ii) Automatic bleeder vents are to be set
closed at all times when the roof is floating, except when the roof is being
floated off or is being landed on the leg supports.
(iii) Prior to filling the tank, each cover,
access hatch, gauge float well or lid on any opening in the internal floating
roof shall be bolted or fastened closed, i.e., no visible gaps. Rim space vents
are to be set to open only when the internal floating roof is not floating or
when the pressure beneath the rim exceeds the manufacturer's recommended
setting.
(3) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall inspect the internal floating roof in accordance with the
procedures specified as follows:
(i) The
floating roof and its closure devices shall be visually inspected by the
remanufacture or other person that stores or treats the hazardous secondary
material to check for defects that could result in air pollutant emissions.
Defects include, but are not limited to: The internal floating roof is not
floating on the surface of the liquid inside the tank; liquid has accumulated
on top of the internal floating roof; any portion of the roof seals have
detached from the roof rim; holes, tears, or other openings are visible in the
seal fabric; the gaskets no longer close off the hazardous secondary material
surface from the atmosphere; or the slotted membrane has more than 10 percent
open area.
(ii) The remanufacturer
or other person that stores or treats the hazardous secondary material shall
inspect the internal floating roof components as follows except as provided in
Subsection R315-261-1084(e)(3)(iii):
(A)
Visually inspect the internal floating roof components through openings on the
fixed-roof, e.g., manholes and roof hatches, at least once every 12 months
after initial fill, and
(B)
Visually inspect the internal floating roof, primary seal, secondary seal, if
one is in service, gaskets, slotted membranes, and sleeve seals, if any, each
time the tank is emptied and degassed and at least every 10 years.
(iii) As an alternative to
performing the inspections specified in Subsection R315-261-1084(e)(3)(ii) for
an internal floating roof equipped with two continuous seals mounted one above
the other, the remanufacturer or other person that stores or treats the
hazardous secondary material may visually inspect the internal floating roof,
primary and secondary seals, gaskets, slotted membranes, and sleeve seals, if
any, each time the tank is emptied and degassed and at least every five years.
(iv) Prior to each inspection
required by Subsection R315-261-1084(e)(3)(ii) or (iii), the remanufacturer or
other person that stores or treats the hazardous secondary material shall
notify the Director in advance of each inspection to provide the Director with
the opportunity to have an observer present during the inspection . The
remanufacturer or other person that stores or treats the hazardous secondary
material shall notify the Director of the date and location of the inspection
as follows:
(A) Prior to each visual
inspection of an internal floating roof in a tank that has been emptied and
degassed, written notification shall be prepared and sent by the remanufacturer
or other person that stores or treats the hazardous secondary material so that
it is received by the Director at least 30 calendar days before refilling the
tank except when an inspection is not planned as provided for in Subsection
R315-261-1084(e)(3)(iv)(B).
(B)
When a visual inspection is not planned and the remanufacturer or other person
that stores or treats the hazardous secondary material could not have known
about the inspection 30 calendar days before refilling the tank, the
remanufacturer or other person that stores or treats the hazardous secondary
material shall notify the Director as soon as possible, but no later than seven
calendar days before refilling of the tank. This notification may be made by
telephone and immediately followed by a written explanation for why the
inspection is unplanned. Alternatively, written notification, including the
explanation for the unplanned inspection , may be sent so that it is received by
the Director at least seven calendar days before refilling the tank.
(v) In the event that a defect is
detected, the remanufacturer or other person that stores or treats the
hazardous secondary material shall repair the defect in accordance with the
requirements of Subsection R315-261-1084(k).
(vi) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(4) Safety devices, as defined in Section
R315-261-1081,
may be installed and operated as necessary on any tank complying with the
requirements of Subsection R315-261-1084(e).
(f) The remanufacturer or other person that
stores or treats the hazardous secondary material who controls air pollutant
emissions from a tank using an external floating roof shall meet the
requirements specified in Subsections R315-261-1084(f)(1) through (3).
