Utah Admin. Code R315-265-1033 - Air Emission Standards for Process Vents-Standards: Closed-Vent Systems and Control Devices
(a)
(1) Owners or operators of closed-vent
systems and control devices used to comply with provisions of Sections
R315-265-1030 through R315-265-1035 shall comply with the provisions of Section
R315-265-1033.
(2)
(i) The owner or operator of an existing
facility who cannot install a closed-vent system and control device to comply
with the provisions of Sections R315-265-1030 through R315-265-1035 on the
effective date that the facility becomes subject to the requirements of
Sections R315-265-1030 through R315-265-1035 shall prepare an implementation
schedule that includes dates by which the closed-vent system and control device
will be installed and in operation. The controls shall be installed as soon as
possible, but the implementation schedule may allow up to 30 months after the
effective date that the facility becomes subject to Sections R315-265-1030
through R315-265-1035 for installation and startup.
(ii) Any unit that begins operation after
December 21, 1990, and is subject to the requirements of Sections R315-265-1030
through R315-265-1035 when operation begins, shall comply with the rules
immediately, for example, shall have control devices installed and operating on
startup of the affected unit; the 30-month implementation schedule does not
apply.
(iii) The owner or operator
of any facility in existence on the effective date of a statutory or regulatory
amendment that renders the facility subject to Sections R315-265-1030 through
R315-265-1035 shall comply with all requirements of Sections R315-265-1030
through R315-265-1035 as soon as practicable but no later than 30 months after
the amendment's effective date. If control equipment required by Sections
R315-265-1030 through R315-265-1035 cannot be installed and begin operation by
the effective date of the amendment, the facility owner or operator shall
prepare an implementation schedule that includes the following information:
Specific calendar dates for award of contracts or issuance of purchase orders
for the control equipment, initiation of on-site installation of the control
equipment, completion of the control equipment installation, and performance of
any testing to demonstrate that the installed equipment meets the applicable
standards of Sections R315-265-1030 through R315-265-1035. The owner or
operator shall enter the implementation schedule in the operating record or in
a permanent, readily available file located at the facility .
(iv) Owners and operators of facilities and
units that become newly subject to the requirements of Sections R315-265-1030
through R315-265-1035 after December 8, 1997, due to an action other than those
described in Subsection R315-265-1033(a)(2)(iii) shall comply with all
applicable requirements immediately, for example, shall have control devices
installed and operating on the date the facility or unit becomes subject to
Sections R315-265-1030 through R315-265-1035; the 30-month implementation
schedule does not apply.
(b) A control device involving vapor
recovery, for example, a condenser or adsorber, shall be designed and operated
to recover the organic vapors vented to it with an efficiency of 95 weight
percent or greater unless the total organic emission limits of Subsection
R315-265-1032(a)(1) for all affected process vents can be attained at an
efficiency less than 95 weight percent.
(c) An enclosed combustion device, for
example, a vapor incinerator, boiler, or process heater, shall be designed and
operated to reduce the organic emissions vented to it by 95 weight percent or
greater; to achieve a total organic compound concentration of 20 ppmv,
expressed as the sum of the actual compounds, not carbon equivalents, on a dry
basis corrected to 3 percent oxygen; or to provide a minimum residence time of
0.50 seconds at a minimum temperature of 760 degrees Celsius. If a boiler or
process heater is used as the control device, then the vent stream shall be
introduced into the flame combustion zone of the boiler or process
heater.
(d)
(1) A flare shall be designed for and
operated with no visible emissions as determined by the methods specified in
Subsection R315-265-1033(e)(1), except for periods not to exceed a total of 5
minutes during any 2 consecutive hours.
(2) A flare shall be operated with a flame
present at all times, as determined by the methods specified in Subsection
R315-265-1033(f)(2)(iii).
(3) A
flare shall be used only if the net heating value of the gas being combusted is
11.2 MJ/scm, 300 Btu/scf, or greater, if the flare is steam-assisted or
air-assisted; or if the net heating value of the gas being combusted is 7.45
MJ/scm, 200 Btu/scf, or greater if the flare is nonassisted. The net heating
value of the gas being combusted shall be determined by the methods specified
in Subsection R315-265-1033(e)(2).
(4)
(i) A
steam-assisted or nonassisted flare shall be designed for and operated with an
exit velocity, as determined by the methods specified in Subsection
R315-265-1033(e)(3), of less than 18.3 m/s, 60 ft/s, except as provided in
Subsections R315-265-1033(d)(4)(ii) and R315-265-1033(d)(4)(iii).
