B. The owner shall conduct an initial and a
second round of source water monitoring for each water treatment plant that
treats a surface water source, a GUDI source, or both. This monitoring may
include sampling for Cryptosporidium, E. coli, and turbidity to determine what
level, if any, of additional Cryptosporidium treatment is required.
1. Initial round of source water monitoring.
The owner shall conduct the following monitoring on the schedule in subdivision
B 3 of this section unless the monitoring avoidance criteria in subdivision B 4
of this section are met.
a. The owner of a
waterworks serving at least 10,000 people shall sample the source water for
Cryptosporidium, E. coli, and turbidity at least monthly for 24
months.
b. The owner of a
waterworks serving fewer than 10,000 people:
(1) Shall sample the source water for E. coli
at least once every two weeks for 12 months, or
(2) May avoid E. coli monitoring if the owner
notifies the department that the owner will monitor for Cryptosporidium as
described in subdivision B 1 c of this section. The owner shall notify the
department no later than three months before the date at which the owner is
otherwise required to start E. coli monitoring.
c. The owner of a waterworks serving fewer
than 10,000 people shall sample the source water for Cryptosporidium at least
twice per month for 12 months or at least monthly for 24 months if the owner
meets one of the following, based on monitoring conducted under subdivision B 1
b of this section:
(1) For a waterworks using
source water from a lake or reservoir, the annual mean E. coli concentration is
greater than 10 E. coli/100 mL.
(2)
For a waterworks using source water from flowing stream, the annual mean E.
coli concentration is greater than 50 E. coli/100 mL.
(3) The waterworks does not conduct E. coli
monitoring as described in subdivision B 1 b of this section.
(4) The waterworks using a GUDI source shall
comply with the requirements of this subdivision B 1 c based on the E. coli
level that applies to the nearest surface water body. If no surface water body
is nearby, the waterworks shall comply based on the requirements that apply to
a waterworks using source water from a lake or reservoir.
d. For the waterworks serving fewer than
10,000 people, the department may approve monitoring for an indicator other
than E. coli under subdivision B 1 b (1) of this section. The department also
may approve an alternative to the E. coli concentration in subdivision B 1 c
(1), B 1 c (2), or B 1 c (4) of this section to trigger Cryptosporidium
monitoring. This approval by the department shall be provided to the owner in
writing and shall include the basis for the department's determination that the
alternative indicator or trigger level will provide a more accurate
identification of whether a waterworks will exceed the Bin 1 Cryptosporidium
level in subdivision B 1 a of this section.
e. The waterworks may sample more frequently
than required under this section if the sampling frequency is evenly spaced
throughout the monitoring period.
2. Second round of source water monitoring.
The owner shall conduct a second round of source water monitoring that meets
the requirements for monitoring parameters, frequency, and duration described
in subdivision B 1 of this section, unless the monitoring exemption criteria in
subdivision B 4 of this section are met. The owner shall conduct this
monitoring on the schedule in subdivision B 3 of this section.
3. Monitoring schedule. The owner shall begin
the monitoring required in subdivisions B 1 and B 2 of this section no later
than the month beginning with the date listed in Table 401.1:
|
TABLE 401.1
Source Water Monitoring Starting Dates
|
|
OWNERS OF WATERWORKS THAT SERVE...
|
SHALL BEGIN THE FIRST ROUND OF SOURCE WATER
MONITORING NO LATER THAN THE MONTH BEGINNING...
|
AND SHALL BEGIN THE SECOND ROUND OF SOURCE WATER
MONITORING NO LATER THAN THE MONTH BEGINNING...
|
|
At least 100,000 people
|
October 1, 2006
|
April 1, 2015
|
|
From 50,000 - 99,999 people
|
April 1, 2007
|
October 1, 2015
|
|
From 10,000 - 49,999 people
|
April 1, 2008
|
October 1, 2016
|
|
Fewer than 10,000 and monitor for E.
coli
|
October 1, 2008
|
October 1, 2017
|
|
Fewer than 10,000 and monitor for
Cryptosporidiuma
|
April 1, 2010
|
April 1, 2019
|
|
aApplies to a waterworks
that meet the conditions of subdivision B 1 c of this section.
|
4.
Monitoring avoidance.
a. The owner is not
required to conduct source water monitoring if the waterworks will provide a
total of at least 5.5-log of treatment for Cryptosporidium, equivalent to
meeting the treatment requirements of Bin 4 in subdivision D 2 of this
section.
b. If the owner chooses to
provide the level of treatment in subdivision B 4 a of this section, rather
than start source water monitoring, then the owner shall notify the department
in writing no later than the date the owner is otherwise required to submit a
sampling schedule for monitoring under subdivision B 5 of this section.
Alternatively, the owner may choose to stop sampling at any point after
initiating monitoring if the owner notifies the department in writing that he
will provide this level of treatment. The owner shall install and operate
technologies to provide this level of treatment by the applicable treatment
compliance date in subdivision D 3 of this section.
5. Sampling schedules.
a. The owner of a waterworks required to
conduct source water monitoring in accordance with subsection B of this section
shall submit a sampling schedule that specifies the calendar dates when the
owner shall collect each required sample.
(1)
The owner shall submit a sampling schedule to the department no later than
three months before the applicable date listed in subdivision B 3 of this
section for each round of required monitoring.
(2) If the department does not respond to the
owner regarding the sampling schedule, then the owner shall sample at the
reported schedule.
b. The
owner shall collect samples within two days before or two days after the dates
indicated in the sampling schedule (i.e., within a five-day period around the
schedule date) unless one of the conditions of this subdivision b applies:
(1) If an extreme condition or situation
exists that may pose danger to the sample collector or that cannot be avoided
and causes the owner to be unable to sample in the scheduled five-day period,
then the owner shall sample as close to the scheduled date as is feasible
unless the department approves an alternative sampling date. The owner shall
submit an explanation for the delayed sampling date to the department
concurrent with the shipment of the sample to the laboratory.
(2) If the owner is unable to report a valid
analytical result for a scheduled sampling date due to equipment failure, loss
of or damage to the sample, failure to comply with the analytical method
requirements, including the quality control requirements of
12VAC5-590-440, or the failure of
an approved laboratory to analyze the sample, then the owner shall collect a
replacement sample. The owner shall collect the replacement sample not later
than 21 days after receiving information that an analytical result cannot be
reported for the scheduled date unless the owner demonstrates that collecting a
replacement sample within this timeframe is not feasible or the department
approves an alternative resampling date. The owner shall submit an explanation
for the delayed sampling date to the department concurrent with the shipment of
the sample to the laboratory.
c. The owner of a waterworks that fails to
meet the criteria of subdivision B 5 b of this section for any source water
sample required under subsection B of this section shall revise the sampling
schedule to add dates for collecting all missed samples. The owner shall submit
the revised schedule to the department for approval before the owner begins
collecting the missed samples.
