Utah Admin. Code R392-302-27 - Dressing Rooms
The manager shall ensure that:
(1) each area and fixture within a dressing
room is maintained in an operable, clean, and sanitary condition;
(2) where dressing rooms are provided, the
entrances and exits are designed to break the line of sight into the dressing
areas from other locations;
(3)
each dressing room is constructed of materials that have smooth, non-slip
surfaces, and are impervious to moisture;
(4) dressing room floors slope to a drain and
are constructed to prevent accumulation of water;
(5) carpeting is not installed on dressing
room floors;
(6) each junction
between walls and floors are coved;
(7) the walls or partitions between dressing
cubicles begin at a height not more than 12 inches from and extend not less
than 60 inches above the finished floor surface or are placed on continuous
raised masonry or concrete bases at least four inches high;
(8) each locker is:
(a) set on:
(i) a solid masonry base no less than four
inches high; or
(ii) legs elevating
the bottom locker at least four inches above the floor; and
(b) equipped with louvers for
ventilation; and
(9) at
least one covered waste receptacle is provided in each dressing room.