(1) The remanufacturer or other person that
stores or treats the hazardous secondary material shall design the external
floating roof in accordance with the following requirements:
(i) The external floating roof shall be
designed to float on the liquid surface except when the floating roof shall be
supported by the leg supports.
(ii)
The floating roof shall be equipped with two continuous seals, one above the
other, between the wall of the tank and the roof edge. The lower seal is
referred to as the primary seal, and the upper seal is referred to as the
secondary seal.
(A) The primary seal shall be
a liquid-mounted seal or a metallic shoe seal, as defined in
40
CFR 261.1081. The total area of the gaps
between the tank wall and the primary seal shall not exceed 212 square
centimeters per meter of tank diameter, and the width of any portion of these
gaps shall not exceed 3.8 centimeters. If a metallic shoe seal is used for the
primary seal, the metallic shoe seal shall be designed so that one end extends
into the liquid in the tank and the other end extends a vertical distance of at
least 61 centimeters above the liquid surface.
(B) The secondary seal shall be mounted above
the primary seal and cover the annular space between the floating roof and the
wall of the tank. The total area of the gaps between the tank wall and the
secondary seal shall not exceed 21.2 square centimeters per meter of tank
diameter, and the width of any portion of these gaps shall not exceed 1.3
centimeters.
(iii) The
external floating roof shall meet the following specifications:
(A) Except for automatic bleeder vents,
vacuum breaker vents, and rim space vents, each opening in a noncontact
external floating roof shall provide a projection below the liquid surface.
(B) Except for automatic bleeder
vents, rim space vents, roof drains, and leg sleeves, each opening in the roof
shall be equipped with a gasketed cover, seal, or lid.
(C) Each access hatch and each gauge float
well shall be equipped with a cover designed to be bolted or fastened when the
cover is secured in the closed position.
(D) Each automatic bleeder vent and each rim
space vent shall be equipped with a gasket.
(E) Each roof drain that empties into the
liquid managed in the tank shall be equipped with a slotted membrane fabric
cover that covers at least 90 percent of the area of the opening.
(F) Each unslotted and slotted guide pole
well shall be equipped with a gasketed sliding cover or a flexible fabric
sleeve seal.
(G) Each unslotted
guide pole shall be equipped with a gasketed cap on the end of the pole.
(H) Each slotted guide pole shall
be equipped with a gasketed float or other device which closes off the liquid
surface from the atmosphere.
(I)
Each gauge hatch and each sample well shall be equipped with a gasketed cover.
(2) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall operate the tank in accordance with the following requirements:
(i) When the floating roof is resting on the
leg supports, the process of filling, emptying, or refilling shall be
continuous and shall be completed as soon as practical.
(ii) Except for automatic bleeder vents, rim
space vents, roof drains, and leg sleeves, each opening in the roof shall be
secured and maintained in a closed position at all times except when the
closure device shall be open for access.
(iii) Covers on each access hatch and each
gauge float well shall be bolted or fastened when secured in the closed
position.
(iv) Automatic bleeder
vents shall be set closed at all times when the roof is floating, except when
the roof is being floated off or is being landed on the leg supports.
(v) Rim space vents shall be set
to open only at those times that the roof is being floated off the roof leg
supports or when the pressure beneath the rim seal exceeds the manufacturer's
recommended setting.
(vi) The cap
on the end of each unslotted guide pole shall be secured in the closed position
at all times except when measuring the level or collecting samples of the
liquid in the tank.
(vii) The cover
on each gauge hatch or sample well shall be secured in the closed position at
all times except when the hatch or well shall be opened for access.
(viii) Both the primary seal and the
secondary seal shall completely cover the annular space between the external
floating roof and the wall of the tank in a continuous fashion except during
inspections.
