Utah Admin. Code R315-261-1033 - Air Emission Standards for Process Vents - Closed-Vent Systems and Control Devices

(a)
(1) The remanufacturer or other person that stores or treats the hazardous secondary materials in hazardous secondary material management units using closed-vent systems and control devices used to comply with Rule R315-261 shall comply with Section R315-261-1033.
(2) Reserved
(b) A control device involving vapor recovery, for example, a condenser or adsorber, shall be designed and operated to recover the organic vapors vented to it with an efficiency of 95 weight percent or greater unless the total organic emission limits of Subsection R315-261-1032(a)(1) for the affected process vents can be attained at an efficiency less than 95 weight percent.
(c) An enclosed combustion device, for example, a vapor incinerator, boiler, or process heater, shall be designed and operated to reduce the organic emissions vented to it by 95 weight percent or greater; to achieve a total organic compound concentration of 20 ppmv, expressed as the sum of the actual compounds, not carbon equivalents, on a dry basis corrected to 3% oxygen; or to provide a minimum residence time of 0.50 seconds at a minimum temperature of 760 deg. C. If a boiler or process heater is used as the control device, then the vent stream shall be introduced into the flame zone of the boiler or process heater.
(d)
(1) A flare shall be designed for and operated with no visible emissions as determined by the methods specified in Subsection R315-261-1033(e)(1), except for periods not to exceed a total of five minutes during any two consecutive hours.
(2) A flare shall be operated with a flame always present, as determined by the methods specified in Subsection R315-261-1033(f)(2)(iii).
(3) A flare shall be used only if the net heating value of the gas being combusted is 11.2 MJ/scm, 300 Btu/scf, or greater if the flare is steam-assisted or air-assisted; or if the net heating value of the gas being combusted is 7.45 MJ/scm, 200 Btu/scf, or greater if the flare is nonassisted. The net heating value of the gas being combusted shall be determined by the methods specified in Subsection R315-261-1033(e)(2).
(4)
(i) A steam-assisted or nonassisted flare shall be designed for and operated with an exit velocity, as determined by the methods specified in Subsection R315-261-1033(e)(3), less than 18.3 m/s, 60 ft/s, except as provided in Subsections R315-261-1033(d)(4)(ii) and R315-261-1033(d)(4)(iii).
(ii) A steam-assisted or nonassisted flare designed for and operated with an exit velocity, as determined by the methods specified in Subsection R315-261-1033(e)(3), equal to or greater than 18.3 m/s, 60 ft/s, but less than 122 m/s, 400 ft/s, is allowed if the net heating value of the gas being combusted is greater than 37.3 MJ/scm, 1,000 Btu/scf.
(iii) A steam-assisted or nonassisted flare designed for and operated with an exit velocity, as determined by the methods specified in Subsection R315-261-1033(e)(3), less than the velocity, Vmax, as determined by the method specified in Subsection R315-261-1033(e)(4) and less than 122 m/s, 400 ft/s is allowed.
(5) An air-assisted flare shall be designed and operated with an exit velocity less than the velocity, Vmax, as determined by the method specified in Subsection R315-261-1033(e)(5).
(6) A flare used to comply with Section R315-261-1033 shall be steam-assisted, air-assisted, or nonassisted.
(e)
(1) Reference Method 22 in 40 CFR part 60 shall be used to determine the compliance of a flare with the visible emission requirements of Sections R315-261-1030 through R315-261-1035. The observation period is two hours and shall be used according to Method 22.
(2) The net heating value of the gas being combusted in a flare shall be calculated using the equation found in 40 CFR 261.1033(e)(2) 2015 ed is incorporated by reference.

Where:

HT = Net heating value of the sample, MJ/scm; where the net enthalpy per mole of offgas is based on combustion at 25 degrees C and 760 mm Hg, but the standard temperature for determining the volume corresponding to 1 mol is 20 degrees C;

K = Constant, 1.74 H 10-7, 1/ppm, g mol/scm, MJ/kcal, where standard temperature for g mol/scm is 20 deg. C;

Ci = Concentration of sample component i in ppm on a wet basis, as measured for organics by Reference Method 18 in 40 CFR part 60 and measured for hydrogen and carbon monoxide by ASTM D 1946-82, incorporated by reference as specified in Section R315-260-11; and

Hi = Net heat of combustion of sample component i, kcal/9 mol at 25 degrees C and 760 mm Hg. The heats of combustion may be determined using ASTM D 2382-83, incorporated by reference as specified in Section R315-260-11, if published values are not available or cannot be calculated.

