Fla. Admin. Code Ann. R. 62-604.400 - Design/Performance Considerations
(1) All
new collection/transmission systems and modifications of existing systems for
which construction permits are required by the Department shall be designed:
(a) In accordance with sound engineering
practices to provide reasonable assurance the collection/transmission system
will meet the requirements of this chapter;
(b) To be located on public right-of-ways,
land owned by the permittee, or easements;
(c) Except as provided in Chapter 62-532,
F.A.C., to be located no closer than 100 feet from a public drinking water
supply well and no closer than 75 feet from a private drinking water supply
well unless the applicant provides documentation accompanying the permit
application showing that another alternative will result in an equivalent level
of reliability and public health protection; and,
(d) To preclude the deliberate introduction
of storm water, surface water, groundwater, roof runoff, subsurface drainage,
swimming pool drainage, air conditioning system condensate water, non-contact
cooling water except as provided by subsection
62-610.668(1),
F.A.C., and sources of uncontaminated wastewater. However,
collection/transmission systems may be designed to augment the supply of
reclaimed water when all conditions of paragraph
62-610.472(3)(c),
F.A.C., are met.
(2) In
addition to subsection (1), above, the following requirements shall be met
where applicable:
(a) Emergency pumping
capability shall be provided for all pump stations. Pumping capability shall be
provided as follows:
1. Pump stations that
receive flow from one or more pump stations through a force main or pump
stations discharging through pipes 12 inches or larger shall provide for
uninterrupted pumping capabilities, including an in-place emergency
generator.
2. For pump stations not
addressed in subparagraph (2)(a)1., above, emergency pumping capability may be
accomplished by connection of the station to at least two independent utility
substations, by providing a connection for portable or in-place engine-driven
generating equipment, or by providing portable pumping equipment.
3. Such emergency standby systems shall have
sufficient capacity to start up and maintain the total rated running capacity
of the station. Regardless of the type of emergency standby system provided, a
riser from the force main with rapid connection capabilities and appropriate
valving shall be provided for all pump stations to hook up portable pumps. All
pump station reliability design features shall be compatible with the available
temporary service power generating and pumping equipment of the authority
responsible for operation and maintenance of the collection/transmission
system.
(b) Pumping
stations shall be protected from lightning and transient voltage surges. As a
minimum, stations shall be equipped with lightning arrestors, surge capacitors
or other similar protection devices, and phase protection. Small pumping
stations serving a single building will not be required to provide surge
protection devices when they are not necessary to protect the pump station.
Complex or critical pumping stations shall be designed to incorporate standby
pumping capability, power generation, and other appropriate features pursuant
to paragraph 62-604.300(5)(h),
F.A.C.
(c) New pumping stations
shall be designed and located on the site so as to minimize adverse effects
resulting from odors, noise, and lighting. The permittee shall give reasonable
assurance that the facility shall not cause odor, noise or lighting in such
amounts or at such levels that they adversely affect neighboring residents, in
commercial or residential areas, so as to be potentially harmful or injurious
to human health or welfare or unreasonably interfere with the enjoyment of life
or property, including outdoor recreation. Reasonable assurance may be based on
such means as aeration, landscaping, treatment of vented gases, buffer zones
owned or under the control of the permittee, chemical additions,
prechlorination, ozonation, innovative structural design or other similar
techniques and methods, as may be required.
(d) New pumping stations shall be enclosed
with a fence or otherwise designed with appropriate features that discourage
the entry of animals and unauthorized persons. An unobstructed sign made of
durable weather resistant material shall be posted at a location visible to the
public with a telephone number for a point of contact in case of
emergency.
(e) In areas with high
water tables, the pump station shall be designed to include measures to
withstand flotation forces when empty. The potential for damage or interruption
of operation because of flooding shall be considered by the permittee when
siting new pumping stations. The electrical and mechanical equipment shall be
protected from physical damage by the 100-year flood. The pumping station shall
be designed to remain fully operational and accessible during the 25-year
flood; lesser flood levels may be designed for, dependent on local conditions,
but in no case shall less than a 10-year flood be used. Design considerations
(water surface elevation, forces arising from water movement, etc.) shall be
based upon available information; where site-specific information is
unavailable, sound engineering practices shall be used in siting and design of
pump station facilities.
(f)
Branches of intersecting force mains shall be provided with appropriate valves
such that one branch may be shut down for maintenance and repair without
interrupting the flow of other branches. Stubouts on a force main, placed in
anticipation of future connections, shall be equipped with a valve to allow
such connections without interruption of service.