(3) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall inspect the external floating roof in accordance with the
procedures specified as follows:
(i) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall measure the external floating roof seal gaps in accordance with
the following requirements:
(A) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall perform measurements of gaps between the tank wall and the
primary seal within 60 calendar days after initial operation of the tank
following installation of the floating roof and, thereafter, at least once
every 5 years.
(B) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall perform measurements of gaps between the tank wall and the
secondary seal within 60 calendar days after initial operation of the tank
following installation of the floating roof and, thereafter, at least once
every year .
(C) If a tank ceases to
hold hazardous secondary material for a period of 1 year or more, subsequent
introduction of hazardous secondary material into the tank shall be considered
an initial operation for the purposes of Subsections R315-261-1084(f)(3)(i)(A)
and (B).
(D) The remanufacturer or
other person that stores or treats the hazardous secondary material shall
determine the total surface area of gaps in the primary seal and in the
secondary seal individually using the following procedure:
(I) The seal gap measurements shall be
performed at one or more floating roof levels when the roof is floating off the
roof supports.
(II) Seal gaps, if
any, shall be measured around the entire perimeter of the floating roof in each
place where a 0.32-centimeter diameter uniform probe passes freely, without
forcing or binding against the seal, between the seal and the wall of the tank
and measure the circumferential distance of each such location.
(III) For a seal gap measured under
Subsection R315-261-1084(f)(3), the gap surface area shall be determined by
using probes of various widths to measure accurately the actual distance from
the tank wall to the seal and multiplying each such width by its respective
circumferential distance.
(IV) The
total gap area shall be calculated by adding the gap surface areas determined
for each identified gap location for the primary seal and the secondary seal
individually, and then dividing the sum for each seal type by the nominal
diameter of the tank. These total gap areas for the primary seal and secondary
seal are then compared to the respective standards for the seal type as
specified in Subsection R315-261-1084(f)(1)(ii).
(E) In the event that the seal gap
measurements do not conform to the specifications in Subsection
R315-261-1084(f)(1)(ii), the remanufacturer or other person that stores or
treats the hazardous secondary material shall repair the defect in accordance
with the requirements of Subsection R315-261-1084(k).
(F) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(ii) The remanufacturer or other person that
stores or treats the hazardous secondary material shall visually inspect the
external floating roof in accordance with the following requirements:
(A) The floating roof and its closure devices
shall be visually inspected by the remanufacturer or other person that stores
or treats the hazardous secondary material to check for defects that could
result in air pollutant emissions. Defects include, but are not limited to:
Holes, tears, or other openings in the rim seal or seal fabric of the floating
roof; a rim seal detached from the floating roof; all or a portion of the
floating roof deck being submerged below the surface of the liquid in the tank;
broken, cracked, or otherwise damaged seals or gaskets on closure devices; and
broken or missing hatches, access covers, caps, or other closure devices.
(B) The remanufacturer or other
person that stores or treats the hazardous secondary material shall perform an
initial inspection of the external floating roof and its closure devices on or
before the date that the tank becomes subject to Section R315-261-1084.
Thereafter, the remanufacturer or other person that stores or treats the
hazardous secondary material shall perform the inspections at least once every
year except for the special conditions provided for in Subsection
R315-261-1084(l).
(C) In the event
that a defect is detected, the remanufacturer or other person that stores or
treats the hazardous secondary material shall repair the defect in accordance
with the requirements of Subsection R315-261-1084(k).
(D) The remanufacturer or other person that
stores or treats the hazardous secondary material shall maintain a record of
the inspection in accordance with the requirements specified in Subsection
R315-261-1089(b).
