Fla. Admin. Code Ann. R. 62-762.802 - Out-of-Service and Closure Requirements for Field Erected Storage Tank Systems
(1) Temporary out-of-service. Field erected
storage tank systems taken temporarily out-of-service are those that are
emptied solely for the purpose of cleaning, routine maintenance, or change of
product for a time period exceeding 90 days, but less than 365 days. These
storage tank systems shall:
(a) Continue to
operate and maintain corrosion protection in accordance with subsection
62-762.702(2),
F.A.C.;
(b) Perform release
detection monthly in accordance with applicable provisions of Rule
62-762.602, F.A.C., if the tank
system has an external release detection method;
(c) Leave venting systems open and
functioning; and,
(d) Be returned
to in-service status or be designated as out-of-service within 365 days of
being taken temporarily out-of-service.
(2) Out-of-service storage tank systems.
(a) Storage tank systems that are taken
out-of-service, as required in this subsection, shall continue to be maintained
in accordance with this chapter unless otherwise noted herein.
(b) Facility owners and operators of
out-of-service storage tank systems shall:
1.
Continue to operate and maintain corrosion protection in accordance with
subsection 62-762.702(2),
F.A.C.,
2. Continue to maintain and
demonstrate financial responsibility pursuant to Rule
62-762.421, F.A.C.,
3. Leave vent lines open and functioning,
4. Remove all regulated substances
so that no more than one inch in depth or 0.3 percent by weight of the
regulated substances remains in the storage tank,
5. Secure or close off the system to outside
access,
6. Register the storage
tank system out-of-service in accordance with Rule
62-762.401, F.A.C.; and,
7. Perform a visual inspection
annually, not to exceed 12 months, of every component of a storage tank system
that contains, transfers, or stores, or is designed to contain, transfer, or
store regulated substances, that can be visually inspected. Each annual visual
inspection of the storage tank system shall be documented as to its condition
pursuant to Rule 62-762.711, F.A.C., and will be
deemed timely if performed within the same calendar month in which the test is
due. Any visual inspection of a storage tank system that reveals uncontrolled
pitting corrosion, structural damage, leakage, or other similar problems is
considered a positive response. The positive response shall be recorded as part
of the release detection records and reported and investigated as an incident
pursuant to Rule 62-762.431, F.A.C. If it is
determined that a release has occurred while the system is out-of-service; and,
a. The incident investigation reveals a
release has led to a discharge while the storage tank system is out-of-service
and storing regulated substances at no more than one inch in depth or 0.3
percent by weight of total system capacity, then the response to the discharge
shall be in accordance with paragraphs
62-762.441(6)(a), (b), (e), (f), and
(g), F.A.C. Repairs shall be made within 365
days of the discharge discovery in accordance with paragraphs
62-762.702(1)(a), (c), (d), and
(e), F.A.C. If the system cannot be repaired
within 365 days after the discovery the discharge, it shall be permanently
closed pursuant to subsection
62-762.802(3),
F.A.C.
b. The incident
investigation reveals a release has not led to a discharge while the storage
tank system is out-of-service, then repairs shall be made in accordance with
paragraphs 62-762.702(1)(a), (c), (d), and
(e), F.A.C., prior to bringing the storage
tank system back into service.
(c) Facility owners and operators of
out-of-service storage tank systems shall monitor tank bottom release detection
systems or devices annually but not to exceed 12 months. The annual monitoring
of tank bottom release detection systems or devices will be deemed timely if
performed within the same calendar month in which the test is due. Records of
these inspections shall be maintained in accordance with subsection
62-762.711(2),
F.A.C. In the event that there is any positive response of a tank bottom
release detection device, an INF must be submitted in writing or electronic
format and an investigation as to the cause performed pursuant to Rule
62-762.431, F.A.C.
