Fla. Admin. Code Ann. R. 62-762.501 - System Requirements for Shop Fabricated Storage Tanks
(1) General requirements.
(a) Wellhead Protection. Persons are advised
that Chapter 62-521, F.A.C., contains restrictions regarding the location of
storage tank systems within 500 feet of a potable water well.
(b) Secondary containment .
1. The materials used for secondary
containment shall be:
a. Impervious to the
regulated substances being stored in the storage tank system and able to
withstand deterioration from external environmental conditions,
b. Non-corrosive or of corrosion-protected
materials; and,
c. Of sufficient
thickness and strength to withstand hydrostatic forces at maximum capacity to
prevent a discharge.
2.
Synthetic liners, unless previously approved by the Department, shall be
designed and tested in accordance with Test Methods, Test Properties
and Testing Frequency for High Density Polyethylene (HDPE) Smooth and Textured
Geomembranessm, GRI - GM13 Standard
Specification, Rev. 16, March 2021, hereby adopted and incorporated by
reference and, as a copyright protected document, is available for inspection
at the Department of Environmental Protection or the Department of State
address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at Geosynthetic Institute, 475 Kedron Avenue,
Folsom, Pennsylvania 19033-1208, (610)522-8440, or at
http://www.geosynthetic-institute.org/,
and be registered with the Department in accordance with subsection
62-762.851(2),
F.A.C. Liners shall not be constructed or consist of naturally occurring
in-situ soils.
3. Secondary
containment constructed of concrete shall be:
a. Designed and constructed in accordance
with Control of Cracking in Concrete Structures (Reapproved
2008), ACI 224R-01, (Reapproved 2008), incorporated by reference in paragraph
62-762.201(33)(b),
F.A.C., and Design Considerations for Environmental Engineering
Concrete Structures, ACI 350.4R-04, 2004 Edition, American Concrete
Institute (ACI), incorporated by reference in paragraph
62-762.201(33)(b),
F.A.C., or
b. Lined in accordance
with SSPC-TU 2/NACE 6G197, February 1997, incorporated by reference in
subparagraph 62-762.201(33)(b)
2., F.A.C., unless previously lined in accordance with Coatings and
Linings over Concrete for Chemical Immersion and Containment Service,
NACE Standard SP0892-2007 (formerly RP0892), 2007 Edition, hereby adopted and
incorporated by reference and, as a copyright protected document, is available
for inspection at the Department of Environmental Protection or the Department
of State address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at AMPP, 15835 Park Ten Place, Houston, Texas
77084, or at https://www.ampp.org/home, and be
registered with the Department in accordance with subsection
62-762.851(2),
F.A.C., or
c. Designed, evaluated,
and certified by a professional engineer licensed in the State of Florida that
the concrete secondary containment system meets the general construction
requirements specified in subparagraph
62-762.501(1)(b)
1., F.A.C.
4. Secondary
Containment constructed with other materials, including clay liner materials
shall be impervious and registered in accordance with subsection
62-762.851(2),
F.A.C.
5. For cathodically
protected tanks and integral piping , secondary containment systems shall not
interfere with the operation of the cathodic protection system.
6. For VCI protected tanks, the secondary
containment system shall provide containment for the vapor corrosion
inhibitors.
7. Secondary
containment systems shall be designed and installed to direct any release to a
monitoring point or points.
8. If
factory-made single-walled spill containment systems or single-walled sumps are
installed on the system, a containment integrity test shall be performed before
the component is placed into service in accordance with the manufacturer's
testing requirements. For system components without manufacturer containment
testing specifications, PEI/RP1200-19, 2019 Edition shall be used.
PEI/RP1200-19 is the Recommended Practices for the Testing and
Verification of Spill, Overfill , Leak Detection and Secondary Containment
Equipment at UST Facilities, hereby adopted and incorporated by
reference and, as a copyright protected document, is available for inspection
at the Department of Environmental Protection or the Department of State
address provided in subsection
62-762.211(1),
F.A.C., or the publisher at PEI, Post Office Box 2380, Tulsa, Oklahoma
74101-2380, (918)494-9696, or the publisher's website at
www.pei.org/. For field-fabricated components
the tests shall be at least for 24 hours in accordance with manufacturer's
requirements.
