Utah Admin. Code R315-264-1084 - Standards: Tanks
(a) The provisions
of Section R315-264-1084 apply to the control of air pollutant emissions from
tanks for which Subsection
R315-264-1082(b)
references the use of Section R315-264-1084 for such air emission control.
(b) The owner or operator shall
control air pollutant emissions from each tank subject to Section R315-264-1084
in accordance with the following requirements as applicable:
(1) For a tank that manages hazardous waste
that meets all of the conditions specified in Subsections
R315-264-1084(b)(1)(i) through (b)(1)(iii), the owner or operator shall control
air pollutant emissions from the tank in accordance with the Tank Level 1
controls specified in Subsection R315-264-1084(c) or the Tank Level 2 controls
specified in Subsection R315-264-1084(d).
(i)
The hazardous waste in the tank has a maximum organic vapor pressure which is
less than the maximum organic vapor pressure limit for the tank's design
capacity category as follows:
(A) For a tank
design capacity equal to or greater than 151 cubic meters, the maximum organic
vapor pressure limit for the tank is 5.2 kPa.
(B) For a tank design capacity equal to or
greater than 75 cubic meters but less than 151 cubic meters, the maximum
organic vapor pressure limit for the tank is 27.6 kPa.
(C) For a tank design capacity less than 75
cubic meters, the maximum organic vapor pressure limit for the tank is 76.6
kPa.
(ii) The hazardous
waste in the tank is not heated by the owner or operator to a temperature that
is greater than the temperature at which the maximum organic vapor pressure of
the hazardous waste is determined for the purpose of complying with Subsection
R315-264-1084(b)(1)(i).
(iii) The
hazardous waste in the tank is not treated by the owner or operator using a
waste stabilization process, as defined in
40 CFR
265.1081, which is adopted by reference.
(2) For a tank that
manages hazardous waste that does not meet all of the conditions specified in
Subsections R315-264-1084(b)(1)(i) through (b)(1)(iii), the owner or operator
shall control air pollutant emissions from the tank by using Tank Level 2
controls in accordance with the requirements of Subsection R315-264-1084(d).
Examples of tanks required to use Tank Level 2 controls include: A tank used
for a waste stabilization process; and a tank for which the hazardous waste in
the tank has a maximum organic vapor pressure that is equal to or greater than
the maximum organic vapor pressure limit for the tank's design capacity
category as specified in Subsection R315-264-1084(b)(1)(i).
(c) Owners and operators
controlling air pollutant emissions from a tank using Tank Level 1 controls
shall meet the requirements specified in Subsections R315-264-1084(c)(1)
through (c)(4):
(1) The owner or operator
shall determine the maximum organic vapor pressure for a hazardous waste to be
managed in the tank using Tank Level 1 controls before the first time the
hazardous waste is placed in the tank. The maximum organic vapor pressure shall
be determined using the procedures specified in Subsection
R315-264-1083(c).
Thereafter, the owner or operator shall perform a new determination whenever
changes to the hazardous waste managed in the tank could potentially cause the
maximum organic vapor pressure to increase to a level that is equal to or
greater than the maximum organic vapor pressure limit for the tank design
capacity category specified in Subsection R315-264-1084(b)(1)(i), as applicable
to the tank.
(2) The tank shall be
equipped with a fixed roof designed to meet the following specifications:
(i) The fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the hazardous waste in the tank. The fixed roof may be a separate cover
installed on the tank, e.g., a removable cover mounted on an open-top tank, or
may be an integral part of the tank structural design, e.g., a horizontal
cylindrical tank equipped with a hatch.
(ii) The fixed roof shall be installed in a
manner such that there are no visible cracks, holes, gaps, or other open spaces
between roof section joints or between the interface of the roof edge and the
tank wall.