(d) The following inspections and testing
requirements are not required while the storage tank system is properly
out-of-service:
1. Monthly visual inspections
in accordance with paragraph
62-762.602(1)(e),
F.A.C.,
2. Monthly inspection of
electronic release detection devices in accordance with paragraph
62-762.602(1)(g),
F.A.C., and
3. Release detection
device annual operability testing, containment and interstitial integrity
testing, and annual overfill protection device testing; however, all
aforementioned testing shall be current in accordance with this chapter and
indicate proper operation before adding regulated substances to the storage
tank system. In addition, before being returned to service, storage tank
systems that have been out-of-service for more than 365 days must be:
a. Structurally evaluated in accordance with
API Std 653, November 2014, including Addendum 1 (2018), Addendum 2 (2020), and
Errata 1 (2020), for field erected tanks, incorporated by reference in
subsection 62-762.411(3),
F.A.C.; and,
b. Integrity tested in
accordance with Rule 62-762.702, F.A.C., for integral
piping.
(e)
Storage tank systems with secondary containment, not requiring repairs pursuant
to Rule 62-762.702, F.A.C., shall only
be designated as out-of-service for a maximum of 10 continuous years. Upon
expiration of this time period, the storage tank system must be closed in
accordance with paragraph
62-762.802(3)(b),
F.A.C.
(f) Storage tank systems
without secondary containment, not requiring repairs pursuant to Rule
62-762.702, F.A.C., shall not
remain in a continuous out-of-service status for more than five years. Upon
expiration of this time period, the storage tank system must be closed in
accordance with paragraph
62-762.802(3)(b),
F.A.C.
(g) Field erected tanks
changing the type of product stored within the tank shall comply with API Std
653, November 2014, including Addendum 1 (2018), Addendum 2 (2020), and Errata
1 (2020), incorporated by reference in subsection
62-762.411(3),
F.A.C.
(3) Closure of
storage tank systems.
(a) The following
storage tank systems must be closed within 90 days in accordance with the
provisions of this subsection:
1. A storage
tank system that is out-of-service, and has not had regulated substances added
to or withdrawn from the system for more than:
a. Five years after January 11, 2017, for
single-walled storage tank systems, or
b. 10 years after January 11, 2017, for
storage tank systems with secondary containment.
2. Upon discovery, a storage tank system that
fails to meet or, if required, is not modified to meet the Storage Tank System
requirements of Rule 62-762.502, F.A.C.
3. A storage tank system that requires repair
pursuant to Rule 62-762.702, F.A.C., but is not
repaired within 90 days to operate in accordance with the requirements of this
chapter shall be taken out-of-service. If the system is not repaired within 365
days after being taken out-of-service, it shall be permanently
closed.
4. A storage tank system
where financial responsibility is not maintained and demonstrated, pursuant to
Rule 62-762.421, F.A.C., within 90
days of termination of the financial mechanism.
(b) Closure of storage tank systems shall be
performed by:
1. Conducting a Closure
Integrity Evaluation for field erected storage tank systems as defined in
subsection 62-762.201(9),
F.A.C., and completing the Closure Integrity Evaluation Report Form for ASTs
62-762.901(7)
(Closure Integrity Report), incorporated by reference in paragraph
62-762.411(2)(c),
F.A.C. The form shall be submitted in paper or electronic format to the
appropriate county,
2. Removing all
liquids and accumulated sludges. The removal and disposal of all liquids and
accumulated sludges may be required according to other federal, state, or local
requirements,
3. Removing or
disconnecting and capping all integral piping,
4. Removing and disposing of a storage tank,
or in-place closure by rendering the storage tank free of regulated substances
and vapors at the time of closure to prevent hazardous explosive conditions, by
maintaining the storage tank to prevent future explosive conditions, and by
protecting the storage tank from flotation in accordance with Chapter 22 of
NFPA 30, 2021 Edition, incorporated by reference in paragraph
62-762.201(36)(a),
F.A.C. In lieu of in-place closure or removal, a storage tank may be used to
store liquids other than regulated substances. Owners and operators are advised
that other federal, state, or local requirements apply that regulate these
activities,
5. For single-walled
storage tanks, and single-walled integral piping in contact with the soil,
regardless of the date of installation of the storage tank system or storage
tank system component, an investigation shall be conducted during closure in
accordance with Instructions for Conducting Sampling During Above
ground Storage Tank Closure, July 2019 Edition,
6. Properly closing monitoring wells
associated with closed systems that are not being used for site assessment
purposes; and,
7. For single-walled
storage tanks and single-walled integral piping that are not in contact with
the soil, a visual inspection must be performed to determine if any discharges
have occurred.
