Utah Admin. Code R432-12-15 - Ceilings
(1) The licensee shall ensure that ceiling
height in the facility is at least eight feet except:
(a) rooms containing ceiling-mounted
equipment have adequate height for the proper functioning of that
equipment;
(b) ceilings in
corridors, storage rooms, and toilet rooms are at least seven feet ten inches;
and
(c) building components and
suspended tracks, rails, and pipes located in the path of normal traffic are
not less than seven feet above the floor.
(2) If existing conditions make compliance
with Subsection R432-12-15(1)
impractical, there shall be enough clearance to avoid injury and at least six
feet four inches above the floor.