(iii) Each opening in
the fixed roof, and any manifold system associated with the fixed roof, shall
be either:
(A) Equipped with a closure device
designed to operate such that when the closure device is secured in the closed
position there are no visible cracks, holes, gaps, or other open spaces in the
closure device or between the perimeter of the opening and the closure device;
or
(B) Connected by a closed-vent
system that is vented to a control device. The control device shall remove or
destroy organics in the vent stream, and shall be operating whenever hazardous
waste is managed in the tank, except as provided for in Subsection
R315-264-1084(c)(2)(iii)(B)(I) and (II).
(I)
During periods when it is necessary to provide access to the tank for
performing the activities of Subsection R315-264-1084(c)(2)(iii)(B)(II),
venting of the vapor headspace underneath the fixed roof to the control device
is not required, opening of closure devices is allowed, and removal of the
fixed roof is allowed. Following completion of the activity, the owner or
operator shall promptly secure the closure device in the closed position or
reinstall the cover, as applicable, and resume operation of the control device.
(II) During periods of routine
inspection, maintenance, or other activities needed for normal operations, and
for removal of accumulated sludge or other residues from the bottom of the
tank.
(iv)
The fixed roof and its closure devices shall be made of suitable materials that
will minimize exposure of the hazardous waste to the atmosphere, to the extent
practical, and will maintain the integrity of the fixed roof and closure
devices throughout their intended service life. Factors to be considered when
selecting the materials for and designing the fixed roof and closure devices
shall include: Organic vapor permeability, the effects of any contact with the
hazardous waste or its vapors managed in the tank; the effects of outdoor
exposure to wind, moisture, and sunlight; and the operating practices used for
the tank on which the fixed roof is installed.
(3) Whenever a hazardous waste is in the
tank, the fixed roof shall be installed with each closure device secured in the
closed position except as follows:
(i)
Opening of closure devices or removal of the fixed roof is allowed at the
following times:
(A) To provide access to the
tank for performing routine inspection, maintenance, or other activities needed
for normal operations. Examples of such activities include those times when a
worker needs to open a port to sample the liquid in the tank, or when a worker
needs to open a hatch to maintain or repair equipment. Following completion of
the activity, the owner or operator shall promptly secure the closure device in
the closed position or reinstall the cover, as applicable, to the tank.
(B) To remove accumulated sludge
or other residues from the bottom of tank.
(ii) Opening of a spring-loaded
pressure-vacuum relief valve, conservation vent, or similar type of pressure
relief device which vents to the atmosphere is allowed during normal operations
for the purpose of maintaining the tank internal pressure in accordance with
the tank design specifications. The device shall be designed to operate with no
detectable organic emissions when the device is secured in the closed position.
The settings at which the device opens shall be established such that the
device remains in the closed position whenever the tank internal pressure is
within the internal pressure operating range determined by the owner or
operator based on the tank manufacturer recommendations, applicable
regulations, fire protection and prevention codes, standard engineering codes
and practices, or other requirements for the safe handling of flammable,
ignitable, explosive, reactive, or hazardous materials. Examples of normal
operating conditions that may require these devices to open are during those
times when the tank internal pressure exceeds the internal pressure operating
range for the tank as a result of loading operations or diurnal ambient
temperature fluctuations.
(iii)
Opening of a safety device, as defined in
40 CFR
265.1081, which is adopted by reference, is
allowed at any time conditions require doing so to avoid an unsafe condition.
(4) The owner or
operator shall inspect the air emission control equipment in accordance with
the following requirements.
(i) The fixed
roof and its closure devices shall be visually inspected by the owner or
operator to check for defects that could result in air pollutant emissions.
Defects include, but are not limited to, visible cracks, holes, or gaps in the
roof sections or between the roof and the tank wall; broken, cracked, or
otherwise damaged seals or gaskets on closure devices; and broken or missing
hatches, access covers, caps, or other closure devices.
(ii) The owner or operator shall perform an
initial inspection of the fixed roof and its closure devices on or before the
date that the tank becomes subject to Section R315-264-1084. Thereafter, the
owner or operator shall perform the inspections at least once every year except
under the special conditions provided for in Subsection R315-264-1084(l).
(iii) In the event that a defect
is detected, the owner or operator shall repair the defect in accordance with
the requirements of Subsection R315-264-1084(k).