9. An interstitial
integrity test shall be performed on each double-walled or double-bottomed
storage tank with a closed interstice after it is delivered and placed at its
final location at the facility, and before the storage tank is placed into
service. This test shall be performed in accordance with the manufacturer's
testing specifications. For storage tanks without manufacturer interstitial
integrity testing requirements, PEI/RP200-19, 2019 Edition, shall be used.
PEI/RP200-19 is the Recommended Practices for Installation of
Aboveground Storage Systems for Motor Vehicle Fueling, hereby adopted
and incorporated by reference and, as a copyright protected document, is
available for inspection at the Department of Environmental Protection or the
Department of State address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at PEI, Post Office Box 2380, Tulsa, Oklahoma
74101-2380, (918)494-9696, or at www.pei.org/. For closed top dike double-walled UL
142 storage tanks with an open interstice not capable of being pressurized,
manufacturer's inspection instructions in accordance with the UL 142 storage
tank 's equipment registration pursuant to subsection
62-762.851(2),
F.A.C., must be performed for structural or other damage to the storage tank
after it is delivered and placed at its final location at the facility, and
before the storage tank is placed into service. If manufacturer instructions
are unavailable, a visual inspection must be performed for structural or other
damage to the storage tank after it is delivered and placed at its final
location at the facility, and before the storage tank is placed into
service.
10. Before integral piping
is placed into service, an interstitial integrity test shall be performed on
double-walled small diameter integral piping in contact with the soil , or that
transports regulated substances over surface waters of the state, in accordance
with Recommended Practices for Installation of Underground Liquid
Storage Systems, PEI/RP100-20, 2020 Edition, hereby adopted and
incorporated by reference and, as a copyright protected document, is available
for inspection at the Department of Environmental Protection or the Department
of State address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at PEI, Post Office Box 2380, Tulsa, Oklahoma
74101-2380, (918)494-9696, or at www.pei.org/, and PEI/RP1200-19, 2019
Edition.
11. If double-walled spill
containment systems are installed, an interstitial integrity test shall be
performed in accordance with the manufacturer's testing requirements. For
system components without manufacturer interstitial integrity testing
specifications, PEI/RP1200-19, 2019 Edition, shall be used before the spill
containment system is placed into service.
(c) Cathodic protection .
1. Test stations. Cathodic protection systems
shall be designed, constructed, and installed with test stations in accordance
with NACE standards contained in paragraph
62-762.211(2)(g),
F.A.C., or another method of monitoring to allow for a determination of current
operating status. Cathodic protection test stations shall provide direct access
to the soil electrolyte in close proximity to each cathodically protected
structure for placement of reference electrodes, and monitoring wires that
connect directly to cathodically protected structures. Facilities where direct
access to soil in close proximity to cathodically protected structures is
present, and where electrical connections to cathodically protected structures
can be conveniently accomplished, need not have separate dedicated cathodic
protection test stations.
2. The
cathodic protection system shall be operated and maintained in accordance with
subsection 62-762.701(2),
F.A.C.
3. Any field-installed
cathodic protection system shall be designed and installed by or under the
direction of a Corrosion Professional .
(d) Corrosion Protection with Vapor Corrosion
Inhibitors (VCI)
1. Testing locations for
vapor corrosion inhibitors. Vapor Corrosion Inhibitor technologies registered
with the Department in accordance with subsection
62-762.851(2),
F.A.C., provide an alternative to cathodic protection for protection of metal
surfaces within the secondary containment . Vapor corrosion inhibitors (VCI)
effectiveness shall be established by the use of electrical resistance probes
located in testing locations as recommended by a Corrosion Professional to
monitor corrosion rates.
2. Any
field-installed VCI protection system shall be designed and installed by or
under the direction of a Corrosion Professional and the VCI manufacturer's
certified installer. The VCI protection system shall be operated and maintained
in accordance with subsection
62-762.701(3),
F.A.C.
(e) Compatibility.
The primary and secondary walls of storage tank systems shall be made of, or
internally lined with, materials that are compatible with the regulated
substance stored in the storage tank systems and with substances or conditions
present in the environment. All storage tank systems containing blends of
ethanol, biodiesel, or other biofuels and additives shall be compatible with
regulated substances stored in the storage tank systems.
