Fla. Admin. Code Ann. R. 64E-5.1408 - Fire Protection
(1) The
radiation room at a panoramic irradiator must have heat and smoke detectors.
The detectors must activate an audible alarm. The alarm must be capable of
alerting a person who is prepared to summon assistance promptly. The sources
must become fully shielded automatically and the air handling systems within
the radiation room must be disabled automatically if a fire is
detected.
(2) The radiation room at
a panoramic irradiator must be equipped with a fire suppression or
extinguishing system capable of extinguishing a fire without the entry of
personnel into the room. The system for the radiation room must have a shut-off
valve to control flooding into unrestricted areas.