(iv) The owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in
Subsection
R315-264-1089(b).
(d) Owners
and operators controlling air pollutant emissions from a tank using Tank Level
2 controls shall use one of the following tanks:
(1) A fixed-roof tank equipped with an
internal floating roof in accordance with the requirements specified in
Subsection R315-264-1084(e);
(2) A
tank equipped with an external floating roof in accordance with the
requirements specified in Subsection R315-264-1084(f)
(3) A tank vented through a closed-vent
system to a control device in accordance with the requirements specified in
Subsection R315-264-1084(g);
(4) A
pressure tank designed and operated in accordance with the requirements
specified in Subsection R315-264-1084(h); or
(5) A tank located inside an enclosure that
is vented through a closed-vent system to an enclosed combustion control device
in accordance with the requirements specified in Subsection R315-264-1084(i).
(e) The owner or
operator who controls air pollutant emissions from a tank using a fixed roof
with an internal floating roof shall meet the requirements specified in
Subsections R315-264-1084(e)(1) through (e)(3).
(1) The tank shall be equipped with a fixed
roof and an internal floating roof in accordance with the following
requirements:
(i) The internal floating roof
shall be designed to float on the liquid surface except when the floating roof
shall be supported by the leg supports.
(ii) The internal floating roof shall be
equipped with a continuous seal between the wall of the tank and the floating
roof edge that meets either of the following requirements:
(A) A single continuous seal that is either a
liquid-mounted seal or a metallic shoe seal, as defined in
40 CFR
265.1081, which is adopted by reference; or
(B) Two continuous seals mounted
one above the other. The lower seal may be a vapor-mounted seal.
(iii) The internal floating roof
shall meet the following specifications:
(A)
Each opening in a noncontact internal floating roof except for automatic
bleeder vents, vacuum breaker vents, and the rim space vents is to provide a
projection below the liquid surface.
(B) Each opening in the internal floating
roof shall be equipped with a gasketed cover or a gasketed lid except for leg
sleeves, automatic bleeder vents, rim space vents, column wells, ladder wells,
sample wells, and stub drains.
(C)
Each penetration of the internal floating roof for the purpose of sampling
shall have a slit fabric cover that covers at least 90 percent of the opening.
(D) Each automatic bleeder vent
and rim space vent shall be gasketed.
(E) Each penetration of the internal floating
roof that allows for passage of a ladder shall have a gasketed sliding cover.
(F) Each penetration of the
internal floating roof that allows for passage of a column supporting the fixed
roof shall have a flexible fabric sleeve seal or a gasketed sliding cover.
(2) The
owner or operator shall operate the tank in accordance with the following
requirements:
(i) When the floating roof is
resting on the leg supports, the process of filling, emptying, or refilling
shall be continuous and shall be completed as soon as practical.
(ii) Automatic bleeder vents are to be set
closed at all times when the roof is floating, except when the roof is being
floated off or is being landed on the leg supports.
(iii) Prior to filling the tank, each cover,
access hatch, gauge float well or lid on any opening in the internal floating
roof shall be bolted or fastened closed, i.e., no visible gaps. Rim space vents
are to be set to open only when the internal floating roof is not floating or
when the pressure beneath the rim exceeds the manufacturer's recommended
setting.
(3) The owner
or operator shall inspect the internal floating roof in accordance with the
procedures specified as follows:
(i) The
floating roof and its closure devices shall be visually inspected by the owner
or operator to check for defects that could result in air pollutant emissions.
Defects include, but are not limited to: The internal floating roof is not
floating on the surface of the liquid inside the tank; liquid has accumulated
on top of the internal floating roof; any portion of the roof seals have
detached from the roof rim; holes, tears, or other openings are visible in the
seal fabric; the gaskets no longer close off the hazardous waste surface from
the atmosphere; or the slotted membrane has more than 10 percent open area.