(f) Exterior coatings. Exterior portions of
tanks and integral piping shall be coated or otherwise protected from external
corrosion. The coating shall be designed and applied to resist corrosion,
deterioration, and degradation of the exterior wall.
(g) All components of a storage tank system
shall be installed in accordance with the manufacturer's
instructions.
(h) All storage tank
systems shall be installed in accordance with the applicable provisions of:
1.
Flammable and Combustible Liquids
Code, Storage of Liquids in Tanks - Aboveground Storage Tank s, Chapter
22 of NFPA 30, 2021 Edition, incorporated by reference in paragraph
62-762.201(36)(a),
F.A.C.,
2.
Code forMotor
Fuel Dispensing Facilities and Repair Garages, NFPA 30A, 2021 Edition,
hereby adopted and incorporated by reference and, as a copyright protected
document, is available for inspection at the Department of Environmental
Protection or the Department of State address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at NFPA, 1 Batterymarch Park, Quincy,
Massachusetts 02169, (617)770-3000, or at www.nfpa.org/,
3.
Process Piping , ASME
B31.3, 2020 Edition, hereby adopted and incorporated by reference and, as a
copyright protected document, is available for inspection at the Department of
Environmental Protection or the Department of State address provided in
subsection 62-762.211(1),
F.A.C., or from the publisher at ASME International, 22 Law Drive, Box 2900,
Fairfield, New Jersey 07007-2900, (800)843-2763, or the publisher's website at
http://www.asme.org/;
4.
PEI/RP200-19, 2019 Edition, incorporated by reference in subparagraph
62-762.501(1)(b)
9., F.A.C.; and,
5. Recommended
Practices for the Design and Installation of Fueling Systems for Emergency
Generators, Stationary Diesel Engines and Oil Burner Systems, PEI/RP1400-21,
2021 Edition, hereby adopted and incorporated by reference and, as a copyright
protected document, is available for inspection at the Department of
Environmental Protection or the Department of State address provided in
subsection 62-762.211(1),
F.A.C., or from the publisher at PEI, Post Office Box 2380, Tulsa, Oklahoma
74101-2380, (918)494-9696, or at www.pei.org/.
(i) Whenever integral piping in contact with
the soil is installed or relocated after January 11, 2017, a survey drawing of
the underground integral piping , signed and sealed by a professional land
surveyor or professional engineer licensed in the State of Florida, shall be
completed and maintained as a record in accordance with Rule
62-762.711,
F.A.C.
(2) Storage tank
installation.
(a) In addition to the
requirements of paragraph
62-762.501(1)(h),
F.A.C., storage tank systems shall be installed according to the applicable
provisions of Installation Instructions for Shop Fabricated Aboveground
Storage Tanks for Flammable, Combustible Liquids, STI R912, Revised
November 2015, hereby adopted and incorporated by reference, and available at
the Department address listed in subsection
62-762.211(1),
F.A.C., or from the publisher at STI, 944 Donata Court, Lake Zurich, IL 60047,
(847)438-8265, or at https://www.steeltank.com/.
(b) Storage tank construction requirements.
1. Storage tanks shall be constructed in
accordance with one of the following requirements hereby adopted and
incorporated by reference and, and a copyright protected document, is available
for inspection from the Department of Environmental Protection or the
Department of State address provided in subsection
62-762.211(1),
F.A.C.:
a.
Standard for Steel
Aboveground Tanks for Flammable and Combustible Liquids, UL 142,
January 2021, 10th Edition. To obtain this reference from the publisher, see
paragraph 62-762.211(2)(m),
F.A.C.,
b.
Welded Tanks for
Oil Storage , API Std 650, 13th Edition, March 2020, incorporated by
reference in subsection
62-762.201(67),
F.A.C. To obtain this reference from the publisher, see paragraph
62-762.211(2)(b),
F.A.C.,
c.
Specification
for Fiberglass Reinforced Plastic Tank s, API Spec 12P, 4th Edition,
Feburary 2016. To obtain this reference from the publisher, see paragraph
62-762.211(2)(b),
F.A.C.,
d.
Standard for
Aboveground Tanks with Integral Secondary Containment , STI
F921®, Revised June 2016. To obtain this
reference from the publisher, see paragraph
62-762.211(2)(l),
F.A.C.,
e.