(iii) Prior to each inspection required by
Subsection R315-261-1084(f)(3)(i) or (ii), the remanufacturer or other person
that stores or treats the hazardous secondary material shall notify the
Director in advance of each inspection to provide the Director with the
opportunity to have an observer present during the inspection . The
remanufacturer or other person that stores or treats the hazardous secondary
material shall notify the Director of the date and location of the inspection
as follows:
(A) Prior to each inspection to
measure external floating roof seal gaps as required under Subsection
R315-261-1084(f)(3)(i), written notification shall be prepared and sent by the
remanufacturer or other person that stores or treats the hazardous secondary
material so that it is received by the Director at least 30 calendar days
before the date the measurements are scheduled to be performed.
(B) Prior to each visual inspection of an
external floating roof in a tank that has been emptied and degassed, written
notification shall be prepared and sent by the remanufacturer or other person
that stores or treats the hazardous secondary material so that it is received
by the Director at least 30 calendar days before refilling the tank except when
an inspection is not planned as provided for in Subsection
R315-261-1084(f)(3)(iii)(C).
(C)
When a visual inspection is not planned and the remanufacturer or other person
that stores or treats the hazardous secondary material could not have known
about the inspection 30 calendar days before refilling the tank, the owner or
operator shall notify the Director as soon as possible, but no later than seven
calendar days before refilling of the tank. This notification may be made by
telephone and immediately followed by a written explanation for why the
inspection is unplanned. Alternatively, written notification, including the
explanation for the unplanned inspection , may be sent so that it is received by
the Director at least seven calendar days before refilling the tank.
(4) Safety devices, as
defined in Section
R315-261-1081,
may be installed and operated as necessary on any tank complying with the
requirements of Subsection R315-261-1084(f).
(g) The remanufacturer or other person that
stores or treats the hazardous secondary material who controls air pollutant
emissions from a tank by venting the tank to a control device shall meet the
requirements specified in Subsections R315-261-1084(g)(1) through (3).
(1) The tank shall be covered by a fixed roof
and vented directly through a closed-vent system to a control device in
accordance with the following requirements:
(i) The fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the liquid in the tank.
(ii) Each
opening in the fixed roof not vented to the control device shall be equipped
with a closure device. If the pressure in the vapor headspace underneath the
fixed roof is less than atmospheric pressure when the control device is
operating, the closure devices shall be designed to operate such that when the
closure device is secured in the closed position there are no visible cracks,
holes, gaps, or other open spaces in the closure device or between the
perimeter of the cover opening and the closure device. If the pressure in the
vapor headspace underneath the fixed roof is equal to or greater than
atmospheric pressure when the control device is operating, the closure device
shall be designed to operate with no detectable organic emissions.
(iii) The fixed roof and its closure devices
shall be made of suitable materials that will minimize exposure of the
hazardous secondary material to the atmosphere, to the extent practical, and
will maintain the integrity of the fixed roof and closure devices throughout
their intended service life. Factors to be considered when selecting the
materials for and designing the fixed roof and closure devices shall include:
Organic vapor permeability, the effects of any contact with the liquid and its
vapor managed in the tank; the effects of outdoor exposure to wind, moisture,
and sunlight; and the operating practices used for the tank on which the fixed
roof is installed.
(iv) The
closed-vent system and control device shall be designed and operated in
accordance with the requirements of Section
R315-261-1087.
(2) Whenever a hazardous secondary
material is in the tank, the fixed roof shall be installed with each closure
device secured in the closed position and the vapor headspace underneath the
fixed roof vented to the control device except as follows:
(i) Venting to the control device is not
required, and opening of closure devices or removal of the fixed roof is
allowed at the following times:
(A) To
provide access to the tank for performing routine inspection , maintenance, or
other activities needed for normal operations. Examples of such activities
include those times when a worker needs to open a port to sample liquid in the
tank, or when a worker needs to open a hatch to maintain or repair equipment.
Following completion of the activity , the remanufacturer or other person that
stores or treats the hazardous secondary material shall promptly secure the
closure device in the closed position or reinstall the cover, as applicable, to
the tank.
(B) To remove accumulated
sludge or other residues from the bottom of a tank.