(ii) The owner or operator shall
inspect the internal floating roof components as follows except as provided in
Subsection R315-264-1084(e)(3)(iii):
(A)
Visually inspect the internal floating roof components through openings on the
fixed-roof, e.g., manholes and roof hatches, at least once every 12 months
after initial fill, and
(B)
Visually inspect the internal floating roof, primary seal, secondary seal, if
one is in service, gaskets, slotted membranes, and sleeve seals, if any, each
time the tank is emptied and degassed and at least every 10 years.
(iii) As an alternative to
performing the inspections specified in Subsection R315-264-1084(e)(3)(ii) for
an internal floating roof equipped with two continuous seals mounted one above
the other, the owner or operator may visually inspect the internal floating
roof, primary and secondary seals, gaskets, slotted membranes, and sleeve
seals, if any, each time the tank is emptied and degassed and at least every 5
years.
(iv) Prior to each
inspection required by Subsections R315-264-1084(e)(3)(ii) or (e)(3)(iii), the
owner or operator shall notify the Director in advance of each inspection to
provide the Director with the opportunity to have an observer present during
the inspection. The owner or operator shall notify the Director of the date and
location of the inspection as follows:
(A)
Prior to each visual inspection of an internal floating roof in a tank that has
been emptied and degassed, written notification shall be prepared and sent by
the owner or operator so that it is received by the Director at least 30
calendar days before refilling the tank except when an inspection is not
planned as provided for in Subsection R315-264-1084(e)(3)(iv)(B).
(B) When a visual inspection is not planned
and the owner or operator could not have known about the inspection 30 calendar
days before refilling the tank, the owner or operator shall notify the Director
as soon as possible, but no later than 7 calendar days before refilling of the
tank. This notification may be made by telephone and immediately followed by a
written explanation for why the inspection is unplanned. Alternatively, written
notification, including the explanation for the unplanned inspection, may be
sent so that it is received by the Director at least 7 calendar days before
refilling the tank.
(v)
In the event that a defect is detected, the owner or operator shall repair the
defect in accordance with the requirements of Subsection R315-264-1084(k).
(vi) The owner or operator shall
maintain a record of the inspection in accordance with the requirements
specified in Subsection
R315-264-1089(b).
(4) Safety devices, as
defined in
40 CFR
265.1081, which is adopted by reference, may
be installed and operated as necessary on any tank complying with the
requirements of Subsection R315-264-1084(e).
(f) The owner or operator who controls air
pollutant emissions from a tank using an external floating roof shall meet the
requirements specified in Subsections R315-264-1084(f)(1) through (f)(3).
(1) The owner or operator shall design the
external floating roof in accordance with the following requirements:
(i) The external floating roof shall be
designed to float on the liquid surface except when the floating roof shall be
supported by the leg supports.
(ii) The floating roof shall be equipped with
two continuous seals, one above the other, between the wall of the tank and the
roof edge. The lower seal is referred to as the primary seal, and the upper
seal is referred to as the secondary seal.
(A) The primary seal shall be a
liquid-mounted seal or a metallic shoe seal, as defined in
40 CFR
265.1081, which is adopted by reference. The
total area of the gaps between the tank wall and the primary seal shall not
exceed 212 square centimeters per meter of tank diameter, and the width of any
portion of these gaps shall not exceed 3.8 centimeters. If a metallic shoe seal
is used for the primary seal, the metallic shoe seal shall be designed so that
one end extends into the liquid in the tank and the other end extends a
vertical distance of at least 61 centimeters above the liquid surface.
(B) The secondary seal shall be
mounted above the primary seal and cover the annular space between the floating
roof and the wall of the tank. The total area of the gaps between the tank wall
and the secondary seal shall not exceed 21.2 square centimeters per meter of
tank diameter, and the width of any portion of these gaps shall not exceed 1.3
centimeters.
(iii) The
external floating roof shall meet the following specifications:
(A) Except for automatic bleeder vents,
vacuum breaker vents, and rim space vents, each opening in a noncontact
external floating roof shall provide a projection below the liquid surface.
(B) Except for automatic bleeder
vents, rim space vents, roof drains, and leg sleeves, each opening in the roof
shall be equipped with a gasketed cover, seal, or lid.