Standard for
Protected Aboveground Tanks for Flammable and Combustible Liquids, UL
2085, December 1997, Revised September 2010, 2nd Edition. To obtain this
reference from the publisher, see paragraph
62-762.211(2)(m),
F.A.C.,
f.
Steel Tank
Institute Standard for Fire Tested Tanks
Flameshield®, STI F001, April 2017. To
obtain this reference from the publisher, see paragraph
62-762.211(2)(l),
F.A.C.,
g.
Fireguard:
Specification for Fireguard Protected Aboveground Storage Tank s, STI
F941, June 2016. To obtain this reference from the publisher, see paragraph
62-762.211(2)(l),
F.A.C.,
h.
Standard for
Aboveground Tanks Used as a Generator Base Tank , STI F011, November
2021. To obtain this reference from the publisher, see paragraph
62-762.211(2)(l),
F.A.C., or
i.
Recommended
Practices for the Design and Installation of Fueling Systems for Emergency
Generators, Stationary Diesel Engines and Oil Burner Systems,
PEI/RP1400-14, 2014 Edition, to obtain this reference from the publisher, see
paragraph 62-762.211(2)(j),
F.A.C.
2. Storage tanks
that meet the above performance requirements, that are constructed of
equivalent material, or have an equivalent design shall be registered with the
Department in accordance with subsection
62-762.851(2),
F.A.C.
(c) Cathodic and
corrosion protection . Steel tanks in contact with the soil shall have a
cathodic or corrosion protection system meeting the following requirements:
1. The cathodic protection system shall be
designed, constructed, and installed in accordance with
Cathodic
Protection of Aboveground Petroleum Storage Tank s, API RP 651, 4th
Edition, September 2014, hereby adopted and incorporated by reference, and
available at the Department address listed in subsection
62-762.211(1),
F.A.C., or from the publisher at API, 1220 L Street, N.W., Washington, D.C.
20005, (202)682-8000, or at http://www.api.org/; and Application
of Cathodic Protection to Control External Corrosion of Carbon Steel On-Grade
Storage Tank Bottoms (formerly External Cathodic Protection of On-Grade Carbon
Steel Storage Tank Bottoms), NACE Standard SP0193-2016-SG (formerly
RP0193-2001), 2016 Edition, hereby adopted and incorporated by reference, and
available at the Department address listed in subsection
62-762.211(1),
F.A.C., or from the publisher at NACE International, 1440 South Creek Drive,
Houston, Texas 77084-4906, (800)797-6223, or at http://www.nace.org/,
2. A field-installed cathodic protection
system shall be designed and installed by or under the direction of a Corrosion
Professional ,
3. The cathodic
protection system shall be designed and installed with at least one test
station in accordance with subparagraph
62-762.501(1)(c)
1., F.A.C., or a method of monitoring to allow for a determination of current
operating status; and,
4. The
cathodic protection system shall be operated and maintained in accordance with
subsection 62-762.701(2),
F.A.C.
5. Storage tank systems
using corrosion protection systems with vapor corrosion inhibitors that are
registered in accordance with subsection
62-762.851(2),
F.A.C., shall be designed and installed under the direction of a Corrosion
Professional , and be installed with at least one electrical resistance probe
test location, or a method of monitoring to allow for a determination of the
corrosion rate on the underside of the tank floor, or other interstitial or
metallic surface. The VCI system shall be designed and installed in accordance
with the requirements specified in subsection
62-762.701(3),
F.A.C.
(d) Secondary
containment .
1. All storage tanks, including
those that contain used oil, shall have secondary containment .
2. Storage tanks containing high viscosity
products are exempt from the requirements for secondary containment .
3. Dike field areas with secondary
containment shall:
a. Conform to the
requirements of Chapter 22 of NFPA 30, 2021 Edition, Flammable and
Combustible Liquids Code, Storage of Liquids in Tanks -
Aboveground Storage Tank s,
b. Contain a minimum of 110 percent of the
maximum capacity of the storage tank located within the dike field area , or of
the largest single-walled storage tank located within a dike field area
containing more than one storage tank . For dike field areas containing more
than one storage tank , capacity calculations shall be made after deducting the
volume of the storage tanks, other than the largest storage tank , below the
height of the dike,
c. Be
constructed, if not roofed or otherwise protected from the accumulation of
rainfall, with either:
(I) A siphon to remove
accumulated liquids or a drainage system that allows the continuous discharge
of water but functions to automatically stop the flow of all liquids upon the
presence of regulated substances, or
(II) A gravity drain pipe which has a
manually controlled valve, normally closed, or a manually controlled pump.
