Fla. Admin. Code Ann. R. 62-762.601 - Release Detection Requirements for Shop Fabricated Storage Tanks
(1) General requirements.
(a) Storage tank systems shall have a method
or combination of methods of release detection that can detect a new release
from any portion of the storage tank system .
(b) Any storage tank system without a method,
or combination of methods, of release detection in accordance with this
section, shall immediately provide a method of release detection , or
immediately empty the storage tank system and place the affected system
out-of-service in accordance with subsection
62-762.801(1),
F.A.C.
(c) Any component of a
storage tank system with an interstice shall have a method of interstitial
monitoring which shall be conducted in accordance with this section.
Interstitial monitoring can be performed with vacuum, pressure, hydrostatic
(liquid-level sensing), sensors or probes, or visual release detection
methods.
(d) Except as otherwise
specified in this rule, the release detection method or combination of methods
used at a facility shall be performed at least once every calendar month, but
not exceeding 35 days, to determine if a release from the storage tank system
has occurred.
(e) Visual
inspections. At least once a month, but not exceeding 35 days, every component
of a storage tank system that contains, transfers, or stores, or is designed to
contain, transfer, or store regulated substances that can be inspected visually
shall be visually inspected and documented as to its condition pursuant to rule
62-762.711, F.A.C. Any visual
inspection of a storage tank system that reveals uncontrolled pitting
corrosion, structural damage, leakage, or other similar problems is considered
a positive response. The positive response shall be recorded as part of the
release detection records, and reported and investigated as an incident
pursuant to rule 62-762.431, F.A.C. Repairs shall
be made in accordance with rule
62-762.701, F.A.C. A monthly
visual inspection is not required for any system component using an electronic
release detection method; however, piping and dispenser sumps that use an
electronic release detection method must also be visually inspected every six
months and records kept of the visual inspection.
(f) Electronic and mechanical release
detection devices shall be:
1. Installed,
calibrated, operated, and maintained in accordance with the manufacturer's
instructions, and shall be designed and installed to provide service checks for
operability to ensure that the device is functioning in accordance with
subsection 62-762.701(4),
F.A.C.; and,
2. Registered in
accordance with subsection
62-762.851(2),
F.A.C., except that controllers or annunciators that are used to display leak
detection test results are not required to be registered.
(g) Electronic release detection devices
shall be inspected for proper operation at least once every calendar month, but
not exceeding 35 days. A record or summary of the alarm history, sensor status,
and testing results related to suspected releases shall be printed from any
electronic release detection device. If the release detection system is not
capable of printing records, a manual log shall be maintained of the alarm
history, sensor status, and testing results.
(h) Release detection shall be constructed
and installed so that groundwater, rainfall, or soil moisture will not render
the release detection method used inoperable.
(i) Storage tank systems containing high
viscosity product are exempt from all release detection requirements except for
visual inspections.
(2)
Storage tanks with secondary containment .
(a)
One or more of the following release detection methods shall be used:
1. Liquid level monitoring systems with
electronic hydrostatic sensors. These methods shall be able to detect incidents
by determining changes in liquid levels within the interstice and monitoring
reservoir, and to provide immediate electronic notification with an audible or
visual alarm to the owner or operator if liquid levels cannot be maintained.
Any alarm that indicates that liquid levels are not being maintained is
considered a positive response and shall be reported and investigated as an
incident pursuant to Rule
62-762.431, F.A.C.
2. Vacuum monitoring. This method shall be
able to detect incidents by determining changes in vacuum levels within the
interstice by continuous monitoring of vacuum levels and to provide immediate
electronic notification with an audible or visual alarm to the owner or
operator if vacuum levels can not be maintained. Any alarm that indicates that
vacuum levels are not being maintained is considered a positive response and
shall be reported and investigated as an incident pursuant to Rule
62-762.431, F.A.C.
3. Pressure monitoring. This method shall be
able to detect incidents by using an inert gas and determining changes in
pressure levels within the interstice by continuous monitoring of pressure
levels and to provide immediate electronic notification with an audible or
visual alarm to the owner or operator if pressure levels can not be maintained.
Any alarm that indicates that pressure levels are not being maintained is
considered a positive response and shall be reported and investigated as an
incident pursuant to Rule
62-762.431, F.A.C.
4. Electronic sensors in a normally dry
interstice . This method shall be able to detect the presence of liquid in the
interstice or monitoring low point and to provide immediate electronic
notification with an audible or visual alarm to the owner or operator if liquid
is detected. Any alarm that indicates the presence of liquid is considered a
positive response and shall be reported and investigated as an incident
pursuant to Rule 62-762.431, F.A.C.
5. Visually inspected liquid level monitoring
systems. This method shall be able to detect incidents by determining changes
in liquid levels within the interstice and monitoring resevoir. Any visual
observation that indicates that liquid levels are not being maintained is
considered a positive response and shall be reported and investigated as an
incident pursuant to Rule
62-762.431, F.A.C.