6. Sampling locations.
a. The owner of a waterworks required to
conduct source water monitoring under subsection B of this section shall
collect samples for each water treatment plant that treats a surface water
source, a GUDI source, or both. Where multiple water treatment plants draw
source water from the same influent, such as the same pipe or intake, the
department may approve one set of monitoring results to be used to satisfy the
requirements of subsection B of this section for all water treatment
plants.
b. The owner shall collect
source water samples before chemical treatment, such as coagulants, oxidants,
and disinfectants. However, the department may approve the collection of a
source water sample after chemical treatment. To grant this approval, the
department shall determine that collecting a sample before chemical treatment
is not feasible for the owner and that the chemical treatment is unlikely to
have a significant adverse effect on the analysis of the sample.
c. The owner of a waterworks that recycles
filter backwash water shall collect source water samples before the point of
filter backwash water addition.
d.
Bank filtration.
(1) The owner that receives
Cryptosporidium treatment credit for bank filtration under
12VAC5-590-395 A 2 b
(1) shall collect source water samples from
the surface water before bank filtration.
(2) The owner that uses bank filtration as
pretreatment to a water treatment plant shall collect source water samples from
the well (i.e., after bank filtration). The use of bank filtration during
monitoring shall be consistent with routine operational practice. The owner
collecting samples after a bank filtration process may not receive treatment
credit for the bank filtration under subdivision E 4 c of this
section.
e. Multiple
sources. The owner of a waterworks that uses multiple source waters, including
multiple surface water sources and blended surface water and groundwater
sources, shall collect samples as specified in subdivision B 6 e (1) or B 6 e
(2) of this section. The use of multiple source waters during monitoring shall
be consistent with routine operational practice.
(1) If a sampling tap is available where the
source waters are combined before treatment, then the owner shall collect
samples from the tap.
(2) If a
sampling tap is not available where the source waters are combined before
treatment, then the owner shall collect samples at each source near the intake
on the same day and shall follow either subdivision B 6 e (2) (a) or B 6 e (2)
(b) of this section for sample analysis.
(a)
The owner may composite samples from each source into one sample before
analysis. The volume of sample from each source shall be weighted according to
the proportion of the source water in the total water treatment plant flow at
the time the sample is collected.
(b) The owner may choose to have samples
analyzed from each source separately and calculate a weighted average of the
analysis results for each sampling date. The weighted average shall be
calculated by multiplying the analysis result for each source water by the
fraction the source water contributed to the total water treatment plant flow
at the time the sample was collected and then summing these values.
f. Additional
requirements. The owner shall submit a description of each sampling location to
the department at the same time as the sampling schedule required in
subdivision B 3 of this section. This description shall address the position of
the sampling location in relation to the waterworks' source waters and
treatment processes, including pretreatment, points of chemical treatment, and
filter backwash recycle. If the department does not respond to an owner
regarding sampling location, then the owner shall sample at each reported
location.
7. Analytical
methods. All analytical methods shall be conducted in accordance with
12VAC5-590-440.
8. Approved laboratories.
a. Cryptosporidium. The owner shall have
Cryptosporidium samples analyzed by a laboratory that has received reciprocal
certification approved under the DCLS Laboratory Certification Program for
Analysis of Cryptosporidium in Water.
b. E. coli. A laboratory certified by the
DCLS for total coliform analysis under
12VAC5-590-440 is approved for E.
coli analysis when the laboratory uses the same technique for E. coli that the
laboratory uses under
12VAC5-590-440. Laboratories shall
use methods for enumeration of E. coli in source water approved in
12VAC5-590-440.
c. Turbidity. Measurements of turbidity shall
be made by a party approved by the department.
9. Reporting of the source water results
shall be in accordance with
12VAC5-590-531.
10. The owner of a waterworks treating a
surface water source, a GUDI source, or both, that operates for only part of
the year shall conduct source water monitoring in accordance with this section,
but with the following modifications:
a. The
owner shall sample the source water only during the months that the waterworks
operates unless the department specifies another monitoring period based on
waterworks operating practices.
b.
The owner of a waterworks that operates less than six months per year and that
monitors for Cryptosporidium shall collect at least six Cryptosporidium samples
per year during each of two years of monitoring. Samples shall be evenly spaced
throughout the period the waterworks operates.
11. New sources.
a. The owner of a waterworks that begins
using a surface water source, a GUDI source, or both, is required to begin
monitoring under subdivision B 3 of this section and shall monitor the new
source on a schedule approved by the department. Source water monitoring shall
meet the requirements of this section. The owner shall also meet the bin
classification and Cryptosporidium treatment requirements of subdivisions D 1
and D 2 of this section, for the new source on a schedule approved by the
department.
b. The requirements of
this section apply to a waterworks using a surface water source, a GUDI source,
or both, that begins operation after the monitoring start date applicable to
the size of the waterworks under subdivision B 3 of this section.
c. The owner shall begin a second round of
source water monitoring no later than six years following the initial bin
classification under subdivision D 1 of this section.
12. Failure to collect any source water
sample required under this section in accordance with the sampling schedule,
sampling location, analytical method, approved laboratory, and reporting
requirements of subdivisions B 5 through B 9 of this section is a monitoring
violation.
13. Grandparenting
monitoring data. The owner may use monitoring data collected before the
applicable monitoring start date in subdivision B 3 of this section
(grandparented data) to meet the initial source water monitoring requirements
in subdivision B 1 of this section. Grandparented data may be substituted for
an equivalent number of months at the end of the monitoring period. All data
submitted under this subdivision B 13 shall meet the requirements in
subdivisions B 13 a through B 13 h of this section and be approved by the
department:
a. The owner may grandparent
Cryptosporidium samples to meet the requirements of this section when the owner
does not have corresponding E. coli and turbidity samples. The owner who
grandparents Cryptosporidium samples without E. coli and turbidity samples is
not required to collect E. coli and turbidity samples when the owner completes
the requirements for Cryptosporidium monitoring under this section.
b. The analysis of E. coli samples shall meet
the analytical method and approved laboratory requirements of subdivisions B 7
and B 8 of this section.
c. The
analysis of Cryptosporidium samples shall meet the requirements of subdivision
B 8 of this section.
d. The
sampling location shall meet the conditions in subdivision B 6 of this
section.
e. Cryptosporidium sample
collection intervals may vary for the conditions specified in subdivisions B 5
b (1) and B 5 b (2) of this section if the owner provides documentation of the
condition when reporting monitoring results.
(1) The department may approve grandparenting
of previously collected data where there are time gaps in the sampling
frequency if the owner conducts additional monitoring the department specifies
to ensure that the data used to comply with the initial source water monitoring
requirements of subsection B of this section are seasonally representative and
unbiased.
(2) The owner may
grandparent previously collected data where the sampling frequency within each
month varied. If the Cryptosporidium sampling frequency varied, then the owner
shall follow the monthly averaging procedure in subdivision D 1 a (5) of this
section when calculating the bin classification for a filtered
waterworks.
f. The owner
of a waterworks that requests to grandparent previously collected monitoring
results shall report the following information by the applicable dates listed
in the following subdivisions. The owner shall report this information to the
department.
(1) The owner shall report the
intent to submit previously collected monitoring results for grandparenting.
This report shall specify the number of previously collected results the owner
shall submit, the dates of the first and last sample, and whether an owner
shall conduct additional source water monitoring to meet the requirements in
subsection B of this section. The owner shall report this information no later
than the date the sampling schedule listed in subdivision B 3 of this section
is required.
(2) The owner shall
report previously collected monitoring results for grandparenting no later than
two months after the applicable date listed in subdivision B 3 of this section.