8. Once a storage
tank system has been properly closed pursuant to subsections
62-762.802(3) and
(4), F.A.C., and the Closure Report or the
Limited Closure Report Form for ASTs
62-762.901(8),
incorporated by reference in subsection
62-762.421(2),
F.A.C., has been submitted to and approved by the county or the Department, the
facility owner shall update the facility's registration status within 10 days
to indicate the storage tank system as closed in accordance with subsection
62-762.401(2),
F.A.C.
(4)
Closure Integrity Report, Closure Report, and Limited Closure Report.
(a) Closure Integrity Report.
1. Storage tank system and system components
not in contact with soil do not require a Closure Integrity
Evaluation.
2. A Closure Integrity
Evaluation for field erected storage tank systems as defined in subsection
62-762.201(9),
F.A.C., must be performed no more than 45 days prior to closure or replacement
for all double-walled and double-bottomed storage tanks, double-walled integral
piping, and hydrant sumps in contact with soil. Spill containment systems that
are completely below-grade also require a Closure Integrity Evaluation. A
Closure Integrity Report must be completed to document the findings of the
Closure Integrity Evaluation.
3. A
Closure Integrity Evaluation requires a visual assessment of the interstitial
space of double-walled and double-bottomed storage tanks, double-walled
integral piping, and double-walled hydrant sumps that are in contact with the
soil to determine if there are any products or pollutants or any water other
than condensate present within the interstice. For storage tank system
components where the interstitial space cannot be visually inspected, other
methods approved by the manufacturer, API Std 653, November 2014, including
Addendum 1 (2018), Addendum 2 (2020), and Errata 1 (2020), PEI/RP1200-19, or
the Department such as vacuum, pressure, or inert gases may be used instead of
visual observations.
4. A Closure
Integrity Evaluation for single-walled hydrant sumps that are in contact with
the soil, and single-walled spill containment systems that are completely
below-grade require a hydrostatic test or another test approved by the
manufacturer.
5. The County must be
provided with a copy of the Closure Integrity Report as part of the
notification process pursuant to paragraph
62-762.411(2)(c),
F.A.C.
6. A failed Closure
Integrity Evaluation requires the reporting of the failed evaluation as an
incident in accordance with paragraph
62-762.431(1)(f),
F.A.C., and the investigation of the incident in accordance with Rule
62-762.431, F.A.C. If sampling
is necessary to determine whether a discharge has occurred, then an
investigation shall be conducted during closure in accordance with
Instructions for Conducting Sampling During Above ground Storage Tank
Closure, July 2019 Edition, regardless of the date of installation of
the storage tank system or system component being closed.
7. The owner or operator who does not, or
elects not to conduct a Closure Integrity Evaluation, in accordance with
paragraph 62-762.802(4)(a),
F.A.C., before the storage tank system or system component has been removed or
closed in-place, regardless of the date of installation of the storage tank
system or system component, shall conduct an investigation at the time of
closure in accordance with Instructions for Conducting Sampling During
Above ground Storage Tank Closure, July 2019
Edition.
(b) Closure
Report. In cases where an investigation is conducted at the time of closure in
accordance with Instructions for Conducting Sampling During Above
ground Storage Tank Closure, July 2019 Edition, a Closure Report shall
be submitted in writing or electronic format to the County within 60 days of
completion of the system or system component closure or replacement. The
Closure Report shall be prepared in accordance with Instructions for
Conducting Sampling During Above ground Storage Tank Closure, July
2019 Edition.
(c) Limited Closure
Report. Form 62-762.901(8),
Limited Closure Report Form for ASTs shall be submitted in writing or
electronic format to the County within 60 days of completion of the closure or
replacement in cases where:
1. A Closure
Integrity Evaluation passed,
2. A
failed Closure Integrity Evaluation was investigated prior to closure and it
was demonstrated that a discharge did not occur, or
3. A Closure Integrity Evaluation or Closure
Report were not required because the closure only involved a storage tank
system or system components that were not in contact with the
soil.
Notes
Rulemaking Authority 376.303 FS. Law Implemented 376.303 FS.
New 1-11-17, Amended 10-17-19, 6-26-23.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.