(3) The actual exit velocity of a flare shall be determined by dividing the volumetric flow rate, in units of standard temperature and pressure, as determined by Reference Methods 2, 2A, 2C, or 2D in 40 CFR part 60 as appropriate, by the unobstructed, free, cross-sectional area of the flare tip.
(4) The maximum allowed velocity in m/s, Vmax, for a flare complying with Subsection R315-261-1033(d)(4)(iii) shall be determined by the following equation:

Log10(Vmax) = (HT + 28.8)/31.7

Where:

28. 8 = Constant;

31. 7 = Constant;

HT = The net heating value as determined in Subsection R315-261-1033(e)(2).

(5) The maximum allowed velocity in m/s, Vmax, for an air-assisted flare shall be determined by the following equation: Vmax = 8.706 + 0.7084 (Ht)

Where:

8.706 = Constant;

0.7084 = Constant;

HT = The net heating value as determined in Subsection R315-261-1033(e)(2).

(f) The remanufacturer or other person that stores or treats the hazardous secondary material shall monitor and inspect each control device required to comply with Section R315-261-1033 to ensure proper operation and maintenance of the control device by implementing the requirements in Subsections R315-261-1033(f)(1) through R315-261-1033(f)(3):
(1) Install, calibrate, maintain, and operate according to the manufacturer's specifications a flow indicator that provides a record of vent stream flow from each affected process vent to the control device at least once each hour. The flow indicator sensor shall be installed in the vent stream at the nearest feasible point to the control device inlet but before the point that the vent streams are combined.
(2) Install, calibrate, maintain, and operate according to the manufacturer's specifications a device to continuously monitor control device operation as specified in Subsections R315-261-1033(f)(2)(i) through R315-261-1033(f)(2)(vii):
(i) For a thermal vapor incinerator, a temperature monitoring device equipped with a continuous recorder. The device shall have an accuracy of plus or minus 1% of the temperature being monitored in degrees C or plus or minus 0.5 degrees C, whichever is greater. The temperature sensor shall be installed at a location in the combustion chamber downstream of the combustion zone.
(ii) For a catalytic vapor incinerator, a temperature monitoring device equipped with a continuous recorder. The device shall be capable of monitoring temperature at two locations and have an accuracy of plus or minus 1% of the temperature being monitored in degrees C or plus or minus 0.5 degrees C, whichever is greater. One temperature sensor shall be installed in the vent stream at the nearest feasible point to the catalyst bed inlet and a second temperature sensor shall be installed in the vent stream at the nearest feasible point to the catalyst bed outlet.
(iii) For a flare, a heat sensing monitoring device equipped with a continuous recorder that shows the continuous ignition of the pilot flame.
(iv) For a boiler or process heater having a design heat input capacity less than 44 MW, a temperature monitoring device equipped with a continuous recorder. The device shall have an accuracy of plus or minus 1% of the temperature being monitored in degrees C or plus or minus 0.5 degrees C, whichever is greater. The temperature sensor shall be installed at a location in the furnace downstream of the combustion zone.
(v) For a boiler or process heater having a design heat input capacity greater than or equal to 44 MW, a monitoring device equipped with a continuous recorder to measure a parameters that shows good combustion operating practices are being used.
(vi) For a condenser, either:
(A) a monitoring device equipped with a continuous recorder to measure the concentration level of the organic compounds in the exhaust vent stream from the condenser; or
(B) a temperature monitoring device equipped with a continuous recorder. The device shall be capable of monitoring temperature with an accuracy of plus or minus 1% of the temperature being monitored in degrees Celsius, deg. C, or plus or minus 0.5 deg. C, whichever is greater. The temperature sensor shall be installed at a location in the exhaust vent stream from the condenser exit, that is, product side.
(vii) For a carbon adsorption system that regenerates the carbon bed directly in the control device such as a fixed-bed carbon adsorber, either:
(A) a monitoring device equipped with a continuous recorder to measure the concentration level of the organic compounds in the exhaust vent stream from the carbon bed; or
(B) a monitoring device equipped with a continuous recorder to measure a parameter that shows the carbon bed is regenerated on a regular, predetermined time cycle.
(3) Inspect the readings from each monitoring device required by Subsections R315-261-1033(f)(1) and R315-261-1033(f)(2) at least once each operating day to check control device operation and, if necessary, immediately implement the corrective measures necessary to ensure the control device operates in compliance with the requirements of Section R315-261-1033.
(g) A remanufacturer or other person that stores or treats hazardous secondary material in a hazardous secondary material management unit using a carbon adsorption system such as a fixed-bed carbon adsorber that regenerates the carbon bed directly onsite in the control device shall replace the existing carbon in the control device with fresh carbon at a regular, predetermined time interval that is no longer than the carbon service life established as a requirement of Subsection R315-261-1035(b)(4)(iii)(F).