(a) For each sample result, the owner shall
report the applicable data elements in
12VAC5-590-531 A
5.
(b) The owner shall certify that the reported
monitoring results include all results the waterworks generated during the time
period beginning with the first reported result and ending with the final
reported result. This applies to samples that were collected from the sampling
location specified for source water monitoring under subdivision B 1 of this
section, not spiked, and analyzed using the laboratory's routine process for
the analytical methods listed in this section.
(c) The owner shall certify that the samples
were representative of a waterworks' source waters and the source waters have
not changed. The owner shall report a description of each sampling location,
which shall address the position of the sampling location in relation to the
waterworks' source waters and treatment processes, including points of chemical
addition and filter backwash recycle.
(d) For Cryptosporidium samples, the
laboratory that analyzed the samples shall provide a letter certifying that the
quality control criteria specified in the methods listed in subdivision B 8 of
this section were met for each sample batch associated with the reported
results. Alternatively, the laboratory may provide bench sheets and sample
examination report forms for each field, matrix spike, initial precision and
recovery (IPR), ongoing precision and recovery (OPR), and method blank sample
associated with the reported results.
g. If the department determines that a
previously collected data set submitted for grandparenting was generated during
source water conditions that were not normal for the waterworks, such as a
drought, the department may disapprove the data. Alternatively, the department
may approve the previously collected data if the owner reports additional
source water monitoring data, as determined by the department, to ensure that
the data set used under subdivision D 1 of this section represents average
source water conditions for the waterworks.
h. If the owner submits previously collected
data that fully meets the number of samples required for initial source water
monitoring under subdivision B 1 of this section and some of the data are
rejected due to not meeting the requirements of this section, then the owner
shall conduct additional monitoring to replace rejected data on a schedule
approved by the department. The owner is not required to begin this additional
monitoring until two months after notification that data have been rejected and
additional monitoring is necessary.
D.
The owner shall determine the Cryptosporidium treatment bin classification as
described in subdivision D 1 of this section and provide additional treatment
for Cryptosporidium, if required, as described in subdivision D 2 of this
section. The owner shall implement Cryptosporidium treatment according to the
schedule in subdivision D 3 of this section.
1. Bin classification for waterworks.
a. Following completion of the initial round
of source water monitoring required under subdivision B 1 of this section, the
owner shall calculate an initial Cryptosporidium bin concentration for each
water treatment plant for which monitoring was required. Calculation of the bin
concentration shall use the Cryptosporidium results reported under subdivision
B 1 of this section and shall follow these procedures:
(1) For the owner who collects a total of at
least 48 samples, the bin concentration is equal to the arithmetic mean of all
sample concentrations.
(2) For the
owner who collects a total of at least 24 samples, but not more than 47
samples, the bin concentration is equal to the highest arithmetic mean of all
sample concentrations in any 12 consecutive months during which Cryptosporidium
samples were collected.
(3) For the
owner of a waterworks that serves fewer than 10,000 people and monitors for
Cryptosporidium for only one year (i.e., collect 24 samples in 12 months), the
bin concentration is equal to the arithmetic mean of all sample
concentrations.
(4) For water
treatment plants that operate only part of the year and that monitor fewer than
12 months per year under subdivision B 1 of this section, the bin concentration
is equal to the highest arithmetic mean of all sample concentrations during any
year of Cryptosporidium monitoring.
(5) If the monthly Cryptosporidium sampling
frequency varies, then the owner shall first calculate a monthly average for
each month of monitoring. The owner shall then use these monthly average
concentrations, rather than individual sample concentrations, in the applicable
calculation for bin classification in subdivisions D 1 a (1) through D 1 a (4)
of this section.
b. The
owner shall determine the initial bin classification from Table 401.2 using the
Cryptosporidium bin concentration calculated under subdivision D 1 a of this
section:
|
TABLE 401.2
Bin Classification for Filtered
Waterworks
|
|
FOR OWNERS OF WATERWORKS THAT ARE...
|
WITH A CRYPTOSPORIDIUM BIN CONCENTRATION
OFa ...
|
THE BIN CLASSIFICATION IS...
|
|
Required to monitor for Cryptosporidium under
subdivision B 1 of this section
|
Cryptosporidium less than 0.075
oocysts/L
|
Bin 1
|
|
Cryptosporidium equal to or greater than 0.075
oocysts/L but less than 1.0 oocysts/L
|
Bin 2
|
|
Cryptosporidium equal to or greater than 1.0
oocysts/L but less than 3.0 oocysts/L
|
Bin 3
|
|
Cryptosporidium equal to or greater than 3.0
oocysts/L
|
Bin 4
|
|
Serving fewer than 10,000 people and NOT required to
monitor for Cryptosporidium under subdivision B 1 c of this
section
|
Not Applicable
|
Bin 1
|
|
aBased on calculations in
subdivision D 1 a or D 1 c of this section, as applicable.
|
c.
Following completion of the second round of source water monitoring required
under subdivision B 2 of this section, the owner shall recalculate the
Cryptosporidium bin concentration using the Cryptosporidium results reported
under subdivision B 2 of this section and following the procedures in
subdivisions D 1 a (1) through D 1 a (4) of this section. The owner shall then
redetermine the bin classification using this bin concentration and Table
401.3.
d. Reporting of bin
classifications.
(1) The owner shall report
the initial bin classification under subdivision D 1 b of this section to the
department for approval no later than six months after the waterworks is
required to complete the initial source water monitoring based on the schedule
in subdivision B 3 of this section.
(2) The owner shall report the bin
classification under subdivision D 1 c of this section to the department for
approval no later than six months after the owner is required to complete the
second round of source water monitoring based on the schedule in subdivision D
1 a (3) of this section.
(3) The
bin classification report to the department shall include a summary of source
water monitoring data and the calculation procedure used to determine bin
classification.
e.
Failure to comply with the conditions of subdivision D 1 d of this section is a
violation of the treatment technique requirement.
2. Waterworks additional Cryptosporidium
treatment requirements.
a. A waterworks shall
provide the level of additional treatment for Cryptosporidium specified in this
subdivision based on the bin classification as determined under subdivision D 1
of this section and according to the schedule in subdivision D 3 b of this
section.
|
TABLE 401.3 Cryptosporidium Treatment
Requirements
|
|
IF THE WATERWORKS BIN CLASSIFICATION
IS...
|
AND THE WATERWORKS USES THE FOLLOWING FILTRATION
TREATMENT IN FULL COMPLIANCE WITH
12VAC5-590-395 A
1 AND
12VAC5-590-395 A
2, THEN THE ADDITIONAL CRYPTOSPORIDIUM
TREATMENT REQUIREMENTS ARE...
|
|
Conventional filtration treatment (including
softening)
|
Direct filtration
|
Slow sand or diatomaceous earth
filtration
|
Alternative filtration technologies
|
|
Bin 1
|
No additional treatment
|
No additional treatment
|
No additional treatment
|
No additional treatment
|
|
Bin 2
|
1-log treatment
|
1.5-log treatment
|
1-log treatment
|
a
|
|
Bin 3
|
2-log treatment
|
2.5-log treatment
|
2-log treatment
|
b
|
|
Bin 4
|
2.5-log treatment
|
3-log treatment
|
2.5-log treatment
|
c
|
|
aAs determined by the
department such that the total Cryptosporidium removal and inactivation is at
least 4.0-log.
bAs determined by the
department such that the total Cryptosporidium removal and inactivation is at
least 5.0-log.
cAs determined by the
department such that the total Cryptosporidium removal and inactivation is at
least 5.5-log.
|
b.