(g) Sewers and force mains shall be laid to
provide the minimum or greater horizontal separation distances from water mains
equal to the horizontal separation distances for water mains to sewers and
force mains established in subsection
62-555.314(1),
F.A.C. Sewers and force mains shall be laid at least three feet (outside to
outside) horizontally from any existing or proposed reclaimed water line
permitted under Part III or Part V of Chapter 62-610, F.A.C. Provided the
applicant demonstrates there is no reasonable alternative, the Department shall
approve smaller horizontal separation distances for sewers if one of the
following conditions is met:
1. The top of the
sewer is installed at least 18 inches below the bottom of the potable water
line or reclaimed water line.
2.
The sewer is encased in watertight carrier pipe or concrete.
3. Both the sewer and the water main are
constructed of slip-on or mechanical joint pipe complying with public water
supply design standards and pressure tested to 150 psi to assure
watertightness.
4. The applicant
provides documentation accompanying the permit application showing that another
alternative will result in an equivalent level of reliability and public health
protection.
(h) Sewers
and force mains shall cross under water mains, unless there is no alternative.
Sewers and force mains shall be laid to provide the minimum vertical separation
distances from water mains equal to the vertical separation distances for water
mains to sewers and force mains established in subsection
62-555.314(2),
F.A.C. Sewers and force mains crossing reclaimed water lines permitted under
Part III or Part IV of Chapter 62-610, F.A.C., shall be laid to provide the
minimum vertical separation distances from water mains equal to the vertical
separation distances for water mains to sewers and force mains established in
subsection 62-555.314(2),
F.A.C. For sewer crossings, the crossing shall be arranged so that the sewer
pipe joints are equidistant and as far as possible from the water main joints.
Adequate structural support shall be provided for the sewer or force main to
maintain line and grade. For sewers, provided the applicant demonstrates there
is no reasonable alternative, the Department shall approve smaller vertical
separation distances if one of the following conditions is met:
1. The sewer is encased in a watertight
carrier pipe or concrete.
2. The
sewer is designed and constructed equal to water pipe and pressure tested to
150 psi to assure watertightness.
3. The applicant provides documentation
accompanying the permit application showing that another alternative will
result in an equivalent level of reliability and public health
protection.
(i) The
provisions of paragraphs
62-604.400(2)(g)
-(i), F.A.C., above are applicable to in-ground crossings. No vertical or
horizontal separation distances are required for above-ground
crossings.
(j) Special protection
shall be furnished for sewer lines crossing canals or other waterways subject
to maintenance dredging or where damage may occur from water craft anchorage so
as to minimize the potential for unintentional discharge of wastewater into
surface waters.
1. Subaqueous lines shall be
buried at least three feet below the design or actual bottom, whichever is
deeper, of a canal and other dredged waterway or the natural bottom of streams,
rivers, estuaries, bays, and other natural water bodies. Designs with less than
the three-foot minimum cover shall be protected by a concrete cap, sleeve, or
some other properly engineered device to insure adequate protection of the
line; subaqueous crossings shall be designed to lie on the bottom of waterways
only when the engineering report provides reasonable assurance that, because of
the depth of the water or other circumstances, the pipeline shall be adequately
protected from damage from natural occurrences or mankind's
activities.
2. Subaqueous crossings
shall be clearly marked by permanent warning signs placed on the banks of
canals, streams, and rivers clearly identifying the nature and location
(including depths below design or natural bottom) of the crossings. Crossings
of lakes, bays and other large bodies of water shall be similarly identified at
the shore and, with suitably fixed signs, in any area where anchoring may
normally be expected. Signs shall have characteristics compatible with
surrounding land use, while serving the intended purpose.
3. Aerial crossings, whether hung from
existing structures, self-supporting, or supported by utility bridges or
structures, shall be designed to maintain existing or required navigational
capabilities within the waterway and to reserve the riparian rights of adjacent
property owners.
4. Provisions for
testing the integrity of underwater lines shall be made, and special pipe
material suitable for underwater construction shall be used.
5. Lines shall be designed to incorporate
valves or other flow regulating devices (which may include pump stations) on
the shoreline or at such distances from the shoreline as may be approved by the
Department to prevent discharge in the event the line is
damaged.
(3)
The manuals referenced in paragraphs
62-604.300(2)(b), (c) and
(j), F.A.C., provide guidance for the design
and construction of alternative collection/transmission systems in Florida. A
central management entity, be it public or private, shall be responsible for
operation and maintenance of the on-lot facilities associated with alternative
collection/transmission systems.
Notes
Rulemaking Authority 403.051, 403.061, 403.087 FS. Law Implemented 403.021, 403.061, 403.062, 403.085, 403.086, 403.087, 403.088 FS.
New 11-27-89, Amended 6-4-92, Formerly 17-604.400, Amended 12-26-96, 11-6-03, 10-4-21.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.