(ii) A steam-assisted or nonassisted flare
designed for and operated with an exit velocity, as determined by the methods
specified in Subsection R315-265-1033(e)(3), equal to or greater than 18.3 m/s,
60 ft/s, but less than 122 m/s, 400 ft/s, is allowed if the net heating value
of the gas being combusted is greater than 37.3 MJ/scm, 1,000
Btu/scf.
(iii) A steam-assisted or
nonassisted flare designed for and operated with an exit velocity, as
determined by the methods specified in Subsection R315-265-1033(e)(3), less
than the velocity, Vmax, as determined by the method specified in Subsection
R315-265-1033(e)(4), and less than 122 m/s, 400 ft/s, is allowed.
(5) An air-assisted flare shall be
designed and operated with an exit velocity less than the velocity, Vmax, as
determined by the method specified in Subsection R315-265-1033(e)(5).
(6) A flare used to comply with Section
R315-265-1033 shall be steam-assisted, air-assisted, or nonassisted.
(e)
(1) Reference Method 22 in 40 CFR part 60
shall be used to determine the compliance of a flare with the visible emission
provisions of this subpart. The observation period is 2 hours and shall be used
according to Method 22.
(2) The net
heating value of the gas being combusted in a flare shall be calculated using
the equation found in
40 CFR
265.1033(e)(2), which is
adopted and incorporated by reference.
(3) The actual exit velocity of a flare shall
be determined by dividing the volumetric flow rate, in units of standard
temperature and pressure, as determined by Reference Methods 2, 2A, 2C, or 2D
in 40 CFR part 60 as appropriate, by the unobstructed, free, cross-sectional
area of the flare tip.
(4) The
maximum allowed velocity in m/s, Vmax, for a flare complying with Subsesction
R315-265-1033(d)(4)(iii) shall be determined by the following equation:
Log10(Vmax) = (HT + 28.8)/31.7
where:
HT = The net heating value as determined in Subsection R315-265-1033(e)(2).
28.8 = Constant.
31.7 = Constant.
(5) The maximum allowed velocity in m/s,
Vmax, for an air-assisted flare shall be determined by the following equation:
Vmax = 8.706 + 0.7084(HT)
where:
8.706 = Constant.
0.7084 = Constant.
HT = The net heating value as determined in Subsection R315-265-1033(e)(2).
(f) The owner or operator shall monitor and
inspect each control device required to comply with Section R315-265-1033 to
ensure proper operation and maintenance of the control device by implementing
the following requirements:
(1) Install,
calibrate, maintain, and operate according to the manufacturer's specifications
a flow indicator that provides a record of vent stream flow from each affected
process vent to the control device at least once every hour. The flow indicator
sensor shall be installed in the vent stream at the nearest feasible point to
the control device inlet, but before being combined with other vent
streams.
(2) Install, calibrate,
maintain, and operate according to the manufacturer's specifications a device
to continuously monitor control device operation as specified below:
(i) For a thermal vapor incinerator, a
temperature monitoring device equipped with a continuous recorder. The device
shall have an accuracy of plus or minus 1 percent of the temperature being
monitored in degrees Celsius or plus or minus 0.5 degrees Celsius, whichever is
greater. The temperature sensor shall be installed at a location in the
combustion chamber downstream of the combustion zone.
(ii) For a catalytic vapor incinerator, a
temperature monitoring device equipped with a continuous recorder. The device
shall be capable of monitoring temperature at two locations and have an
accuracy of plus or minus 1 percent of the temperature being monitored in
degrees Celsius or plus or minus 0.5 degrees Celsius, whichever is greater. One
temperature sensor shall be installed in the vent stream at the nearest
feasible point to the catalyst bed inlet and a second temperature sensor shall
be installed in the vent stream at the nearest feasible point to the catalyst
bed outlet.
(iii) For a flare, a
heat sensing monitoring device equipped with a continuous recorder that
indicates the continuous ignition of the pilot flame.
(iv) For a boiler or process heater having a
design heat input capacity less than 44 MW, a temperature monitoring device
equipped with a continuous recorder. The device shall have an accuracy of plus
or minus 1 percent of the temperature being monitored in degrees Celsius or
plus or minus 0.5 degrees Celsius, whichever is greater. The temperature sensor
shall be installed at a location in the furnace downstream of the combustion
zone.
(v) For a boiler or process
heater having a design heat input capacity greater than or equal to 44 MW, a
monitoring device equipped with a continuous recorder to measure a parameter or
parameters that indicate good combustion operating practices are being
used.
(vi) For a condenser, either:
(A) A monitoring device equipped with a
continuous recorder to measure the concentration level of the organic compounds
in the exhaust vent stream from the condenser; or
(B) A temperature monitoring device equipped
with a continuous recorder. The device shall be capable of monitoring
temperature with an accuracy of plus or minus 1 percent of the temperature
being monitored in degrees Celsius or plus or minus 0.5 degrees Celsius,
whichever is greater. The temperature sensor shall be installed at a location
in the exhaust vent stream from the condenser exit, for example, product
side.