(h) A remanufacturer or other person that stores or treats hazardous secondary material in a hazardous secondary material management unit using a carbon adsorption system such as a carbon canister that does not regenerate the carbon bed directly onsite in the control device shall replace the existing carbon in the control device with fresh carbon on a regular basis by using one of the procedures in Subsections R315-261-1033(h)(1) through R315-261-1033(h)(2):
(1) Monitor the concentration level of the organic compounds in the exhaust vent stream from the carbon adsorption system on a regular schedule, and replace the existing carbon with fresh carbon immediately if carbon breakthrough is indicated. The monitoring frequency shall be daily or at an interval no greater than 20% of the time required to consume the total carbon working capacity established as a requirement of Subsection R315-261-1035(b)(4)(iii)(G), whichever is longer.
(2) Replace the existing carbon with fresh carbon at a regular, predetermined time interval that is less than the design carbon replacement interval established as a requirement of Subsection R315-261-1035(b)(4)(iii)(G).
(i) An alternative operational or process parameter may be monitored if it can be demonstrated that another parameter shall ensure that the control device is operated in conformance with these standards and the control device's design specifications.
(j) A remanufacturer or other person that stores or treats hazardous secondary material at an affected facility seeking to comply with Rule R315-261 by using a control device other than a thermal vapor incinerator, catalytic vapor incinerator, flare, boiler, process heater, condenser, or carbon adsorption system shall develop documentation including enough information to describe the control device operation and identify the process parameter or parameters that show proper operation and maintenance of the control device.
(k) A closed-vent system shall meet either of the design requirements in Subsection R315-261-1033(k)(1) or R315-261-1033(k)(2):
(1) A closed-vent system shall be designed to operate with no detectable emissions, as shown by an instrument reading of less than 500 ppmv above background as determined by the procedure in Subsection R315-261-1034(b), and by visual inspections; or
(2) A closed-vent system shall be designed to operate at a pressure below atmospheric pressure. The system shall be equipped with at least one pressure gauge or other pressure measurement device that can be read from a readily accessible location to verify that negative pressure is being maintained in the closed-vent system if the control device is operating.
(l) The remanufacturer or other person that stores or treats the hazardous secondary material shall monitor and inspect each closed-vent system required to comply with Section R315-261-1033 to ensure proper operation and maintenance of the closed-vent system by implementing the requirements in Subsections R315-261-1033(l)(1) through R315-261-1033(l)(3):
(1) Each closed-vent system that is used to comply with Subsection R315-261-1033(k)(1) shall be inspected and monitored in accordance with the requirements in Subsections R315-261-1033(l)(1)(i) through R315-261-1033(l)(1)(iv):
(i) An initial leak detection monitoring of the closed-vent system shall be conducted by the remanufacturer or other person that stores or treats the hazardous secondary material on or before the date that the system becomes subject to Section R315-261-1033. The remanufacturer or other person that stores or treats the hazardous secondary material shall monitor the closed-vent system components and connections using the procedures specified in Subsection R315-261-1034(b) to demonstrate that the closed-vent system operates with no detectable emissions, as shown by an instrument reading of less than 500 ppmv above background.
(ii) After initial leak detection monitoring required in Subsection R315-261-1033(l)(1)(i), the remanufacturer or other person that stores or treats the hazardous secondary material shall inspect and monitor the closed-vent system as follows:
(A) Closed-vent system joints, seams, or other connections that are permanently or semi-permanently sealed, for example, a welded joint between two sections of hard piping or a bolted and gasketed ducting flange, shall be visually inspected at least once per year to check for defects that could result in air pollutant emissions. The remanufacturer or other person that stores or treats the hazardous secondary material shall monitor a component or connection using the procedures specified in Subsection R315-261-1034(b) to demonstrate that it operates with no detectable emissions following any time the component is repaired or replaced, for example, a section of damaged hard piping is replaced with new hard piping, or the connection is unsealed, for example, a flange is unbolted.
(B) Closed-vent system components or connections other than those specified in Subsection R315-261-1033(l)(1)(ii)(A) shall be monitored annually and at other times as requested by the director, except as provided for in Subsection R315-261-1033(o), using the procedures specified in Subsection R315-261-1034(b) to demonstrate that the components or connections operate with no detectable emissions.
(iii) In the event that a defect or leak is detected, the remanufacturer or other person that stores or treats the hazardous secondary material shall repair the defect or leak in accordance with the requirements of Subsection R315-261-1033(l)(3).
(iv) The remanufacturer or other person that stores or treats the hazardous secondary material shall maintain a record of the inspection and monitoring in accordance with the requirements specified in Section R315-261-1035.
(2) Each closed-vent system that is used to comply with Subsection R315-261-1033(k)(2) shall be inspected and monitored in accordance with the requirements in Subsections R315-251-1033(1)(2)(i) through R315-261-1033(1)(2)(iv):