(C) Each access hatch and each gauge float
well shall be equipped with a cover designed to be bolted or fastened when the
cover is secured in the closed position.
(D) Each automatic bleeder vent and each rim
space vent shall be equipped with a gasket.
(E) Each roof drain that empties into the
liquid managed in the tank shall be equipped with a slotted membrane fabric
cover that covers at least 90 percent of the area of the opening.
(F) Each unslotted and slotted guide pole
well shall be equipped with a gasketed sliding cover or a flexible fabric
sleeve seal.
(G) Each unslotted
guide pole shall be equipped with a gasketed cap on the end of the pole.
(H) Each slotted guide pole shall
be equipped with a gasketed float or other device which closes off the liquid
surface from the atmosphere.
(I)
Each gauge hatch and each sample well shall be equipped with a gasketed cover.
(2) The
owner or operator shall operate the tank in accordance with the following
requirements:
(i) When the floating roof is
resting on the leg supports, the process of filling, emptying, or refilling
shall be continuous and shall be completed as soon as practical.
(ii) Except for automatic bleeder vents, rim
space vents, roof drains, and leg sleeves, each opening in the roof shall be
secured and maintained in a closed position at all times except when the
closure device shall be open for access.
(iii) Covers on each access hatch and each
gauge float well shall be bolted or fastened when secured in the closed
position.
(iv) Automatic bleeder
vents shall be set closed at all times when the roof is floating, except when
the roof is being floated off or is being landed on the leg supports.
(v) Rim space vents shall be set
to open only at those times that the roof is being floated off the roof leg
supports or when the pressure beneath the rim seal exceeds the manufacturer's
recommended setting.
(vi) The cap
on the end of each unslotted guide pole shall be secured in the closed position
at all times except when measuring the level or collecting samples of the
liquid in the tank.
(vii) The
cover on each gauge hatch or sample well shall be secured in the closed
position at all times except when the hatch or well shall be opened for access.
(viii) Both the primary seal and
the secondary seal shall completely cover the annular space between the
external floating roof and the wall of the tank in a continuous fashion except
during inspections.
(3)
The owner or operator shall inspect the external floating roof in accordance
with the procedures specified as follows:
(i)
The owner or operator shall measure the external floating roof seal gaps in
accordance with the following requirements:
(A) The owner or operator shall perform
measurements of gaps between the tank wall and the primary seal within 60
calendar days after initial operation of the tank following installation of the
floating roof and, thereafter, at least once every 5 years.
(B) The owner or operator shall perform
measurements of gaps between the tank wall and the secondary seal within 60
calendar days after initial operation of the tank following installation of the
floating roof and, thereafter, at least once every year.
(C) If a tank ceases to hold hazardous waste
for a period of 1 year or more, subsequent introduction of hazardous waste into
the tank shall be considered an initial operation for the purposes of
Subsections R315-264-1084(f)(3)(i)(A) and (f)(3)(i)(B).
(D) The owner or operator shall determine the
total surface area of gaps in the primary seal and in the secondary seal
individually using the following procedure:
(1) The seal gap measurements shall be
performed at one or more floating roof levels when the roof is floating off the
roof supports.
(2) Seal gaps, if
any, shall be measured around the entire perimeter of the floating roof in each
place where a 0.32-centimeter diameter uniform probe passes freely, without
forcing or binding against the seal, between the seal and the wall of the tank
and measure the circumferential distance of each such location.
(3) For a seal gap measured under Subsection
R315-264-1084(f)(3), the gap surface area shall be determined by using probes
of various widths to measure accurately the actual distance from the tank wall
to the seal and multiplying each such width by its respective circumferential
distance.
(4) The total gap area
shall be calculated by adding the gap surface areas determined for each
identified gap location for the primary seal and the secondary seal
individually, and then dividing the sum for each seal type by the nominal
diameter of the tank. These total gap areas for the primary seal and secondary
seal are then compared to the respective standards for the seal type as
specified in Subsection R315-264-1084(f)(1)(ii).