Additional treatment.
(1) The owner shall use
one or more of the treatment and management options listed in subsection E of
this section, termed the microbial toolbox, to comply with the additional
Cryptosporidium treatment required in subdivision D 2 a of this
section.
(2) A waterworks
classified in Bin 3 and Bin 4 shall achieve at least 1-log of the additional
Cryptosporidium treatment required under subdivision D 2 a of this section
using either one or a combination of the following:
(i) bag filters,
(ii) bank filtration,
(iii) cartridge filters,
(iv) chlorine dioxide,
(v) membranes,
(vi) ozone, or
(vii) UV as described in subdivisions E 3
through E 7 of this section.
c. Failure by a waterworks in any month to
achieve treatment credit by meeting criteria in subdivisions E 3 through E 7 of
this section for microbial toolbox options that is at least equal to the level
of treatment required in subdivision D 2 a of this section is a violation of
the treatment technique requirement.
d. If the department determines during a
sanitary survey or an equivalent source water assessment that after an owner
completed the monitoring conducted under subdivision B 1 or B 2 of this
section, significant changes occurred in the waterworks watershed that could
lead to increased contamination of the source water by Cryptosporidium, then
the owner shall take actions specified by the department to address the
contamination. These actions may include additional source water monitoring or
implementing microbial toolbox options listed in subdivision E 2 of this
section.
3. Schedule for
compliance with Cryptosporidium treatment requirements.
a. Following the initial bin classification
in accordance with subdivision D 1 b of this section, the owner shall provide
the level of treatment for Cryptosporidium required under subdivision D 2 of
this section according to the schedule in subdivision D 3 b of this
section.
b. If the bin
classification for a filtered waterworks changes following the second round of
source water monitoring, as determined under subdivision D 1 c of this section,
then the owner shall provide the level of treatment for Cryptosporidium
required under subdivision D 2 of this section on a schedule approved by the
department.
E.
The owner of a waterworks required to provide additional treatment for
Cryptosporidium shall implement microbial toolbox options that are designed and
operated as described in subdivisions E 1 through E 7 of this section.
1. The owner receives the treatment credits
listed in Table 401.4 by meeting the conditions for microbial toolbox options
described in subdivisions E 3 through E 7 of this section. The owner shall
apply these treatment credits to meet the treatment requirements in subdivision
D 2 of this section.
2. Microbial
Toolbox Summary Table: Options, Treatment Credits and Criteria.
|
TABLE 401.4
Microbial Toolbox Summary: Options, Treatment Credits
and Criteria
|
|
TOOLBOX OPTION
|
CRYPTOSPORIDIUM TREATMENT CREDIT WITH DESIGN AND
IMPLEMENTATION CRITERIA
|
|
Source Protection and Management Toolbox
Options
|
|
Alternative source and intake
management
|
No prescribed credit. The owner may conduct
simultaneous monitoring for treatment bin classification at alternative intake
locations or under alternative intake management strategies. Specific criteria
are in subdivision E 3 b of this section.
|
|
Prefiltration Toolbox Options
|
|
Presedimentation basin with
coagulation
|
0.5-log credit during any month that presedimentation
basins achieve a monthly mean reduction of 0.5-log or greater in turbidity or
alternative performance criteria approved by the department. To be eligible,
basins shall be operated continuously with coagulant addition and all water
treatment plant flow shall pass through basins. Specific criteria are in
subdivision E 4 a of this section.
|
|
Two-stage lime softening
|
0.5-log credit for two-stage softening where chemical
addition and hardness precipitation occur in both stages. All water treatment
plant flow shall pass through both stages. Single-stage softening is credited
as equivalent to conventional treatment. Specific criteria are in subdivision E
4 b of this section.
|
|
Bank filtration
|
0.5-log credit for 25-foot setback; 1.0-log credit
for 50-foot setback; aquifer shall be unconsolidated sand containing at least
10% fines; average turbidity in wells shall be less than 1 NTU. A waterworks
using wells followed by filtration when conducting source water monitoring
shall sample the well to determine bin classification and is not eligible for
additional credit. Specific criteria are in subdivision E 4 c of this
section.
|
|
Treatment Performance Toolbox Options
|
|
Combined filter performance
|
0.5-log credit for CFE turbidity less than or equal
to 0.15 NTU in at least 95% of measurements each month. Specific criteria are
in subdivision E 5 a of this section.
|
|
Individual filter performance
|
0.5-log credit (in addition to 0.5-log combined
filter performance credit) if individual filter effluent turbidity is less than
or equal to 0.15 NTU in at least 95% of samples each month in each filter and
is never greater than 0.3 NTU in two consecutive measurements in any filter.
Specific criteria are in subdivision E 5 b of this section.
|
|
Additional Filtration Toolbox Options
|
|
Bag or cartridge filters (individual
filters)
|
Up to 2-log credit based on the removal efficiency
demonstrated during challenge testing with a 1.0-log factor of safety. Specific
criteria are in subdivision E 6 a of this section.
|
|
Bag or cartridge filters (in series)
|
Up to 2.5-log credit based on the removal efficiency
demonstrated during challenge testing with a 0.5-log factor of safety. Specific
criteria are in subdivision E 6 a of this section.
|
|
Membrane filtration
|
Log credit equivalent to removal efficiency
demonstrated in challenge test for device if supported by direct integrity
testing. Specific criteria are in subdivision E 6 b of this
section.
|
|
Second stage filtration
|
0.5-log credit for second separate granular media
filtration stage if treatment train includes coagulation before first filter.
Specific criteria are in subdivision E 6 c of this section.
|
|
Slow sand filters
|
2.5-log credit as a secondary filtration step;
3.0-log credit as a primary filtration process. No prior chlorination for
either option. Specific criteria are in subdivision E 6 d of this
section.
|
|
Inactivation Toolbox Options
|
|
Chlorine dioxide
|
Log credit based on measured CT in relation to Table
401.5. Specific criteria in subdivision E 7 b of this section.
|
|
Ozone
|
Log credit based on measured CT in relation to Table
401.6. Specific criteria in subdivision E 7 b of this section.
|
|
UV
|
Log credit based on validated UV dose in relation to
Table 401.7; reactor validation testing required to establish UV dose and
associated operating conditions. Specific criteria in subdivision E 7 c of this
section.
|
3.
Source toolbox components.
a.
Reserved.
b. Alternative source.
(1) The owner may conduct source water
monitoring that reflects a different intake location (either in the same source
or for an alternate source) or a different procedure for the timing or level of
withdrawal from the source (alternative source water monitoring). If the
department approves, then the owner may determine the bin classification under
subdivision D 1 of this section based on the alternative source water
monitoring results.
