Fla. Admin. Code Ann. R. 62-762.602 - Release Detection Requirements for Field Erected Storage Tank Systems
(1) General requirements.
(a) Storage tank systems shall have a method
or combination of methods of release detection that can detect a new release
from any portion of the storage tank system .
(b) Any storage tank system without a method,
or combination of methods, of release detection in accordance with this
section, shall immediately provide a method of release detection , or
immediately empty the storage tank system and place the affected system
out-of-service , or close the system in accordance with subsection
62-762.802(3),
F.A.C.
(c) Any component of a
storage tank system with an interstice shall have a method of interstitial
monitoring which shall be conducted in accordance with this section.
Interstitial monitoring can be performed with vacuum, pressure, hydrostatic
(liquid-level sensing), sensors or probes, or visual release detection
methods.
(d) Except as otherwise
specified in this Rule, the release detection method or combination of methods
used at a facility shall be performed at least once every calendar month, but
not exceeding 35 days, to determine if a release from the storage tank system
has occurred.
(e) Visual
inspections. At least once a month, but not exceeding 35 days, every component
of a storage tank system that contains, transfers, or stores, or is designed to
contain, transfer, or store regulated substances can be inspected visually
shall be visually inspected and documented as to its condition pursuant to Rule
62-762.711, F.A.C. Any visual
inspection of a storage tank system that reveals uncontrolled pitting
corrosion, structural damage, leakage, or other similar problems is considered
a positive response. The positive response shall be recorded as part of the
release detection records and reported and investigated as an incident pursuant
to rule 62-762.431, F.A.C. Repairs shall
be made in accordance with Rule
62-762.702, F.A.C. A visual
inspection is not required for any system component using an electronic release
detection method.
(f) Electronic
and mechanical release detection devices shall be:
1. Installed, calibrated, operated, and
maintained in accordance with the manufacturer's instructions, and shall be
designed and installed to provide service checks for operability to ensure that
the device is functioning in accordance with subsection
62-762.702(4),
F.A.C.; and,
2. Registered in
accordance with subsection
62-762.851(2),
F.A.C., except that controllers or annunciators that are used to display leak
detection test results are not required to be registered.
(g) Electronic release detection devices
shall be inspected for proper operation at least once every calendar month, but
not exceeding 35 days. A record or summary of the alarm history, sensor status,
and testing results related to suspected releases shall be printed from any
electronic release detection device. If the release detection system is not
capable of printing records, a manual log shall be maintained of the alarm
history, sensor status, and testing results.
(h) Release detection shall be constructed
and installed so that groundwater, rainfall, or soil moisture will not render
the release detection method used inoperable.
(i) Storage tank systems containing high
viscosity product are exempt from all release detection requirements except for
visual inspections.
(2)
Storage tanks with secondary containment .
(a)
One or more of the following release detection methods shall be used:
1. Liquid level monitoring systems with
electronic hydrostatic sensors. These methods shall be able to detect incidents
by determining changes in liquid levels within the interstice and monitoring
reservoir and to provide immediate electronic notification with an audible or
visual alarm to the owner or operator if liquid levels cannot be maintained.
Any alarm that indicates that liquid levels are not being maintained is
considered a positive response and shall be reported and investigated as an
incident pursuant to Rule
62-762.431, F.A.C.
2. Vacuum monitoring. This method shall be
able to detect incidents by determining changes in vacuum levels within the
interstice by continuous monitoring of vacuum levels and to provide immediate
electronic notification with an audible or visual alarm to the owner or
operator if vacuum levels can not be maintained. Any alarm that indicates that
vacuum levels are not being maintained is considered a positive response and
shall be reported and investigated as an incident pursuant to Rule
62-762.431, F.A.C.
3. Pressure monitoring. This method shall be
able to detect incidents by using an inert gas and determining changes in
pressure levels within the interstice by continuous monitoring of pressure
levels and to provide immediate electronic notification with an audible or
visual alarm to the owner or operator if pressure levels can not be maintained.
Any alarm that indicates that pressure levels are not being maintained is
considered a positive response and shall be reported and investigated as an
incident pursuant to Rule
62-762.431, F.A.C.
4. Electronic sensors in a normally dry
interstice . This method shall be able to detect the presence of liquid in the
interstice or monitoring low point and to provide immediate electronic
notification with an audible or visual alarm to the owner or operator if liquid
is detected. Any alarm that indicates the presence of liquid is considered a
positive response and shall be reported and investigated as an incident
pursuant to Rule 62-762.431, F.A.C.
5. Visually inspected liquid level monitoring
systems. This method shall be able to detect incidents by determining changes
in liquid levels within the interstice and monitoring resevoir. Any visual
observation that indicates that liquid levels are not being maintained is
considered a positive response and shall be reported and investigated as an
incident pursuant to Rule
62-762.431, F.A.C.
6. Visually inspected vacuum or pressure
monitoring with gauges. This method shall be able to detect incidents by
determining changes in vacuum or pressure levels within the interstice .
a. Pressure readings shall be able to detect
a 50 percent change from one month to the next, or any change in pressure
exceeding 50 percent of the initial level or of a pressure level that is
reestablished at the time of an incident investigation or annual testing of the
gauge, and for vacuum systems, any complete loss of vacuum or positive pressure
reading. Vacuum or pressure refreshment must be performed in accordance with
manufacturer's specifications and the system's equipment registration in
subsection 62-762.851(2),
F.A.C. Any change indicated above is considered a positive response and shall
be reported and investigated as an incident pursuant to Rule
62-762.431, F.A.C.
b. Liquid-filled gauges shall be calibrated
using NIST traceable standards prior to initial operation. The gauges shall be
operational at all times.