(E) In the event that the seal gap
measurements do not conform to the specifications in Subsection
R315-264-1084(f)(1)(ii), the owner or operator shall repair the defect in
accordance with the requirements of Subsection R315-264-1084(k).
(F) The owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in
Subsection
R315-264-1089(b).
(ii) The owner or
operator shall visually inspect the external floating roof in accordance with
the following requirements:
(A) The floating
roof and its closure devices shall be visually inspected by the owner or
operator to check for defects that could result in air pollutant emissions.
Defects include, but are not limited to: Holes, tears, or other openings in the
rim seal or seal fabric of the floating roof; a rim seal detached from the
floating roof; all or a portion of the floating roof deck being submerged below
the surface of the liquid in the tank; broken, cracked, or otherwise damaged
seals or gaskets on closure devices; and broken or missing hatches, access
covers, caps, or other closure devices.
(B) The owner or operator shall perform an
initial inspection of the external floating roof and its closure devices on or
before the date that the tank becomes subject to Section R315-264-1084.
Thereafter, the owner or operator shall perform the inspections at least once
every year except for the special conditions provided for in Subsection
R315-264-1084(l).
(C) In the event
that a defect is detected, the owner or operator shall repair the defect in
accordance with the requirements of Subsection R315-264-1084(k).
(D) The owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in
Subsection
R315-264-1089(b).
(iii) Prior to each
inspection required by Subsections R315-264-1084(f)(3)(i) or (f)(3)(ii), the
owner or operator shall notify the Director in advance of each inspection to
provide the Director with the opportunity to have an observer present during
the inspection. The owner or operator shall notify the Director of the date and
location of the inspection as follows:
(A)
Prior to each inspection to measure external floating roof seal gaps as
required under Subsection R315-264-1084(f)(3)(i), written notification shall be
prepared and sent by the owner or operator so that it is received by the
Director at least 30 calendar days before the date the measurements are
scheduled to be performed.
(B)
Prior to each visual inspection of an external floating roof in a tank that has
been emptied and degassed, written notification shall be prepared and sent by
the owner or operator so that it is received by the Director at least 30
calendar days before refilling the tank except when an inspection is not
planned as provided for in Subsection R315-264-1084(f)(3)(iii)(C).
(C) When a visual inspection is not planned
and the owner or operator could not have known about the inspection 30 calendar
days before refilling the tank, the owner or operator shall notify the Director
as soon as possible, but no later than 7 calendar days before refilling of the
tank. This notification may be made by telephone and immediately followed by a
written explanation for why the inspection is unplanned. Alternatively, written
notification, including the explanation for the unplanned inspection, may be
sent so that it is received by the Director at least 7 calendar days before
refilling the tank.
(4) Safety devices, as defined in
40 CFR
265.1081, which is adopted by reference, may
be installed and operated as necessary on any tank complying with the
requirements of Subsection R315-264-1084(f).
(g) The owner or operator who controls air
pollutant emissions from a tank by venting the tank to a control device shall
meet the requirements specified in Subsections R315-264-1084(g)(1) through
(g)(3).
(1) The tank shall be covered by a
fixed roof and vented directly through a closed-vent system to a control device
in accordance with the following requirements:
(i) The fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the liquid in the tank.
(ii) Each
opening in the fixed roof not vented to the control device shall be equipped
with a closure device. If the pressure in the vapor headspace underneath the
fixed roof is less than atmospheric pressure when the control device is
operating, the closure devices shall be designed to operate such that when the
closure device is secured in the closed position there are no visible cracks,
holes, gaps, or other open spaces in the closure device or between the
perimeter of the cover opening and the closure device. If the pressure in the
vapor headspace underneath the fixed roof is equal to or greater than
atmospheric pressure when the control device is operating, the closure device
shall be designed to operate with no detectable organic emissions.
(iii) The fixed roof and its closure devices
shall be made of suitable materials that will minimize exposure of the
hazardous waste to the atmosphere, to the extent practical, and will maintain
the integrity of the fixed roof and closure devices throughout their intended
service life. Factors to be considered when selecting the materials for and
designing the fixed roof and closure devices shall include: Organic vapor
permeability, the effects of any contact with the liquid and its vapor managed
in the tank; the effects of outdoor exposure to wind, moisture, and sunlight;
and the operating practices used for the tank on which the fixed roof is
installed.