(2) If the
owner conducts alternative source water monitoring under subdivision E 3 b (1)
of this section, then the owner shall also monitor the current water treatment
plant intake concurrently as described in subsection B of this section. "Plant
intake" means the works or structures at the head of a conduit through which
source water is diverted (e.g., river or lake) into the water treatment
plant.
(3) Alternative source water
monitoring under subdivision E 3 b (1) of this section shall meet the
requirements for source water monitoring to determine bin classification, as
described in subdivisions B 1 through B 13 of this section. The owner shall
report the alternative source water monitoring results to the department, along
with supporting information documenting the operating conditions under which
the samples were collected.
(4) If
the owner determines the bin classification under subdivision D 1 of this
section using alternative source water monitoring results that reflect a
different intake location or a different procedure for managing the timing or
level of withdrawal from the source, then the owner shall relocate the intake
or permanently adopt the withdrawal procedure, as applicable, no later than the
applicable treatment compliance date in subdivision D 3 of this
section.
4.
Prefiltration treatment toolbox components.
a.
Presedimentation. The owner receives 0.5-log Cryptosporidium treatment credit
for a presedimentation basin during any month the process meets the following
criteria:
(1) The presedimentation basin
shall be in continuous operation and shall treat the entire water treatment
plant flow at a waterworks using a surface water source, a GUDI source, or
both.
(2) A coagulant shall be
continuously added to the presedimentation basin.
(3) The presedimentation basin shall achieve
the performance criteria in either of the following:
(a) Demonstrates at least 0.5-log mean
reduction of influent turbidity. This reduction shall be determined using daily
turbidity measurements in the presedimentation process influent and effluent
and shall be calculated as follows: log10 (monthly mean of daily influent
turbidity) - log10 (monthly mean of daily effluent turbidity).
(b) Complies with the performance criteria
approved by the department that demonstrate at least 0.5-log mean removal of
micron-sized particulate material through the presedimentation process.
b. Two-stage
lime softening. The owner receives an additional 0.5-log Cryptosporidium
treatment credit for a two-stage lime softening plant if chemical addition and
hardness precipitation occur in two separate and sequential softening stages
before filtration. Both softening stages shall treat the entire plant flow
taken from a surface water source, a GUDI source, or both.
c. Bank filtration. The owner receives
Cryptosporidium treatment credit for bank filtration that serves as
pretreatment to a water filtration plant by meeting the criteria in this
subdivision. The owner using bank filtration upon beginning source water
monitoring under subdivision B 1 of this section shall collect samples as
described in subdivision B 6 d of this section and is not eligible for this
credit.
(1) Wells with a groundwater flow
path of at least 25 feet receive 0.5-log treatment credit; and wells with a
groundwater flow path of at least 50 feet receive 1.0-log treatment credit. The
groundwater flow path shall be determined as specified in subdivision E 4 c (4)
of this section.
(2) Only wells in
granular aquifers are eligible for treatment credit. Granular aquifers are
those comprised of sand, clay, silt, rock fragments, pebbles or larger
particles, and minor cement. The owner shall characterize the aquifer at the
well site to determine aquifer properties. The owner shall extract a core from
the aquifer and demonstrate that in at least 90% of the core length, grains
less than 1.0 mm in diameter constitute at least 10% of the core
material.
(3) Only horizontal and
vertical wells are eligible for treatment credit.
(4) For vertical wells, the groundwater flow
path is the measured distance from the edge of the surface water body under
high flow conditions (determined by the 100-year flood elevation boundary or by
the floodway, as defined in Federal Emergency Management Agency flood hazard
maps) to the well screen. For horizontal wells, the groundwater flow path is
the measured distance from the bed of the river under normal flow conditions to
the closest horizontal well lateral screen.
(5) The owner shall monitor each wellhead for
turbidity at least once every four hours while the bank filtration process is
in operation. If monthly average turbidity levels, based on daily maximum
values in the well, exceed 1 NTU, the owner shall report this result to the
department and conduct an assessment within 30 days to determine the cause of
the high turbidity levels in the well. If the department determines that
microbial removal has been compromised, the department may revoke treatment
credit until the owner implements corrective actions approved by the department
to remediate the problem.
(6)
Springs and infiltration galleries are not eligible for treatment credit under
this section.
(7) Bank filtration
demonstration of performance. The department may approve Cryptosporidium
treatment credit for bank filtration based on a demonstration-of-performance
study that meets the criteria in this subdivision. This treatment credit may be
greater than 1.0-log and may be awarded to bank filtration that does not meet
the criteria in subdivisions E 4 c (1) through E 4 c (5) of this section.
(a) The study shall follow a protocol
approved by the department and shall involve the collection of data on the
removal of Cryptosporidium or a surrogate for Cryptosporidium and related
hydrogeologic and water quality parameters during the full range of operating
conditions.
(b) The study shall
include sampling both from any production well and from monitoring wells that
are screened and located along the shortest flow path between the surface water
source and the production well.
5. Treatment performance toolbox components.
a. Combined filter performance. The owner
using conventional filtration treatment or direct filtration treatment receives
an additional 0.5-log Cryptosporidium treatment credit during any month the
waterworks meets the criteria in this subdivision. Combined filter effluent
(CFE) turbidity shall be less than or equal to 0.15 NTU in at least 95% of the
measurements. Turbidity shall be measured as described in
12VAC5-590-376 B.
b. Individual filter performance.
The owner using conventional filtration treatment or direct filtration
treatment receives 0.5-log Cryptosporidium treatment credit, which can be in
addition to the 0.5-log credit under subdivision E 5 a of this section, during
any month the waterworks meets the criteria in this subdivision. Compliance
with these criteria shall be based on individual filter turbidity monitoring as
described in
12VAC5-590-376 B.
(1) The filtered water turbidity for each
individual filter shall be less than or equal to 0.15 NTU in at least 95% of
the measurements recorded each month.
(2) No individual filter may have a measured
turbidity greater than 0.3 NTU in two consecutive measurements collected 15
minutes apart.
(3) The owner that
has received treatment credit for individual filter performance and fails to
meet the requirements of subdivision E 5 b (1) or E 5 b (2) of this section
during any month does not receive a treatment technique violation under
subdivision D 2 c of this section if the department determines the following:
(a) The failure was due to unusual and
short-term circumstances that could not reasonably be prevented through
optimizing water treatment plant design, operation, and maintenance.
(b) The waterworks has experienced no more
than two failures in any calendar year.
6. Additional filtration toolbox
components.
a. Bag and cartridge filters. The
owner receives Cryptosporidium treatment credit of up to 2.0-log for individual
bag or cartridge filters and up to 2.5-log for bag or cartridge filters
operated in series by meeting the criteria in subdivisions E 6 a (1) through E
6 a (10) of this section. To be eligible for this credit, the owner shall
report the results of challenge testing that meets the requirements of
subdivisions E 6 a (2) through E 6 a (9) of this section to the department. The
filters shall treat the entire water treatment plant flow taken from a surface
water source, a GUDI source, or both.
(1) The
Cryptosporidium treatment credit awarded to bag or cartridge filters shall be
based on the removal efficiency demonstrated during challenge testing that is
conducted according to the criteria in subdivisions E 6 a (2) through E 6 a (9)
of this section. A factor of safety equal to 1-log for individual bag or
cartridge filters and 0.5-log for bag or cartridge filters in series shall be
applied to challenge testing results to determine removal credit. The owner may
use the results from challenge testing conducted before January 5, 2006, if the
prior testing was consistent with the criteria specified in subdivisions E 6 a
(2) through E 6 a (9) of this section.