(vii) For a carbon
adsorption system such as a fixed-bed carbon adsorber that regenerates the
carbon bed directly in the control device, either:
(A) A monitoring device equipped with a
continuous recorder to measure the concentration level of the organic compounds
in the exhaust vent stream from the carbon bed, or
(B) A monitoring device equipped with a
continuous recorder to measure a parameter that indicates the carbon bed is
regenerated on a regular, predetermined time cycle.
(3) Inspect the readings from each
monitoring device required by Subsections R315-265-1033(f) (1) and
R315-265-1033(f)(2) at least once each operating day to check control device
operation and, if necessary, immediately implement the corrective measures
necessary to ensure the control device operates in compliance with the
requirements of Section R315-265-1033.
(g) An owner or operator using a carbon
adsorption system such as a fixed-bed carbon adsorber that regenerates the
carbon bed directly onsite in the control device, shall replace the existing
carbon in the control device with fresh carbon at a regular, predetermined time
interval that is no longer than the carbon service life established as a
requirement of Subsection R315-265-1035(b)(4)(iii)(F).
(h) An owner or operator using a carbon
adsorption system such as a carbon canister that does not regenerate the carbon
bed directly onsite in the control device shall replace the existing carbon in
the control device with fresh carbon on a regular basis by using one of the
following procedures:
(1) Monitor the
concentration level of the organic compounds in the exhaust vent stream from
the carbon adsorption system on a regular schedule and replace the existing
carbon with fresh carbon immediately if carbon breakthrough is indicated. The
monitoring frequency shall be daily or at an interval no greater than 20
percent of the time required to consume the total carbon working capacity
established as a requirement of Subsection R315-265-1035(b)(4)(iii)(G),
whichever is longer.
(2) Replace
the existing carbon with fresh carbon at a regular, predetermined time interval
that is less than the design carbon replacement interval established as a
requirement of Subsection R315-265-1035(b)(4)(iii)(G).
(i) An owner or operator of an affected
facility seeking to comply with the provisions of Sections R315-265-1030
through R315-265-1035 by using a control device other than a thermal vapor
incinerator, catalytic vapor incinerator, flare, boiler, process heater,
condenser, or carbon adsorption system is required to develop documentation
including sufficient information to describe the control device operation and
identify the process parameter or parameters that indicate proper operation and
maintenance of the control device.
(j) A closed-vent system shall meet either of
the following design requirements:
(1) A
closed-vent system shall be designed to operate with no detectable emissions,
as indicated by an instrument reading of less than 500 ppmv above background as
determined by the procedure in Subsection R315-265-1034(b), and by visual
inspections; or
(2) A closed-vent
system shall be designed to operate at a pressure below atmospheric pressure.
The system shall be equipped with at least one pressure gauge or other pressure
measurement device that can be read from a readily accessible location to
verify that negative pressure is being maintained in the closed-vent system if
the control device is operating.
(k) The owner or operator shall monitor and
inspect each closed-vent system required to comply with Section R315-265-1033
to ensure proper operation and maintenance of the closed-vent system by
implementing the following requirements:
(1)
Each closed-vent system that is used to comply with Subsection
R315-265-1033(j)(1) shall be inspected and monitored in accordance with the
following requirements:
(i) An initial leak
detection monitoring of the closed-vent system shall be conducted by the owner
or operator on or before the date that the system becomes subject to Section
R315-265-1033. The owner or operator shall monitor the closed-vent system
components and connections using the procedures specified in Subsection
R315-265-1034(b) to demonstrate that the closed-vent system operates with no
detectable emissions, as indicated by an instrument reading of less than 500
ppmv above background.
(ii) After
initial leak detection monitoring required in Subsection
R315-265-1033(k)(1)(i), the owner or operator shall inspect and monitor the
closed-vent system as follows:
(A) Closed-vent
system joints, seams, or other connections that are permanently or
semi-permanently sealed, for example, a welded joint between two sections of
hard piping or a bolted and gasketed ducting flange, shall be visually
inspected at least once per year to check for defects that could result in air
pollutant emissions. The owner or operator shall monitor a component or
connection using the procedures specified in Subsection R315-265-1034(b) to
demonstrate that it operates with no detectable emissions following any time
the component is repaired or replaced, for example, a section of damaged hard
piping is replaced with new hard piping, or the connection is unsealed, for
example, a flange is unbolted.