Gravity drain pipes shall be designed and constructed to prevent a discharge in
the event of fire; and,
d. Have all integral piping and other
penetrations that pass through the secondary containment of dike field areas
sealed around the penetration with an impervious compatible material to prevent
the discharge of regulated substances.
(e) Overfill protection .
1. Owners or operators shall ensure that the
volume available in the storage tank is greater than the volume of regulated
substances to be transferred to the storage tank before the transfer is made
and shall ensure that any transfer is repeatedly monitored to prevent
overfilling and spilling, and no storage tank shall be filled beyond 95 percent
capacity.
2. All storage tanks
shall be equipped with at least one of the following overfill protection
devices or containment method:
a. A level
gauge or other measuring device that accurately shows the level of regulated
substances in the storage tank , and is visible to the transfer operator,
b. A high level (at 90 percent
tank capacity) warning alarm that is either visible, audible, or both to the
transfer operator and the transfer operator is to ensure the tank is not filled
beyond 95 percent capacity,
c. A
high level (at 95 percent tank capacity) liquid flow cutoff controller,
or
d. An impervious dike field area
designed to contain overfills.
3. All overfill protection devices shall be
tested for operability at installation and test results shall be maintained and
available for inspection by the Department or county in accordance with Rule
62-762.711, F.A.C.
4. Effective October 17, 2019, owners and
operators shall:
a. Designate a primary
overfill protection device used to meet the requirements in subparagraph
62-762.501(2)(e)
2., F.A.C., and any additional overfill devices shall not interfere with the
designated primary device; and,
b.
Ensure the designated primary overfill protection device is registered pursuant
to registration of storage tank system equipment and release detection systems
and methods, subsection
62-762.851(2),
F.A.C.
5. An annual
operability test shall be performed on the designated primary overfill
protection device used to meet the Department's overfill protection requirement
at intervals not exceeding 12 months to ensure proper operation and test
results shall be maintained and available for inspection by the Department or
county in accordance with Rule
62-762.711, F.A.C. An annual
operability test will be deemed timely if performed within the same calendar
month in which the test is due.
6.
Storage tanks with capacities of 15, 000 gallons or less that do not receive
delivery by a mated (joined) tight fill adaptor connection of the delivery hose
to the tank riser may use calibrated stick measurements for overfill
protection , and are not required to be equipped with one of the devices
specified in subparagraph
62-762.501(2)(e)
2., F.A.C., provided that an inches to gallons chart is posted at the tank fill
areas or readily available to the delivery driver. Such tanks shall not be
filled beyond 95 percent capacity.
7. Used oil tanks that receive less than 25
gallons at one time are not required to have overfill
protection .
(f) Spill
containment systems.
1. Storage tanks shall
be installed with a spill containment system at each storage tank fill
connection, except within dike field areas with secondary containment . The
spill containment system shall meet the requirements of paragraph
62-762.501(1)(b),
F.A.C., and be registered in accordance with subsection
62-762.851(2),
F.A.C.
2. Fillbox covers.
a. Effective June 25, 2024, regardless of the
date of installation of the storage tank system , fillbox covers shall be marked
or the fill connection tagged and facility signage shall be prominently
displayed in accordance with the following document, hereby adopted and
incorporated by reference: Using the API Color-Symbol System to
Identify Equipment, Vehicles, and Transfer Points for Petroleum Fuels and
Related Products at Dispensing and Storage Facilities and Distribution
Terminals, API Recommended Practice 1637, 4th Edition, April 2020. API
1637 is a copyright protected document and is available for inspection at the
Department of Environmental Protection or the Department of State address
provided in subsection
62-762.211(1),
F.A.C., or the American Petroleum Institute information provided in paragraph
62-762.211(2)(b),
F.A.C.
b. For storage tank systems
storing aviation fuel, regardless of the date of installation of the storage
tank system , fillbox covers shall be marked or the fill connection tagged and
facility signage shall be prominently displayed in accordance with the
following document, hereby adopted and incorporated by reference:
Identification Markings for Dedicated Aviation Fuel Manufacturing and
Distribution Facilities, Airport Storage and Mobile Fuelling
Equipment, EI 1542, 9th Edition, July 2012. EI 1542 is a copyright
protected document and is available for inspection at the of Environmental
Protection or the Department of State address provided in subsection
62-762.211(1),
F.A.C., or the Energy Institute information provided in paragraph
62-762.211(2)(d),
F.A.C.; or
c. An equivalent method
may also be approved by the Department using an alternative procedure in
accordance with subsection
62-762.851(1),
F.A.C.