(2) Challenge testing shall be performed on
full-scale bag or cartridge filters, and the associated filter housing or
pressure vessel, that are identical in material and construction to the filters
and housings the waterworks will use for removal of Cryptosporidium. Bag or
cartridge filters shall be challenge tested in the same configuration that the
waterworks will use, either as individual filters or as a series configuration
of filters.
(3) Challenge testing
shall be conducted using Cryptosporidium or a surrogate that is removed no more
efficiently than Cryptosporidium. The microorganism or surrogate used during
challenge testing is referred to as the challenge particulate. The
concentration of the challenge particulate shall be determined using a method
capable of discreetly quantifying the specific microorganism or surrogate used
in the test; gross measurements such as turbidity shall not be used.
(4) The maximum feed water concentration that
can be used during a challenge test shall be based on the detection limit of
the challenge particulate in the filtrate (i.e., filtrate detection limit) and
shall be calculated using the following equation:
Maximum Feed Concentration = 1 x
104 x (Filtrate Detection Limit)
(5) Challenge testing shall be conducted at
the maximum design flow rate for the filter as specified by the
manufacturer.
(6) Each filter
evaluated shall be tested for a duration sufficient to reach 100% of the
terminal pressure drop that establishes the maximum pressure drop under which
the filter may be used to comply with the requirements of this subdivision E
6.
(7) Removal efficiency of a
filter shall be determined from the results of the challenge test and expressed
in terms of log removal values using the following equation:
LRV = LOG10(Cf)
- LOG10(Cp),
where LRV = log removal value demonstrated during challenge
testing;
Cf = the feed concentration measured
during the challenge test; and
Cp = the filtrate concentration
measured during the challenge test.
In applying this equation, the same units shall be used for
the feed and filtrate concentrations. If the challenge particulate is not
detected in the filtrate, then the term Cp shall be set
equal to the detection limit.
(8) Each filter tested shall be challenged
with the challenge particulate during three periods over the filtration cycle:
within two hours of start-up of a new filter; when the pressure drop is between
45% and 55% of the terminal pressure drop; and at the end of the cycle after
the pressure drop has reached 100% of the terminal pressure drop. An LRV shall
be calculated for each of these challenge periods for each filter tested. The
LRV for the filter (LRV filter) shall be assigned the value of the minimum LRV
observed during the three challenge periods for that filter.
(9) If fewer than 20 filters are tested, then
the overall removal efficiency for the filter product line shall be set equal
to the lowest LRV filter among the filters tested. If 20 or more filters are
tested, then the overall removal efficiency for the filter product line shall
be set equal to the 10th percentile of the set of LRV filter values for the
various filters tested. The percentile is defined by (i/(n+1)), where i is the
rank of n individual data points ordered lowest to highest. If necessary, the
10th percentile may be calculated using linear interpolation.
(10) If a previously tested filter is
modified in a manner that could change the removal efficiency of the filter
product line, then challenge testing to demonstrate the removal efficiency of
the modified filter shall be conducted and submitted to the department.
b. Membrane filtration.
(1) The owner receives Cryptosporidium
treatment credit for membrane filtration that meets the criteria of this
subdivision E 6 b. Membrane cartridge filters that meet the definition of
membrane filtration in
12VAC5-590-10 are eligible for
this credit. The level of treatment credit the owner receives is equal to the
lower of the values determined as follows:
(a) The removal efficiency demonstrated
during challenge testing conducted under the conditions in subdivision E 6 b
(2) of this section.
(b) The
maximum removal efficiency that can be verified through direct integrity
testing used with the membrane filtration process under the conditions in
subdivision E 6 b (3) of this section.
(2) Challenge Testing. The membrane used by
the waterworks shall undergo challenge testing to evaluate removal efficiency
and the owner shall report the results of the challenge testing to the
department. Challenge testing shall be conducted according to the criteria in
subdivisions E 6 b (2) (a) through E 6 b (2) (g) of this section. The owner may
use data from challenge testing conducted before January 5, 2006, if the prior
testing was consistent with the following criteria:
(a) Challenge testing shall be conducted on
either a full-scale membrane module, identical in material and construction to
the membrane modules used in the waterworks treatment facility, or a
smaller-scale membrane module, identical in material and similar in
construction to the full-scale module. A module is defined as the smallest
component of a membrane unit in which a specific membrane surface area is
housed in a device with a filtrate outlet structure.
(b) Challenge testing shall be conducted
using Cryptosporidium or a surrogate that is removed no more efficiently than
Cryptosporidium. The organism or surrogate used during challenge testing is
referred to as the challenge particulate. The concentration of the challenge
particulate, in both the feed and filtrate water, shall be determined using a
method capable of discretely quantifying the specific challenge particulate
used in the test; gross measurements such as turbidity shall not be
used.
(c) The maximum feed water
concentration that can be used during a challenge test is based on the
detection limit of the challenge particulate in the filtrate and shall be
determined according to the following equation:
Maximum Feed Concentration = 3.16 x
106 x (Filtrate Detection Limit)
(d) Challenge testing shall be conducted
under representative hydraulic conditions at the maximum design flux and
maximum design process recovery specified by the manufacturer for the membrane
module. Flux is defined as the throughput of a pressure-driven membrane process
expressed as flow per unit of membrane area. Recovery is defined as the
volumetric percent of feed water that is converted to filtrate over the course
of an operating cycle uninterrupted by events such as chemical cleaning or a
solids removal process (i.e., backwashing).
(e) Removal efficiency of a membrane module
shall be calculated from the challenge test results and expressed as a log
removal value according to the following equation:
LRV = LOG10(Cf)
- LOG10(Cp),
where LRV = log removal value demonstrated during the
challenge test;
Cf = the feed concentration measured
during the challenge test; and
Cp = the filtrate concentration
measured during the challenge test.
Equivalent units shall be used for the feed and filtrate
concentrations. If the challenge particulate is not detected in the filtrate,
then the term Cp is set equal to the detection limit for
the purpose of calculating the LRV. An LRV shall be calculated for each
membrane module evaluated during the challenge test.
(f) The removal efficiency of a membrane
filtration process demonstrated during challenge testing shall be expressed as
a log removal value (LRVC-Test). If fewer than 20
modules are tested, then LRVC-Test is equal to the
lowest of the representative LRVs among the modules tested. If 20 or more
modules are tested, then LRVC-Test is equal to the 10th
percentile of the representative LRVs among the modules tested. The percentile
is defined by (i/(n+1)), where i is the rank of n individual data points
ordered lowest to highest. If necessary, the 10th percentile may be calculated
using linear interpolation.
(g) The
challenge test shall establish a QCRV for a nondestructive performance test
that demonstrates the Cryptosporidium removal capability of the membrane
filtration module. This performance test shall be applied to each production
membrane module used by the waterworks that was not directly challenge tested
to verify Cryptosporidium removal capability. Production modules that do not
meet the established QCRV are not eligible for the treatment credit
demonstrated during the challenge test.