6. Visually inspected vacuum or pressure
monitoring with gauges. This method shall be able to detect incidents by
determining changes in vacuum or pressure levels within the interstice .
a. Pressure readings shall be able to detect
a 50 percent change from one month to the next, or any change in pressure
exceeding 50 percent of the initial level or of a pressure level that is
reestablished at the time of an incident investigation or annual testing of the
gauge, and for vacuum systems, any complete loss of vacuum or positive pressure
reading. Vacuum or pressure refreshment must be performed in accordance with
manufacturer's specifications and the system's equipment registration in
subsection 62-762.851(2),
F.A.C. Any change indicated above is considered a positive response and shall
be reported and investigated as an incident pursuant to Rule
62-762.431, F.A.C.
b. Liquid-filled gauges shall be calibrated
using the National Institute of Standards and Technology (NIST) traceable
standards, hereby adopted and incorporated by reference, prior to initial
operation. Information on NIST can be obtained from 100 Bureau Drive, Stop
1070, Gaithersburg, Maryland 20899-1070, (301)975-6478, or at
http://www.nist.gov/index.html.
The gauges shall be operational at all times.
7. Visual monitoring of normally dry
interstices. This method shall be able to detect the presence of liquid at a
low point of the interstice . Any presence of water, other than condensate, or
regulated substances in the interstice is considered a positive response. The
positive response shall be recorded as part of the release detection records
and reported and investigated as an incident pursuant to Rule
62-762.431, F.A.C.
8. Visual monitoring of dike fields. This
method shall be able to detect the presence of liquid at a low point in the
dike field. The accumulation of water or condensation in the low point of the
dike field shall not interfere with the ability to detect regulated substances.
Any release of regulated substance in the dike field is considered a positive
response and shall be reported and investigated as an incident pursuant to Rule
62-762.431,
F.A.C.
(3)
Storage tanks without secondary containment .
(a) Required release detection methods.
Storage tanks that are exempt from secondary containment shall have monthly
visual inspections performed in accordance with paragraph
62-762.601(1)(e),
F.A.C.
(b) Performance
Requirements. Visual inspections of storage tanks shall include an inspection
of the exterior of each tank , the integral piping , and any other storage tank
system components.
(4)
Small diameter integral piping with secondary containment .
(a) One or more of the applicable release
detection methods in subsection
62-762.601(2),
F.A.C., shall be used.
(b) In
addition, pressurized small diameter integral piping in contact with the soil
shall be equipped with a release detection system that can detect a leak within
one hour. One of the following methods shall be used:
1. Mechanical line leak detectors. Mechanical
line leak detectors shall be capable of detecting a discharge of 3.0 gallons
per hour (gph) with a probability of detection of 0.95, and a probability of
false alarm of 0.05 at an equivalent line pressure of 10 pounds per square inch
(psi) and restrict flow within one hour.
2. Electronic line leak detectors. Electronic
line leak detectors shall be capable of detecting a discharge of 3.0 gph with a
probability of detection of 0.95, and a probability of false alarm of 0.05 at
an equivalent line pressure of 10 psi and alert the operator by restricting or
shutting off the flow of regulated substances through piping when a leak is
detected.
3. Electronic
interstitial monitoring devices. Storage tank systems without line leak
detectors, shall have electronic interstitial monitoring devices that are
capable of detecting a release of 10 gallons within one hour and shutting off
the pump.
4. For emergency
generator storage tank systems that are monitored 24-hours per day, if the
release detection system detects leaks of 3.0 gph at 10 psi line pressure
within one hour, an audible or visual alarm will be triggered to alert the
on-site operator.
(5) A positive response is defined as any
instance where the release detection system has shut off power to the pump,
restricted the flow, or triggered an audible or visual alarm for pressurized
integral piping in contact with the soil . The positive response shall be
recorded as part of the release detection records and reported and investigated
as an incident pursuant to Rule
62-762.431, F.A.C.
(6) Bulk product piping and hydrant piping
with secondary containment associated with shop fabricated storage tank systems
shall meet the requirements of subsection
62-762.602(5),
F.A.C.
(7) Bulk product and hydrant
piping without secondary containment associated with shop fabricated storage
tank systems shall meet the requirements of subsection
62-762.602(6),
F.A.C.
(8) Annual operability
testing of release detection systems. All release detection devices shall be
tested annually at intervals not exceeding 12 months to ensure proper
operation. An annual operability test will be deemed timely if performed within
the same calendar month in which the test is due. The test must either simulate
an actual alarm condition or shall be conducted according to manufacturer's
specifications, and shall include, at a minimum, a determination of whether the
device operates as designed. Remote testing of the system can be performed by
the manufacturer if the remote test is included in the third-party
certification by a Nationally Recognized Testing Laboratory .
(9) Operability test results shall be
maintained and available for inspection by the Department or county in
accordance with Rule 62-762.711,
F.A.C.
Notes
Rulemaking Authority 376.303 FS. Law Implemented 376.303 FS.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.