3. Spill
containment systems, including double-walled spill containment systems, shall
be installed to allow for release detection in accordance with Rule
62-762.601,
F.A.C.
(g) Dispensers and
dispenser sumps.
1. The dispenser used for
transferring fuels from storage tanks to vehicles or portable containers shall
be installed and maintained in accordance with the provisions of NFPA 30, 2021
Edition, incorporated by reference in paragraph
62-762.201(36)(a),
F.A.C.; and Chapter 6, Fuel Dispensing Systems; Chapter 9,
Operational Requirements; and Chapter 11, Marine
Fueling of NFPA 30A Code for Motor Fuel Dispensing Facilities
and Repair Garages, 2021 Edition, incorporated by reference in
subparagraph 62-762.501(1)(h)
2., F.A.C.
2. Dispensers shall be
installed with a dispenser sump , except those within an impervious dike field
area with secondary containment , meeting the performance requirements of
paragraph 62-762.501(1)(b),
F.A.C., and registered in accordance with subsection
62-762.851(2),
F.A.C. The dispenser sump shall extend beneath the union of the integral piping
and the dispenser , including the shear valve, if applicable. Dispensers mounted
directly upon the storage tank or that are otherwise associated with storage
tank systems that do not have underground integral piping are exempt from this
requirement unless the dispensers are located over the surface waters of the
state.
3. Dispenser sumps shall be
installed to allow for release detection in accordance with Rule
62-762.601, F.A.C. The dispenser
sump shall be capable of containing a release for the entire area beneath the
dispenser .
(h) Piping
sumps.
1. Piping sumps shall meet the
performance requirements of paragraph
62-762.501(1)(b),
F.A.C., and be registered in accordance with subsection
62-762.851(2),
F.A.C. The piping sumps shall be designed, constructed, and installed to
minimize water entering the sump .
2. Piping sumps shall be installed to allow
for release detection in accordance with Rule
62-762.601,
F.A.C.
(i) Hydrant sumps .
Underground hydrant sumps shall be installed to prevent the discharge of
regulated substances during fueling of aircraft, vessels, or at any other time
the hydrant system is in use, and be registered in accordance with subsection
62-762.851(2),
F.A.C. Any such equipment shall be sealed to and around the hydrant piping with
an impervious , compatible material.
(j) Relocation of storage tanks. Storage
tanks that have been removed and reinstalled at a different property shall be
re-registered with the Department in accordance with subsection 62-762, 401(1),
F.A.C. They shall be reinstalled in accordance with manufacturer's
specifications and inspected in accordance with STI SP001, January 2018,
incorporated by reference in subsection
62-762.411(3),
F.A.C., and with the requirements in Rule
62-762.501,
F.A.C.
(3) Small diameter
integral piping .
(a) Installation.
1. All integral piping installed after
January 11, 2017, shall be installed in accordance with the manufacturer's
instructions, if applicable, and according to the applicable provisions of
PEI/RP200-19, 2019 Edition, incorporated by reference in subparagraph
62-762.501(1)(b)
9., F.A.C.; Chapter 27 of NFPA 30, 2021 Edition, Flammable and
Combustible Liquids Code,
Piping Systems,
incorporated by reference in paragraph
62-762.201(36)(a),
F.A.C.; NFPA 30A, 2021 Edition, incorporated by reference in subparagraph
62-762.501(1)(h)
2., F.A.C.; and Pipeline Transportation Systems for Liquids and
Slurries, ASME B31.4, 2019 Edition, hereby adopted and incorporated by
reference and, as a copyright protected document, is available for inspection
at the Department of Environmental Protection or the Department of State
address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at ASME International, 22 Law Drive, Box 2900,
Fairfield, New Jersey 07007-2900, (800)843-2763, or the publisher's website at
http://www.asme.org/.