(B)
Closed-vent system components or connections other than those specified in
Subsection R315-265-1033(k)(1)(ii)(A) shall be monitored annually and at other
times as requested by the Director , except as provided for in Subsection
R315-265-1033(n), using the procedures specified in Subsection R315-265-1034(b)
to demonstrate that the components or connections operate with no detectable
emissions.
(iii) In the
event that a defect or leak is detected, the owner or operator shall repair the
defect or leak in accordance with the requirements of Subsection
R315-265-1033(k)(3).
(iv) The owner
or operator shall maintain a record of the inspection and monitoring in
accordance with the requirements specified in Section R315-265-1035.
(2) Each closed-vent system that
is used to comply with Subsection R315-265-1033(j)(2) shall be inspected and
monitored in accordance with the following requirements:
(i) The closed-vent system shall be visually
inspected by the owner or operator to check for defects that could result in
air pollutant emissions. Defects include, but are not limited to, visible
cracks, holes, or gaps in ductwork or piping or loose connections.
(ii) The owner or operator shall perform an
initial inspection of the closed-vent system on or before the date that the
system becomes subject to Section R315-265-1033. Thereafter, the owner or
operator shall perform the inspections at least once every year .
(iii) In the event that a defect or leak is
detected, the owner or operator shall repair the defect in accordance with the
requirements of Subsection R315-265-1033(k)(3).
(iv) The owner or operator shall maintain a
record of the inspection and monitoring in accordance with the requirements
specified in Section R315-265-1035.
(3) The owner or operator shall repair all
detected defects as follows:
(i) Detectable
emissions, as indicated by visual inspection , or by an instrument reading
greater than 500 ppmv above background, shall be controlled as soon as
practicable, but not later than 15 calendar days after the emission is
detected, except as provided for in Subsection
R315-265-1033(k)(3)(iii).
(ii) A
first attempt at repair shall be made no later than 5 calendar days after the
emission is detected.
(iii) Delay
of repair of a closed-vent system for which leaks have been detected is allowed
if the repair is technically infeasible without a process unit shutdown, or if
the owner or operator determines that emissions resulting from immediate repair
would be greater than the fugitive emissions likely to result from delay of
repair. Repair of such equipment shall be completed by the end of the next
process unit shutdown.
(iv) The
owner or operator shall maintain a record of the defect repair in accordance
with the requirements specified in Section R315-265-1035.
(l) Closed-vent systems and
control devices used to comply with provisions of Sections R315-265-1030
through R315-265-1035 shall be operated at all times if emissions may be vented
to them.
(m) The owner or operator
using a carbon adsorption system to control air pollutant emissions shall
document that all carbon that is a hazardous waste and that is removed from the
control device is managed in one of the following manners, regardless of the
average volatile organic concentration of the carbon:
(1) Regenerated or reactivated in a thermal
treatment unit that meets one of the following:
(i) The owner or operator of the unit has
been issued a final permit under Rule R315-270 which implements the
requirements of Sections
R315-264-600
through
R315-264-603;
or
(ii) The unit is equipped with
and operating air emission controls in accordance with the applicable
requirements of Sections R315-265-1030 through R315-265-1035 and Sections
R315-265-1080 through R315-265-1090 or of Sections
R315-264-1030
through
R315-264-1036
and Sections
R315-264-1080
through
R315-264-1090;
or
(2) Incinerated in a
hazardous waste incinerator for which the owner or operator either:
(i) Has been issued a final permit under Rule
R315-270 which implements the requirements of Sections
R315-264-340
through
R315-264-351;
or
(ii) Has designed and operates
the incinerator in accordance with the interim status requirements of
40
CFR 265.340 through 352, which are adopted
and incorporated by reference.
(3) Burned in a boiler or industrial furnace
for which the owner or operator either:
(i)
Has been issued a final permit under Rule R315-270 which implements the
requirements of Sections
R315-266-100
through
R315-266-112;
or
(ii) Has designed and operates
the boiler or industrial furnace in accordance with the interim status
requirements of Sections
R315-266-100
through
R315-266-112.
(n) Any components of a
closed-vent system that are designated, as described in Subsection
R315-265-1035(c)(9), as unsafe to monitor are exempt from the requirements of
Subsection R315-265-1033(k)(1)(ii)(B) if:
(1)
The owner or operator of the closed-vent system determines that the components
of the closed-vent system are unsafe to monitor because monitoring personnel
would be exposed to an immediate danger as a consequence of complying with
Subsection R315-265-1033(k)(1)(ii)(B); and
(2) The owner or operator of the closed-vent
system adheres to a written plan that requires monitoring the closed-vent
system components using the procedure specified in Subsection
R315-265-1033(k)(1)(ii)(B) as frequently as practicable during safe-to-monitor
times.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.