(i) The closed-vent system shall be visually inspected by the remanufacturer or other person that stores or treats the hazardous secondary material to check for defects that could result in air pollutant emissions. Defects include visible cracks, holes, or gaps in ductwork or piping or loose connections.
(ii) The remanufacturer or other person that stores or treats the hazardous secondary material shall perform an initial inspection of the closed-vent system on or before the date that the system becomes subject to Section R315-261-1033. Thereafter, the remanufacturer or other person that stores or treats the hazardous secondary material shall perform the inspections at least once each year.
(iii) In the event that a defect or leak is detected, the remanufacturer or other person that stores or treats the hazardous secondary material shall repair the defect in accordance with the requirements of Subsection R315-261-1033(l)(3).
(iv) The remanufacturer or other person that stores or treats the hazardous secondary material shall maintain a record of the inspection and monitoring in accordance with the requirements specified in Section R315-261-1035.
(3) The remanufacturer or other person that stores or treats the hazardous secondary material shall repair the detected defects in accordance with Subsections R315-261-1033(l)(3)(i) through R315-261-1033(l)(3)(iv):
(i) Detectable emissions, as shown by visual inspection, or by an instrument reading greater than 500 ppmv above background, shall be controlled as soon as practicable, but before 15 calendar days after the emission is detected, except as provided for in Subsection R315-261-1033(l)(3)(iii).
(ii) A first attempt at repair shall be made no later than five calendar days after the emission is detected.
(iii) Delay of repair of a closed-vent system where leaks have been detected is allowed if the repair is technically infeasible without a process unit shutdown, or if the remanufacturer or other person that stores or treats the hazardous secondary material determines that emissions resulting from immediate repair would be greater than the fugitive emissions likely to result from delay of repair. Repair of the equipment shall be finished by the end of the next process unit shutdown.
(iv) The remanufacturer or other person that stores or treats the hazardous secondary material shall maintain a record of the defect repair in accordance with the requirements specified in Section R315-261-1035.
(m) Closed-vent systems and control devices used to comply with Sections R315-261-1030 through R315-261-1035 shall be always be operated when emissions may be vented to them.
(n) The owner or operator using a carbon adsorption system to control air pollutant emissions shall document that any carbon that is a hazardous waste and that is removed from the control device is managed in in accordance with Subsection R315-261-1033(n)(1), R315-261-1033(n)(2), or R315-261-1033(n)(3), regardless of the average volatile organic concentration of the carbon:
(1) Regenerated or reactivated in a thermal treatment unit that meets one of the requirements in Subsections R315-261-1033(n)(1)(i) through R315-261-1033(n)(1)(iii):
(i) The owner or operator of the unit has been issued a final permit under Rule R315-270 that implements the requirements of Sections R315-264-600 through R315-264-603; or
(ii) The unit is equipped with and operating air emission controls in accordance with the applicable requirements of Sections R315-261-1030 through R315-261-1035 and R315-261-1080 through R315-261-1089 or R315-265-1030 through R315-265-1035 and R315-265-1080 through R315-265-1090; or
(iii) The unit is equipped with and operating air emission controls in accordance with a national emission standard for hazardous air pollutants under 40 CFR part 61 or 40 CFR part 63.
(2) Incinerated in a hazardous waste incinerator that the owner or operator either:
(i) has been issued a final permit under Rule R315-270 that implements the requirements of Sections R315-264-340 through R315-264-351; or
(ii) has designed and operates the incinerator in accordance with the interim status requirements of Sections R315-265-340 through R315-265-352.
(3) Burned in a boiler or industrial furnace that the owner or operator either:
(i) has been issued a final permit under Rule R315-270 that implements the requirements of Sections R315-266-100 through R315-266-112; or
(ii) has designed and operates the boiler or industrial furnace in accordance with the interim status requirements of Sections R315-266-100 through R315-266-112.
(o) Any components of a closed-vent system that are designated, as described in Subsection R315-261-1035(c)(9), as unsafe to monitor are exempt from the requirements of Subsection R315-261-1033(l)(1)(ii)(B) if:
(1) the remanufacturer or other person that stores or treats the hazardous secondary material in a hazardous secondary material management unit using a closed-vent system determines that the components of the closed-vent system are unsafe to monitor because monitoring personnel would be exposed to an immediate danger as a result of complying with Subsection R315-261-1033(l)(1)(ii)(B); and
(2) the remanufacturer or other person that stores or treats the hazardous secondary material in a hazardous secondary material management unit using a closed-vent system adheres to a written plan that requires monitoring the closed-vent system components using the procedure specified in Subsection R315-261-1033(l)(1)(ii)(B) as often as practicable during safe-to-monitor times.

Notes

Utah Admin. Code R315-261-1033
Adopted by Utah State Bulletin Number 2016-9, effective 4/15/2016 Amended by Utah State Bulletin Number 2025-02, effective 1/13/2025

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.