A. The owner of a waterworks that uses a
surface water source, a GUDI source, or both and provides filtration treatment
shall monitor in accordance with this section.
B. Turbidity measurements shall be performed
on representative samples of the filtered water every four hours (or more
frequently) that the waterworks serves water to the public. The owner may
substitute continuous turbidity monitoring for grab sample monitoring if the
owner validates the continuous measurement for accuracy on a regular basis
using a protocol approved by the department. For a waterworks using slow sand
filtration or filtration treatment other than conventional treatment, direct
filtration, or diatomaceous earth filtration, the department may reduce the
sampling frequency to once per day if the department determines that less
frequent monitoring is sufficient to indicate effective filtration performance.
For a waterworks serving 500 or fewer persons, the department may reduce the
turbidity sampling frequency to once per day, regardless of the type of
filtration treatment used, if the department determines that less frequent
monitoring is sufficient to indicate effective filtration performance.
1. The owner of a waterworks supplied by a
surface water source, a GUDI source, or both using conventional filtration
treatment or direct filtration shall conduct continuous monitoring of turbidity
for each individual filter. The turbidimeter shall be calibrated using the
procedure specified by the turbidimeter manufacturer. The owner shall record
the results of individual filter turbidity monitoring a minimum of every 15
minutes.
2. If there is a failure
in the continuous turbidity monitoring equipment, then the owner shall conduct
grab sampling every four hours instead of continuous monitoring but for no more
than five working days (for a waterworks serving 10,000 or more persons) or 14
days (for a waterworks serving less fewer than 10,000 persons) following the
failure of the equipment.
3. If a
waterworks serving fewer than 10,000 persons consists of two or fewer filters,
continuous monitoring of the CFE may be used instead of individual filter
monitoring.
C. The
residual disinfectant concentration of the water entering the distribution
system shall be monitored continuously, and the lowest and highest values shall
be recorded each day. If there is a failure in the continuous monitoring
equipment, then grab sampling every four hours shall be conducted instead of
continuous monitoring, but such grab sampling shall be conducted for no more
than five working days following the failure of the equipment. The owner of a
waterworks serving 3,300 or fewer persons may collect grab samples instead of
continuous monitoring on an ongoing basis at the frequencies prescribed in
Table 376.1.
1. The day's samples cannot be
collected at the same time.
2. The
sampling intervals are subject to department's evaluation and
approval.
3. If at any time the
residual disinfectant concentration falls below 0.2 mg/L in a waterworks using
grab sampling instead of continuous monitoring, then the owner shall collect a
grab sample every four hours until the residual disinfectant concentration is
equal to or greater than 0.2 mg/L.
|
TABLE 376.1
Grab Sample Monitoring Frequency
|
|
WATERWORKS SIZE BY POPULATION
|
SAMPLES/DAY
|
|
500 or less
|
1
|
|
501 - 1,000
|
2
|
|
1,000 - 2,500
|
3
|
|
2,501 - 3,300
|
4
|
D. The residual disinfectant concentration
shall be measured at least at the same points in the distribution system and at
the same time as total coliform bacteria are sampled, as specified in
12VAC5-590-370 A
and
12VAC5-590-380 D,
except that the department may allow the owner of a waterworks that uses a
groundwater source along with a surface water source, a GUDI source, or both to
collect residual disinfectant samples at points other than the total coliform
sampling points if the department determines that these points are more
representative of treated (disinfected) water quality within the distribution
system. Heterotrophic bacteria, measured as HPC as specified in
12VAC5-590-395 A 2 a
(3), may be measured instead of residual
disinfectant concentration.
E. The
following information on the samples collected in the distribution system in
conjunction with total coliform monitoring pursuant to
12VAC5-590-395 A
2 shall be reported monthly to the department
by the owner:
1. Number of instances where the
residual disinfectant concentration is measured;
2. Number of instances where the residual
disinfectant concentration is not measured but heterotropic plate count (HPC)
is measured;
3. Number of instances
where the residual disinfectant concentration is measured but not detected and
no HPC is measured;
4. Number of
instances where no residual disinfectant concentration is detected and where
the HPC is greater than 500/mL;
5.
Number of instances where the residual disinfectant concentration is not
measured and HPC is greater than 500/mL; and
6. For the current and previous month the
waterworks serves water to the public, the value of "V," in percent, in the
following formula:
V = [(c + d + e) / (a + b)] X 100
where
a = the value in subdivision E 1 of this section;
b = the value in subdivision E 2 of this section;
c = the value in subdivision E 3 of this section;
d = the value in subdivision E 4 of this section;
e = the value in subdivision E 5 of this
section.