(ii) Opening of a safety device, as defined
in Section
R315-261-1081,
is allowed at any time conditions require doing so to avoid an unsafe
condition.
(3) The
remanufacturer or other person that stores or treats the hazardous secondary
material shall inspect and monitor the air emission control equipment in
accordance with the following procedures:
(i)
The fixed roof and its closure devices shall be visually inspected by the
remanufacturer or other person that stores or treats the hazardous secondary
material to check for defects that could result in air pollutant emissions.
Defects include, but are not limited to, visible cracks, holes, or gaps in the
roof sections or between the roof and the tank wall; broken, cracked, or
otherwise damaged seals or gaskets on closure devices; and broken or missing
hatches, access covers, caps, or other closure devices.
(ii) The closed-vent system and control
device shall be inspected and monitored by the remanufacturer or other person
that stores or treats the hazardous secondary material in accordance with the
procedures specified in Section
R315-261-1087.
(iii) The remanufacturer or other
person that stores or treats the hazardous secondary material shall perform an
initial inspection of the air emission control equipment on or before the date
that the tank becomes subject to Section R315-261-1084. Thereafter, the
remanufacturer or other person that stores or treats the hazardous secondary
material shall perform the inspections at least once every year except for the
special conditions provided for in Subsection R315-261-1084(l).
(iv) In the event that a defect is detected,
the remanufacture or other person that stores or treats the hazardous secondary
material shall repair the defect in accordance with the requirements of
Subsection R315-261-1084(k).
(v)
The remanufacturer or other person that stores or treats the hazardous
secondary material shall maintain a record of the inspection in accordance with
the requirements specified in Subsection
R315-261-1089(b).
(h) The remanufacturer
or other person that stores or treats the hazardous secondary material who
controls air pollutant emissions by using a pressure tank shall meet the
following requirements.
(1) The tank shall be
designed not to vent to the atmosphere as a result of compression of the vapor
headspace in the tank during filling of the tank to its design capacity.
(2) All tank openings shall be
equipped with closure devices designed to operate with no detectable organic
emissions as determined using the procedure specified in Subsection
R315-261-1083(d).
(3) Whenever a hazardous secondary material
is in the tank, the tank shall be operated as a closed system that does not
vent to the atmosphere except under either or the following conditions as
specified in Subsection R315-261-1084(h)(3)(i) or (h)(3)(ii).
(i) At those times when opening of a safety
device, as defined in Section
R315-261-1081,
is required to avoid an unsafe condition.
(ii) At those times when purging of inerts
from the tank is required and the purge stream is routed to a closed-vent
system and control device designed and operated in accordance with the
requirements of Section
R315-261-1087.
(i) The remanufacturer
or other person that stores or treats the hazardous secondary material who
controls air pollutant emissions by using an enclosure vented through a
closed-vent system to an enclosed combustion control device shall meet the
requirements specified in Subsections R315-261-1084(i)(1) through (4).
(1) The tank shall be located inside an
enclosure. The enclosure shall be designed and operated in accordance with the
criteria for a permanent total enclosure as specified in "Procedure T -
Criteria for and Verification of a Permanent or Temporary Total Enclosure"
under
40
CFR 52.741, appendix B. The enclosure may
have permanent or temporary openings to allow worker access; passage of
material into or out of the enclosure by conveyor, vehicles, or other
mechanical means; entry of permanent mechanical or electrical equipment; or
direct airflow into the enclosure. The remanufacturer or other person that
stores or treats the hazardous secondary material shall perform the
verification procedure for the enclosure as specified in Section 5.0 to
"Procedure T - Criteria for and Verification of a Permanent or Temporary Total
Enclosure" initially when the enclosure is first installed and, thereafter,
annually.
(2) The enclosure shall
be vented through a closed-vent system to an enclosed combustion control device
that is designed and operated in accordance with the standards for either a
vapor incinerator, boiler, or process heater specified in Section
R315-261-1087.