(iv) The closed-vent
system and control device shall be designed and operated in accordance with the
requirements of Section
R315-264-1087.
(2) Whenever a
hazardous waste is in the tank, the fixed roof shall be installed with each
closure device secured in the closed position and the vapor headspace
underneath the fixed roof vented to the control device except as follows:
(i) Venting to the control device is not
required, and opening of closure devices or removal of the fixed roof is
allowed at the following times:
(A) To
provide access to the tank for performing routine inspection, maintenance, or
other activities needed for normal operations. Examples of such activities
include those times when a worker needs to open a port to sample liquid in the
tank, or when a worker needs to open a hatch to maintain or repair equipment.
Following completion of the activity, the owner or operator shall promptly
secure the closure device in the closed position or reinstall the cover, as
applicable, to the tank.
(B) To
remove accumulated sludge or other residues from the bottom of a tank.
(ii) Opening of a
safety device, as defined in
40 CFR
265.1081, which is adopted by reference, is
allowed at any time conditions require doing so to avoid an unsafe condition.
(3) The owner or
operator shall inspect and monitor the air emission control equipment in
accordance with the following procedures:
(i)
The fixed roof and its closure devices shall be visually inspected by the owner
or operator to check for defects that could result in air pollutant emissions.
Defects include, but are not limited to, visible cracks, holes, or gaps in the
roof sections or between the roof and the tank wall; broken, cracked, or
otherwise damaged seals or gaskets on closure devices; and broken or missing
hatches, access covers, caps, or other closure devices.
(ii) The closed-vent system and control
device shall be inspected and monitored by the owner or operator in accordance
with the procedures specified in Section
R315-264-1087.
(iii) The owner or operator shall
perform an initial inspection of the air emission control equipment on or
before the date that the tank becomes subject to Section R315-264-1084.
Thereafter, the owner or operator shall perform the inspections at least once
every year except for the special conditions provided for in Subsection
R315-264-1084(l).
(iv) In the
event that a defect is detected, the owner or operator shall repair the defect
in accordance with the requirements of Subsection R315-264-1084(k).
(v) The owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in
Subsection
R315-264-1089(b).
(h) The
owner or operator who controls air pollutant emissions by using a pressure tank
shall meet the following requirements.
(1)
The tank shall be designed not to vent to the atmosphere as a result of
compression of the vapor headspace in the tank during filling of the tank to
its design capacity.
(2) All tank
openings shall be equipped with closure devices designed to operate with no
detectable organic emissions as determined using the procedure specified in
Subsection
R315-264-1083(d).
(3) Whenever a hazardous waste is
in the tank, the tank shall be operated as a closed system that does not vent
to the atmosphere except under either or the following conditions as specified
in Subsections R315-264-1084(h)(3)(i) or (h)(3)(ii).
(i) At those times when opening of a safety
device, as defined in
40 CFR
265.1081, which is adopted by reference, is
required to avoid an unsafe condition.
(ii) At those times when purging of inerts
from the tank is required and the purge stream is routed to a closed-vent
system and control device designed and operated in accordance with the
requirements of Section
R315-264-1087.
(i) The
owner or operator who controls air pollutant emissions by using an enclosure
vented through a closed-vent system to an enclosed combustion control device
shall meet the requirements specified in Subsections R315-264-1084(i)(1)
through (i)(4).
(1) The tank shall be located
inside an enclosure. The enclosure shall be designed and operated in accordance
with the criteria for a permanent total enclosure as specified in "Procedure
T-Criteria for and Verification of a Permanent or Temporary Total Enclosure"
under
40
CFR 52.741, appendix B. The enclosure may
have permanent or temporary openings to allow worker access; passage of
material into or out of the enclosure by conveyor, vehicles, or other
mechanical means; entry of permanent mechanical or electrical equipment; or
direct airflow into the enclosure. The owner or operator shall perform the
verification procedure for the enclosure as specified in Section 5.0 to
"Procedure T-Criteria for and Verification of a Permanent or Temporary Total
Enclosure" initially when the enclosure is first installed and, thereafter,
annually.