2. An
interstitial integrity test shall be performed on double-walled integral piping
that is in contact with the soil , or that transports regulated substances over
surface waters of the state in accordance with PEI/RP100-20, 2020 Edition,
incorporated by reference in subparagraph
62-762.501(1)(b)
10., F.A.C., and PEI/RP1200-19, 2019 Edition, incorporated by reference by
subparagraph 62-762.501(1)(b)
8., F.A.C., before the integral piping is placed into service.
3. All new integral piping that is not in
contact with the soil , shall meet the construction requirements in paragraphs
62-762.501(3)(a) through
(c), F.A.C., and shall be UV rated if exposed
to sunlight if made of non-metallic materials.
4. New double-walled integral piping that is
in contact with the soil shall be installed with a slope to a low point
monitoring system. Double-walled integral piping utilizing hydrostatic,
pressure or vacuum monitoring are not subject to this requirement.
5. All new pressurized small diameter
integral piping that is in contact with the soil must be installed with line
leak detectors meeting the requirements of paragraph
62-762.601(4)(b),
F.A.C. The line leak detectors must be tested annually, at intervals not
exceeding 12 months in accordance with paragraph
62-762.601(1)(b),
F.A.C., and be installed in accordance with manufacturer's instructions. For
line leak detectors without manufacturer's instructions, the installation must
be in accordance with Section 7 of PEI/RP200-19, Recommended Practices
for Installation of Aboveground Storage Systems for Motor Vehicle
Fueling, Pumps and Valves, 2019 Edition, incorporated
by reference in subparagraph
62-762.501(1)(b)
9., F.A.C.
6. All pressurized small
diameter integral piping installed prior to January 11, 2017, that is in
contact with the soil must be installed with line leak detectors meeting the
requirements of paragraph
62-762.601(4)(b),
F.A.C., by January 11, 2018. The line leak detectors must be tested annually at
intervals not exceeding 12 months in accordance with paragraph
62-762.601(1)(b),
F.A.C., and be installed in accordance with manufacturer's instructions. The
annual test will be deemed timely if performed within the same calendar month
in which the test is due. For line leak detectors without manufacturer's
instructions, the installation must be in accordance with Section 7 of
PEI/RP200-19, 2019 Edition. Line leak detectors are not required for piping
that is not in contact with the soil .
(b) Secondary containment .
1. All small diameter integral piping ,
including remote fill piping , that is in contact with the soil or that
transports regulated substances over surface waters of the state, including
those that contain used oil, shall have secondary containment .
2. Small diameter integral piping containing
high viscosity products are exempt from the requirements for secondary
containment .
3. Single-walled
integral piping that is in contact with the soil , and is not exempt pursuant to
subparagraph 62-762.501(3)(b)
2., F.A.C., shall be immediately and permanently closed in accordance with
subsection 62-762.801(2),
F.A.C.
(c) Construction .
1. Fiberglass reinforced plastic piping ,
semi-rigid non-metallic, or other non-rigid piping installed in contact with
the soil shall be installed in accordance with Non-metallic Underground
Piping for Flammable Liquids, UL 971, May 2021, 2nd Edition, hereby
adopted and incorporated by reference and, as a copyright protected document,
is available for inspection at the Department of Environmental Protection or
the Department of State address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at UL, 333 Pfingsten Road, Northbrook, Illinois
60062-2096, (847)272-8800, or at www.ul.com/,
or certified by a Nationally Recognized Testing Laboratory that these
requirements are met, and registered in accordance with subsection
62-762.851(2),
F.A.C.