(3) Safety devices, as defined in Section
R315-261-1081,
may be installed and operated as necessary on any enclosure, closed-vent
system, or control device used to comply with the requirements of Subsections
R315-261-1084(i)(1) and (2).
(4)
The remanufacturer or other person that stores or treats the hazardous
secondary material shall inspect and monitor the closed-vent system and control
device as specified in Section
R315-261-1087.
(j) The remanufacturer
or other person that stores or treats the hazardous secondary material shall
transfer hazardous secondary material to a tank subject to Section
R315-261-1084 in accordance with the following requirements:
(1) Transfer of hazardous secondary material,
except as provided in Subsection R315-261-1084(j)(2), to the tank from another
tank subject to Section R315-261-1084 shall be conducted using continuous
hard-piping or another closed system that does not allow exposure of the
hazardous secondary material to the atmosphere. For the purpose of complying
with this provision, an individual drain system is considered to be a closed
system when it meets the requirements of 40 CFR part 63, subpart RR - National
Emission Standards for Individual Drain Systems.
(2) The requirements of Subsection
R315-261-1084(j)(1) do not apply when transferring a hazardous secondary
material to the tank under any of the following conditions:
(i) The hazardous secondary material meets
the average VO concentration conditions specified in Subsection
R315-261-1082(c)(1)
at the point of material origination.
(ii) The hazardous secondary material has
been treated by an organic destruction or removal process to meet the
requirements in Subsection
R315-261-1082(c)(2).
(iii) The hazardous secondary material meets
the requirements of Subsection
R315-261-1082(c)(4).
(k) The remanufacturer or other
person that stores or treats the hazardous secondary material shall repair each
defect detected during an inspection performed in accordance with the
requirements of Subsection R315-261-1084(c)(4), (e)(3), (f)(3), or (g)(3) as
follows:
(1) The remanufacturer or other
person that stores or treats the hazardous secondary material shall make first
efforts at repair of the defect no later than 5 calendar days after detection,
and repair shall be completed as soon as possible but no later than 45 calendar
days after detection except as provided in Subsection R315-261-1084(k)(2).
(2) Repair of a defect may be
delayed beyond 45 calendar days if the remanufacturer or other person that
stores or treats the hazardous secondary material determines that repair of the
defect requires emptying or temporary removal from service of the tank and no
alternative tank capacity is available at the site to accept the hazardous
secondary material normally managed in the tank. In this case, the
remanufacturer or other person that stores or treats the hazardous secondary
material shall repair the defect the next time the process or unit that is
generating the hazardous secondary material managed in the tank stops
operation. Repair of the defect shall be completed before the process or unit
resumes operation.
(l)
Following the initial inspection and monitoring of the cover as required by the
applicable provisions of Sections
R315-261-1080
through 1089, subsequent inspection and monitoring may be performed at
intervals longer than 1 year under the following special conditions:
(1) In the case when inspecting or monitoring
the cover would expose a worker to dangerous, hazardous, or other unsafe
conditions, then the remanufacturer or other person that stores or treats the
hazardous secondary material may designate a cover as an "unsafe to inspect and
monitor cover" and comply with all of the following requirements:
(i) Prepare a written explanation for the
cover stating the reasons why the cover is unsafe to visually inspect or to
monitor, if required.
(ii) Develop
and implement a written plan and schedule to inspect and monitor the cover,
using the procedures specified in the applicable section of Sections
R315-261-1080
through 1089, as frequently as practicable during those times when a worker can
safely access the cover.
(2) In the case when a tank is buried
partially or entirely underground, a remanufacturer or other person that stores
or treats the hazardous secondary material is required to inspect and monitor,
as required by the applicable provisions of Section R315-261-1084, only those
portions of the tank cover and those connections to the tank, e.g., fill ports,
access hatches, gauge wells, etc., that are located on or above the ground
surface.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.