(h) If a previously tested membrane is
modified in a manner that could change the removal efficiency of the membrane
or the applicability of the nondestructive performance test and associated
QCRV, then additional challenge testing to demonstrate the removal efficiency
of, and determine a new QCRV for, the modified membrane shall be conducted and
submitted to the department.
(3) Direct integrity testing. The owner shall
conduct direct integrity testing in a manner that demonstrates a removal
efficiency equal to or greater than the removal credit awarded to the membrane
filtration process and meets the requirements described in subdivisions E 6 b
(3) (a) through E 6 b (3) (f) of this section. A direct integrity test is
defined as a physical test applied to a membrane unit to identify and isolate
integrity breaches (i.e., one or more leaks that could result in contamination
of the filtrate).
(a) The direct integrity
test shall be independently applied to each membrane unit in service. A
membrane unit is defined as a group of membrane modules that share common
valving that allows the unit to be isolated from the rest of the waterworks for
the purpose of integrity testing or other maintenance.
(b) The direct integrity method shall have a
resolution of three micrometers or less, where resolution is defined as the
size of the smallest integrity breach that contributes to a response from the
direct integrity test.
(c) The
direct integrity test shall have a sensitivity sufficient to verify the log
treatment credit awarded to the membrane filtration process by the department,
where sensitivity is defined as the maximum log removal value that can be
reliably verified by a direct integrity test. Sensitivity shall be determined
using the approach in either of the following as applicable to the type of
direct integrity test the waterworks uses:
(i) For direct integrity tests that use an
applied pressure or vacuum, the direct integrity test sensitivity shall be
calculated according to the following equation:
LRVDIT =
LOG10(Qp /(VCF x
Qbreach)),
where LRVDIT = the sensitivity of the
direct integrity test;
Qp = total design filtrate flow from
the membrane unit;
Qbreach = flow of water from an
integrity breach associated with the smallest integrity test response that can
be reliably measured; and
VCF = volumetric concentration factor.
The volumetric concentration factor is the ratio of the
suspended solids concentration on the high-pressure side of the membrane
relative to that in the feed water.
(ii) For direct integrity tests that use a
particulate or molecular marker, the direct integrity test sensitivity shall be
calculated according to the following equation:
LRVDIT =
LOG10(Cf) -
LOG10(Cp),
where LRVDIT = the sensitivity of the
direct integrity test;
Cf = the typical feed concentration of
the marker used in the test; and
Cp = the filtrate concentration of the
marker from an integral membrane unit.
(d) The owner shall establish a control limit
within the sensitivity limits of the direct integrity test that is indicative
of an integral membrane unit capable of meeting the removal credit awarded by
the department.
(e) If the result
of a direct integrity test exceeds the control limit established under
subdivision E 6 b (3) (d) of this section, then the owner shall remove the
membrane unit from service. The owner shall conduct a direct integrity test to
verify any repairs, and may return the membrane unit to service only if the
direct integrity test is within the established control limit.
(f) The owner shall conduct direct integrity
testing on each membrane unit at a frequency of not less than once each day
that the membrane unit is in operation. The department may approve less
frequent testing based on demonstrated process reliability, the use of multiple
barriers effective for Cryptosporidium, or reliable process safeguards.
(4) Indirect integrity
monitoring. The owner shall conduct continuous indirect integrity monitoring on
each membrane unit according to the criteria in subdivisions E 6 b (4) (a)
through E 6 b (4) (e). Indirect integrity monitoring is defined as monitoring
some aspect of filtrate water quality that is indicative of the removal of
particulate matter. The owner that implements continuous direct integrity
testing of membrane units in accordance with the criteria in subdivisions E 6 b
(3) (a) through E 6 b (3) (f) of this section is not subject to the
requirements for continuous indirect integrity monitoring. The owner shall
submit a monthly report to the department summarizing all continuous indirect
integrity monitoring results triggering direct integrity testing and the
corrective action that was taken in each case.
(a) Unless the department approves an
alternative parameter, continuous indirect integrity monitoring shall include
continuous filtrate turbidity monitoring.
(b) Continuous monitoring shall be conducted
at a frequency of no less than once every 15 minutes.
(c) Continuous monitoring shall be separately
conducted on each membrane unit.
(d) If indirect integrity monitoring includes
turbidity and if the filtrate turbidity readings are above 0.15 NTU for a
period greater than 15 minutes (i.e., two consecutive 15-minute readings above
0.15 NTU), direct integrity testing shall immediately be performed on the
associated membrane unit as specified in subdivisions E 6 b (3) (a) through E 6
b (3) (f) of this section.
(e) If
indirect integrity monitoring includes an alternative parameter approved by the
department and if the alternative parameter exceeds a control limit approved by
the department for a period greater than 15 minutes, then direct integrity
testing shall immediately be performed on the associated membrane units as
specified in subdivisions E 6 b (3) (a) through E 6 b (3) (f) of this section.
c. Second
stage filtration. The owner receives 0.5-log Cryptosporidium treatment credit
for a separate second stage of filtration that consists of sand, dual media,
GAC, or other fine grain media following granular media filtration if approved
by the department. To be eligible for this credit, the first stage of
filtration shall be preceded by a coagulation step and both filtration stages
shall treat the entire water treatment treatment plant flow taken from a
surface water source, a GUDI source, or both. A cap, such as GAC, on a single
stage of filtration is not eligible for this credit. The department shall
approve the treatment credit based on an assessment of the design
characteristics of the filtration process.
d. Slow sand filtration as secondary filter.
The owner is eligible to receive 2.5-log Cryptosporidium treatment credit for a
slow sand filtration process that follows a separate stage of filtration if
both filtration stages treat the entire water treatment plant flow taken from a
surface water source, a GUDI source, or both and no residual disinfectant is
present in the influent water to the slow sand filtration process. The
department shall approve the treatment credit based on an assessment of the
design characteristics of the filtration process. This subdivision does not
apply to treatment credit awarded to slow sand filtration used as a primary
filtration process.
7.
Inactivation toolbox components.
a.
Calculation of CT values.
(1) CT is the
product of the disinfectant contact time (T, in minutes) and disinfectant
concentration (C, in milligrams per liter). The owner of a waterworks with
treatment credit for chlorine dioxide or ozone under subdivision E 7 b of this
section shall calculate CT at least once each day, with both C and T measured
during peak hourly flow in accordance with the procedure listed in
12VAC5-590-500.
(2) A waterworks with several disinfection
segments in sequence may calculate CT for each segment, where a disinfection
segment is defined as a treatment unit process with a measurable residual
disinfectant level and a liquid volume. Under this approach, the owner shall
add the Cryptosporidium CT values in each segment to determine the total CT for
the treatment plant.
b.
CT values for chlorine dioxide and ozone.