7. Visual monitoring of normally dry
interstices. This method shall be able to detect the presence of liquid at a
low point of the interstice . Any presence of water, other than condensate, or
regulated substances in the interstice is considered a positive response and
shall be reported and investigated as an incident pursuant to Rule
62-762.431, F.A.C.
8. Visual monitoring of dike fields. This
method shall be able to detect the presence of regulated substances at a low
point in the dike field. The accumulation of water or condensation in the low
point of the dike field shall not interfere with the ability to detect
regulated substances. Any release of regulated substances in the dike field is
considered a positive response and shall be reported and investigated as an
incident pursuant to Rule
62-762.431,
F.A.C.
(3)
Storage tanks without secondary containment .
(a) Required release detection methods.
1. Storage tanks that are exempt from
secondary containment shall have monthly visual inspections performed in
accordance with paragraph
62-762.602(1)(e),
F.A.C.
2. Storage tanks, except
those containing high viscosity product , shall have one of the following
methods of release detection :
a. Electronic
sensing equipment installed beneath the storage tank .
b. External monitoring using tracer or helium
testing systems registered in accordance with subsection
62-762.851(2),
F.A.C.
c. Another method registered
in accordance with subsection
62-762.851(2),
F.A.C.
(b)
Performance Requirements. Single-walled release detection systems shall be
designed and constructed to allow monitoring of the tank for the purpose of
discovering if an incident has occurred. Single-walled release detection
systems shall be constructed and installed so that groundwater, rainfall, or
soil moisture will not render the testing or sampling method inoperative.
1. Electronic sensing equipment placed
externally around storage tanks that involve the use of electronic sensors,
probes, or fiber-optic systems shall be tested at least annually at intervals
not exceeding 12 months to verify that they operate properly. Groundwater and
vapor monitoring wells using the placement of sensors or probes in vertical,
horizontal, or directionally-drilled wells shall be designed and installed in
accordance with the equipment registration for that system.
2. Visual inspections of field erected
storage tanks shall include an inspection of the exterior of each tank , the
integral piping system, the dike field area , and any other storage system
components.
(4)
Small diameter integral piping with secondary containment associated with field
erected storage tank systems shall meet the requirements of subsection
62-762.601(4),
F.A.C.
(5) Bulk product piping and
hydrant piping with secondary containment shall have one or more of the release
detection methods in subsection
62-762.602(2),
F.A.C.
(6) Bulk product and hydrant
piping without secondary containment . Single-walled bulk product and hydrant
piping in contact with the soil , except those containing high viscosity
product , shall have one or more of the following release detection methods:
(a) An annual line pressure test performed in
accordance with Recommended Practice for the Pressure Testing of Steel
Pipelines for the Transportation of Gas, Petroleum Gas, Hazardous Liquids,
Highly Volatile Liquids, or Carbon Dioxide, API RP 1110, (R2018), 6th
Edition, February 2013, hereby adopted and incorporated by reference and, as a
copyright protected document, is available for inspection at the Department of
Environmental Protection or the Department of State address provided in
subsection 62-762.211(1),
F.A.C., or from the publisher at API, 1220 L Street, N.W., Washington, DC
20005, (202)682-8000, or at http://www.api.org/, regardless of the date
of installation of the piping .
(b)
External monitoring shall be performed in accordance with the requirements of
paragraph 62-762.602(1)(d),
F.A.C., if designed to detect a discharge from any portion of the integral
piping . External release detection methods using fiber optic, acoustic, helium,
cable, and chemical marker release detection methods shall be performed
monthly, or annually at intervals not exceeding 12 months if approved by a
Nationally Recognized Testing Laboratory as having a 0.2 gallon per hour leak
rate detection capability.
(c)
Internal release detection methods, other than pressure testing, which are
registered in accordance with subsection
62-762.851(2),
F.A.C., shall be able to detect a leak of 0.2 gallon per hour with a
probability of detection of 0.95, and a probability of false alarm of 0.05.
Internal release detection systems meeting the 0.2 gallon per hour threshold
shall be performed annually at intervals not exceeding 12 months. Annual
pigging of bulk product piping can be performed as a method of internal release
detection instead of other methods specified above. The pigging must provide
ultrasonic thickness, magnetic flux, or other data that demonstrates that the
piping does not have holes or sources where product leaks from the
pipe .
(d) Bulk product and hydrant
piping not in contact with the soil shall be visually inspected in accordance
with paragraph 62-762.602(1)(e),
F.A.C., monthly but not exceeding 35 days.
(7) Annual operability testing of release
detection systems. All release detection devices shall be tested annually at
intervals not exceeding 12 months to ensure proper operation. The test must
either simulate an actual alarm condition or shall be conducted according to
manufacturer's specifications, and shall include, at a minimum, a determination
of whether the device operates as designed. Remote testing of the system can be
performed by the manufacturer if the remote test is included in the third-party
certification by a Nationally Recognized Testing Laboratory .
(8) All annual testing shall be performed at
intervals not exceeding 12 months and will be deemed timely if performed within
the same calendar month in which the test is due.
(9) Operability test results shall be
maintained and available for inspection by the Department or county in
accordance with Rule 62-762.711,
F.A.C.
Notes
Rulemaking Authority 376.303 FS. Law Implemented 376.303, 403.091 FS.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.