2. Rigid metallic integral
piping shall be constructed in accordance with ASME B31.3, 2020 Edition,
incorporated by reference in subparagraph
62-762.501(1)(h)
3., F.A.C., or PEI/RP200-19, 2019 Edition, incorporated by reference in
subparagraph 62-762.501(1)(b)
9., F.A.C. In addition, steel integral piping in contact with the soil shall be
cathodically protected in accordance with the following documents:
Cathodic Protection of Underground Petroleum Storage Tanks and Piping
Systems, API RP 1632, (R2010), 3rd Edition, May 1996, hereby adopted
and incorporated by reference and, as a copyright protected document, is
available for inspection at the Department of Environmental Protection or the
Department of State address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at API, 1220 L Street, N.W., Washington, DC
20005, (202)682-8000, or at http://www.api.org/; Control of
External Corrosion on Underground or Submerged Metallic Piping
Systems, NACE Standard SP0169-2013 (formerly RP0169), 2013 Edition,
hereby adopted and incorporated by reference and, as a copyright protected
document, is available for inspection at the Department of Environmental
Protection or the Department of State address provided in subsection
62-762.211(1),
F.A.C., or from the publisher at AMPP, 15835 Park Ten Place, Houston, Texas
77084, (800)797-6223, or at https://www.ampp.org/home; and
Recommended Practice for Corrosion Protection of Underground Piping
Networks Associated with Liquid Storage and Dispensing Systems, STI
R892, Revised January 2006, hereby adopted and incorporated by and, as a
copyright protected document, is available for inspection at the Department of
Environmental Protection or the Department of State address provided in
subsection 62-762.211(1),
F.A.C., or from the publisher at STI, 944 Donata Court, Lake Zurich, IL 60047,
(847)438-8265, or at https://www.steeltank.com/.
3. Metallic double-walled integral piping
constructed of nonferrous materials such as copper shall be constructed in
accordance with the requirements in Chapter 27 of NFPA 30, 2021 Edition,
incorporated by reference in paragraph
62-762.201(36)(a),
F.A.C.
4. Integral double-walled
piping constructed of other materials, design, or corrosion protection shall be
registered with the Department in accordance with subsection
62-762.851(2),
F.A.C.
5. Small diameter integral
piping using corrosion protection systems with vapor corrosion inhibitors that
are registered in accordance with subsection
62-762.851(2),
F.A.C., shall be designed and installed under the direction of a Corrosion
Professional , and shall be installed with at least one electrical resistance
probe or a method of monitoring to allow for a determination of the corrosion
rate within the piping interstice . The VCI system shall be designed and
installed in accordance with the requirements specified in subsection
62-762.701(3),
F.A.C.
(d) Valves.
1. Shear valves. Pressurized small diameter
integral piping systems connected to dispensers shall be installed with shear
valves or emergency shutoff valves in accordance with Section 6.3 of NFPA 30A,
Code for Motor Fuel Dispensing Facilities and Repair Garages,
Requirements for Dispensing Devices, 2021 Edition. NFPA 30A is
incorporated by reference in subparagraph
62-762.501(1)(h)
2., F.A.C. These valves shall be designed to close automatically if a dispenser
is displaced from its normal position. The valves shall be rigidly anchored
independently of the dispenser . The valves shall be tested in accordance with
PEI/RP1200-19, 2019 Edition, incorporated by reference in subparagraph
62-762.501(1)(b)
8., F.A.C., at the time of installation by a certified contractor to confirm
that the automatic closing function of the valve operates properly, and that
the valve is properly anchored.
2.
Isolation block valves. Any storage tank system , regardless of the date of
installation of the storage tank system , located at an elevation that produces
a gravity head on small diameter integral piping positioned below the product
level in the tank must be installed and maintained with an isolation block
valve in accordance with Chapter 22.13 of NFPA 30, 2021 Edition,
Flammable and Combustible Liquids Code,
Tank Openings
Other Than Vents. NFPA 30 is incorporated by reference in paragraph
62-762.201(36)(a),
F.A.C.
3. Anti-siphon valves. For
storage tank systems that produce a gravity head on small diameter integral
piping positioned below the product level in the tank , anti-siphon valves shall
be installed and maintained in accordance with Section 7 of PEI/RP200-19, 2019
Edition, and Section 11.2 of NFPA 30A, Marine Fueling,
Storage, 2021 Edition. NFPA 30A is incorporated by reference in
subparagraph 62-762.501(1)(h)
2., F.A.C. For such storage tank systems installed prior to January 11, 2017,
anti-siphon valves shall be installed within one year of January 11, 2017.
Integral piping located within an impervious dike field area does not require
anti-siphon valves.
(4) Bulk product piping associated with shop
fabricated storage tanks shall meet the requirements of subsection
62-762.502(4),
F.A.C.
Notes
Rulemaking Authority 376.303 FS. Law Implemented 376.303 FS.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.