(1)
The owner receives the Cryptosporidium treatment credit listed in Table 401.5
by meeting the corresponding chlorine dioxide CT value for the applicable water
temperature, as described in subdivision E 7 a of this section.
|
TABLE 401.5
CT Values (mg-min/L) for Cryptosporidium Inactivation
by Chlorine Dioxidea
|
|
WATER
TEMPERATURE,oC
|
|
LOG CREDIT
|
<0.5
|
1
|
2
|
3
|
5
|
7
|
|
0.25
|
159
|
153
|
140
|
128
|
107
|
90
|
|
0.5
|
319
|
305
|
279
|
256
|
214
|
180
|
|
1.0
|
637
|
610
|
558
|
511
|
429
|
360
|
|
1.5
|
956
|
915
|
838
|
767
|
643
|
539
|
|
2.0
|
1275
|
1220
|
1117
|
1023
|
858
|
719
|
|
2.5
|
1594
|
1525
|
1396
|
1278
|
1072
|
899
|
|
3.0
|
1912
|
1830
|
1675
|
1534
|
1286
|
1079
|
|
|
WATER
TEMPERATURE,oC
|
|
LOG CREDIT
|
10
|
15
|
20
|
25
|
30
|
|
0.25
|
69
|
45
|
29
|
19
|
12
|
|
0.5
|
138
|
89
|
58
|
38
|
24
|
|
1.0
|
277
|
179
|
116
|
75
|
49
|
|
1.5
|
415
|
268
|
174
|
113
|
73
|
|
2.0
|
553
|
357
|
232
|
150
|
98
|
|
2.5
|
691
|
447
|
289
|
188
|
122
|
|
3.0
|
830
|
536
|
347
|
226
|
147
|
|
aThe owner may use this
equation to determine log credit between the indicated values: Log credit =
(0.001506×(1.09116)Temp)×
CT.
|
(2)
The owner receives the Cryptosporidium treatment credit listed in Table 401.6
by meeting the corresponding ozone CT values for the applicable water
temperature, as described in subdivision E 7 a of this section.
|
TABLE 401.6
CT Values (mg-min/L) for Cryptosporidium Inactivation
by Ozonea
|
|
LOG CREDIT
|
WATER TEMPERATURE, °C
|
|
<0.5
|
1
|
2
|
3
|
5
|
7
|
10
|
15
|
20
|
25
|
30
|
|
0.25
|
6.0
|
5.8
|
5.2
|
4.8
|
4.0
|
3.3
|
2.5
|
1.6
|
1.0
|
0.6
|
0.39
|
|
0.5
|
12
|
12
|
10
|
9.5
|
7.9
|
6.5
|
4.9
|
3.1
|
2.0
|
1.2
|
0.78
|
|
1.0
|
24
|
23
|
21
|
19
|
16
|
13
|
9.9
|
6.2
|
3.9
|
2.5
|
1.6
|
|
1.5
|
36
|
35
|
31
|
29
|
24
|
20
|
15
|
9.3
|
5.9
|
3.7
|
2.4
|
|
2.0
|
48
|
46
|
42
|
38
|
32
|
26
|
20
|
12
|
7.8
|
4.9
|
3.1
|
|
2.5
|
60
|
58
|
52
|
48
|
40
|
33
|
25
|
16
|
9.8
|
6.2
|
3.9
|
|
3.0
|
72
|
69
|
63
|
57
|
47
|
39
|
30
|
19
|
12
|
7.4
|
4.7
|
|
aThe owner may use this
equation to determine log credit between the indicated values: Log credit =
(0.0397×(1.09757)Temp)× CT.
|
c. UV light. The owner receives
Cryptosporidium, Giardia lamblia, and virus treatment credits for UV light
reactors by achieving the corresponding UV dose values shown in subdivision E 7
c (1) of this section. The owner shall validate and monitor UV reactors as
described in subdivisions E 7 c (2) and E 7 c (3) of this section to
demonstrate that they are achieving a particular UV dose value for treatment
credit.
(1) UV dose table. The treatment
credits listed in Table 401.7 are for UV light at a wavelength of 254 nm as
produced by a low-pressure mercury vapor lamp. To receive treatment credit for
other lamp types, the owner shall demonstrate an equivalent germicidal dose
through reactor validation testing as described in subdivision E 7 c (2) of
this section. The UV dose values listed in Table 401.7 are applicable only to
post-filter applications of UV in filtered waterworks.
|
TABLE 401.7
UV Doses for Cryptosporidium, Giardia lamblia and
Virus Inactivation Credit
|
|
LOG CREDIT
|
CRYPTOSPORIDIUM UV DOSE (mJ/cm2)
|
GIARDIA LAMBLIA UV DOSE (mJ/cm2)
|
VIRUS UV DOSE
(mJ/cm2)
|
|
0.5
|
1.6
|
1.5
|
39
|
|
1.0
|
2.5
|
2.1
|
58
|
|
1.5
|
3.9
|
3.0
|
79
|
|
2.0
|
5.8
|
5.2
|
100
|
|
2.5
|
8.5
|
7.7
|
121
|
|
3.0
|
12
|
11
|
143
|
|
3.5
|
15
|
15
|
163
|
|
4.0
|
22
|
22
|
186
|
(2)
Reactor validation testing. The owner shall use UV reactors that have undergone
validation testing to determine the operating conditions under which the
reactor delivers the UV dose required in subdivision E 7 c (1) of this section
(i.e., validated operating conditions). These operating conditions shall
include flow rate, UV intensity as measured by a UV sensor, and UV lamp status.
(a) When determining validated operating
conditions, the owner shall account for the following factors:
(i) UV absorbance of the water;
(ii) lamp fouling and aging;
(iii) measurement uncertainty of online
sensors;
(iv) UV dose distributions
arising from the velocity profiles through the reactor;
(v) failure of UV lamps or other critical
waterworks components; and
(vi)
inlet and outlet piping or channel configurations of the UV reactor.
(b) Validation testing shall
include the following: full-scale testing of a reactor that conforms uniformly
to the UV reactors used by the waterworks and inactivation of a test
microorganism whose dose-response characteristics have been quantified with a
low-pressure mercury vapor lamp.
(c) UV reactor validation testing shall be in
accordance with EPA's recommended validation protocol for UV reactors, as
described in EPA's "Ultraviolet Disinfection Guidance Manual for the Final Long
Term 2 Enhanced Surface Water Treatment Rule," November 2006, EPA Office of
Water. Alternative protocols may be considered for approval by the department
on a case-by-case basis.
(d)
Validation testing, whether onsite or offsite, shall be performed by a third
party independent of the UV reactor manufacturer and the owner to ensure that
validation testing and data analysis are conducted in a technically sound
manner without bias.
(e) To receive
credit for lamp types other than low-pressure types, the owner shall
demonstrate an equivalent germicidal dose through reactor validation
testing.
(f) A validation report
shall be submitted and approved by the department to receive disinfection
credit.
(3) UV reactor
monitoring.
(a) The owner shall monitor the UV
reactors to determine if the reactors are operating within validated conditions
as determined under subdivision E 7 c (2) of this section. This monitoring
shall include UV intensity as measured by a UV sensor, flow rate, lamp status,
and other parameters the department designates based on UV reactor operation.
The owner shall verify the calibration of UV sensors and shall recalibrate
sensors in accordance with a protocol approved by the department.
(b) To receive treatment credit for UV light,
the owner shall treat at least 95% of the water delivered to the public during
each month by the UV reactors operating within validated conditions for the
required UV dose as described in subdivisions E 7 c (1) and E 7 c (2) of this
section. The owner shall demonstrate compliance with this condition by the
monitoring required under subdivision E 7 c (3) (a) of this section.