(2) The enclosure shall
be vented through a closed-vent system to an enclosed combustion control device
that is designed and operated in accordance with the standards for either a
vapor incinerator, boiler, or process heater specified in Section
R315-264-1087.
(3) Safety devices, as defined in
40 CFR
265.1081, which is adopted by reference, may
be installed and operated as necessary on any enclosure, closed-vent system, or
control device used to comply with the requirements of Subsections
R315-264-1084(i)(1) and (i)(2).
(4) The owner or operator shall inspect and
monitor the closed-vent system and control device as specified in Section
R315-264-1087.
(j) The owner or
operator shall transfer hazardous waste to a tank subject to Section
R315-264-1084 in accordance with the following requirements:
(1) Transfer of hazardous waste, except as
provided in Subsection R315-264-1084(j)(2), to the tank from another tank
subject to Section R315-264-1084 or from a surface impoundment subject to
Section
R315-264-1085
shall be conducted using continuous hard-piping or another closed system that
does not allow exposure of the hazardous waste to the atmosphere. For the
purpose of complying with this provision, an individual drain system is
considered to be a closed system when it meets the requirements of Subsection
R307-214-2(29),
which incorporates 40 CFR part 63, subpart RR-National Emission Standards for
Individual Drain Systems.
(2) The
requirements of Subsection R315-264-1084(j)(1) do not apply when transferring a
hazardous waste to the tank under any of the following conditions:
(i) The hazardous waste meets the average VO
concentration conditions specified in Subsection
R315-264-1082(c)(1)
at the point of waste origination.
(ii) The hazardous waste has been treated by
an organic destruction or removal process to meet the requirements in
Subsection
R315-264-1082(c)(2).
(iii) The hazardous waste meets
the requirements of Subsection
R315-264-1082(c)(4).
(k) The
owner or operator shall repair each defect detected during an inspection
performed in accordance with the requirements of Subsections
R315-264-1084(c)(4), (e)(3), (f)(3), or (g)(3) as follows:
(1) The owner or operator shall make first
efforts at repair of the defect no later than 5 calendar days after detection,
and repair shall be completed as soon as possible but no later than 45 calendar
days after detection except as provided in Subsection R315-264-1084(k)(2).
(2) Repair of a defect may be
delayed beyond 45 calendar days if the owner or operator determines that repair
of the defect requires emptying or temporary removal from service of the tank
and no alternative tank capacity is available at the site to accept the
hazardous waste normally managed in the tank. In this case, the owner or
operator shall repair the defect the next time the process or unit that is
generating the hazardous waste managed in the tank stops operation. Repair of
the defect shall be completed before the process or unit resumes operation.
(l) Following the
initial inspection and monitoring of the cover as required by the applicable
provisions of Sections
R315-264-1080
through 1090, subsequent inspection and monitoring may be performed at
intervals longer than 1 year under the following special conditions:
(1) In the case when inspecting or monitoring
the cover would expose a worker to dangerous, hazardous, or other unsafe
conditions, then the owner or operator may designate a cover as an "unsafe to
inspect and monitor cover" and comply with all of the following requirements:
(i) Prepare a written explanation for the
cover stating the reasons why the cover is unsafe to visually inspect or to
monitor, if required.
(ii) Develop
and implement a written plan and schedule to inspect and monitor the cover,
using the procedures specified in the applicable section of Sections
R315-264-1080
through 1090, as frequently as practicable during those times when a worker can
safely access the cover.
(2) In the case when a tank is buried
partially or entirely underground, an owner or operator is required to inspect
and monitor, as required by the applicable provisions of Section R315-264-1084,
only those portions of the tank cover and those connections to the tank, e.g.,
fill ports, access hatches, gauge wells, etc., that are located on or above the
ground surface.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.